IMMERSION SENSOR
GENERAL
T7005, T7006, T7007, and T7008 Platinum Sensors (“Sensors”) monitor temperatures in building management control applications, including Direct Digital Control systems. They are designed for a variety of media such as air, liquid, and steam and can be used with EXCEL 5000 Controllers, DELTA 540 and 541 Data Gathering Panels, DeltaNet R7044 Excel Plus Controllers, and DeltaNet MicroCel™ and MacroCel™Controllers.
Each Sensor consists of a platinum-film resistance element on a ceramic chip and is overlaid with protective glass to ensure long-term reliability. Platinum element resistance varies directly with temperature change. Sensors are calibrated to a very close tolerance by double laser trimming of the element. This method of calibration eliminates field calibration.
Copyright © 1997 Honeywell Inc. • All Rights Reserved
74-2921-1
T7005, T7006, T7007, AND T7008 PLATINUM SENSORS
DESCRIPTION
T7005, T7006, T7007, and T7008 Platinum Sensors (“Sensors”) monitor temperatures in building management control applications, including Direct Digital Control systems. They are designed for a variety of media such as air, liquid, and steam.
Dimensions in Inches (Millimeters):
3-1/8  (79.5)
SPECIFICATIONS
Models:
T7005 Space Sensor:
The T7005 Space Sensor monitors temperature in a room or area of a building. The platinum sensing element provides fast response to temperature changes. Any Honeywell T7000 Standard Series no display (blank) cover can be used. Indicate cover selection when ordering sensor.
T7006 Duct Sensor:
The T7006 Duct Sensor measures air temperature in a duct. The platinum sensing element is in the tip of a brass probe.
Sensor with 11-7/8-in. (301.6-mm) probeSensor with 4-3/8-in. (111.1-mm) probe
T7007 Remote Bulb Sensor:
The T7007 Remote Bulb Sensor measures the temperature in applications where other sensors are not appropriate such as outdoor air temperature and strap-on pipe sensing. The sensor can also be used in ducts where standard duct sensors are not practical. The platinum sensing element is in a sealed probe attached to an oil resistant cable.
T7008 Immersion Sensor:
The T7008 Immersion Sensors detect temperatures of heated or chilled water, or other fluids. The platinum sensing element is in the tip of a sealed, corrosion­resistant brass probe. The T7008 sensors have 1/2 in—14 NPSC straight pipe threads and mounts in a well for tank or pipe installation.
T7008A1042 High Temperature SensorT7008A1059 Chilled Water Sensor-higher accuracy
sensing element, hermetically sealed to prevent damage due to moisture from condensation.
2-1/8
(54)
2-1/8
(54)
3/8
(10)
1-13/16
(46)
T7006C: 11-7/8 (301.6) T7006D: 4-3/8 (111.1)
2-5/8 (67)
1/2"-14 NPSL 
STRAIGHT PIN 
THREADS
1-3/8
(35)
T7005
3/8 (10)
T7006
T7007
5 (127)
T7008
3/8 (10)
4
(102)
34-1/2 (877)
(102)
4
2-1/8
(54)
2-1/8
(54)
C3963-3
74-2921—1
2
T7005, T7006, T7007, AND T7008 PLATINUM SENSORS
Sensor Specifications:
Models
T7008 Immersion Sensor
Data
Application Room and area
Mounting Directly on wall Directly on duct Sun Shield/Bulb
Lead Wires Two 22 AWG (0.38 sq mm) wires for
Operating Temperature
Ambient Humidity 95% rh, noncondensing 100% Condensing Coefficient 4.8 ohms/F (8.6 ohms/K) — positive temperature coefficient Sensing Element Platinum-Film Platinum-film in
Sensor Resistance
T7005 Space
Sensor
air temperatures
low resistance splicing
35 to 149F (1.7 to 65C)
3474 ohms at 75F (23.9C)
T7006C&D Duct
Sensor
Air temperature in ducts
–40 to 160F
(–40 to 71C)
brass tube
T7007 Remote
Bulb Sensor High Temperature Chilled Water
Outdoor air and pipe temperature sensing
Holder for outdoor air use, or Strap­on Kit or clamp on pipe sensing
Oil resistance cable with two 18 AWG (0.81 sq mm) wires for low resistance splicing
Platinum-film Platinum-film in brass tube
High temperature fluid system such as hot water
1/2 in. — NPSC straight pipe threads into well
Two 18 AWG (0.81 sq mm) wires for low resistance splicing
70 to 392F (–21 to 200C)
Fluid systems requiring high or accuracy such as chilled water or where condensation in the sensor may occur
Two 18 AWG (0.81 sq mm) wires for low resistance splicing
20 to 225F (6.7 to 108C)
Accessories:
T7005 Space Sensor:
Cover, Satin Chrome:
Vertical Mount with Logo, 14004406-300Horizontal Mount with Logo, 14004406-400Vertical or Horizontal no Logo, 14004406-800
Cover, Beige:
Vertical Mount with Logo, 14004407-300 Horizontal Mount with Logo, 14004407-400
Vertical or Horizontal no Logo, 14004407-800 Finish Plate, Black: 14002136-004 Finish Plate, Beige: 14002136-005 Wall Mounting Ring: 14004458-001 Adapter Plate: 14001496-001 Standoff Ring: 14000885-005
T7007 Remote Bulb Sensor:
Installation Kit (all pipes): 14503800 Installation Kit (uninsulated pipe): 14503801 Sun Shield/Bulb Holder: 107323A
T7008 Immersion Sensor:
Copper Well: 23904A Heat Conductive Compound (required for use with well):
107408 (4 oz) or equivalent
3
74-2921—1
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524
Honeywell Latin American Division
Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
Honeywell Europe S.A.
3 Avenue du Bourget 1140 Brussels Belgium
Honeywell Asia Pacific Inc.
Room 3213-3225 Sun Hung kai Centre No. 30 Harbour Road Wanchai Hong Kong
74-2921—1 Rev. 4-97
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers