T7005, T7006, T7007, a
T7005
SPACE SENSOR
T7008 Platinum Senso
SPECIFICATION DATA
FEATURES
• Fast response
• Precise temperature 
measurement
• EXCEL 5000 
DeltaNet system compatibility
T7006
DUCT SENSOR
®
, DELTA, and
REMOTE BULB SENSOR
T7007
T7008
IMMERSION SENSOR
GENERAL
T7005, T7006, T7007, and T7008 Platinum Sensors (“Sensors”) monitor 
temperatures in building management control applications, including Direct Digital 
Control systems. They are designed for a variety of media such as air, liquid, and 
steam and can be used with EXCEL 5000 Controllers, DELTA 540 and 541 Data 
Gathering Panels, DeltaNet R7044 Excel Plus Controllers, and DeltaNet MicroCel™ 
and MacroCel™Controllers.
Each Sensor consists of a platinum-film resistance element on a ceramic chip and 
is overlaid with protective glass to ensure long-term reliability. Platinum element 
resistance varies directly with temperature change. Sensors are calibrated to a very 
close tolerance by double laser trimming of the element. This method of calibration 
eliminates field calibration.
Copyright © 1997 Honeywell Inc.  •  All Rights Reserved
74-2921-1

T7005, T7006, T7007, AND T7008 PLATINUM SENSORS
DESCRIPTION
T7005, T7006, T7007, and T7008 Platinum Sensors 
(“Sensors”) monitor temperatures in building management 
control applications, including Direct Digital Control systems. 
They are designed for a variety of media such as air, liquid, 
and steam.
Dimensions in Inches (Millimeters):
3-1/8  
(79.5)
SPECIFICATIONS
Models:
❑ T7005 Space Sensor:
The T7005 Space Sensor monitors temperature in a room 
or area of a building. The platinum sensing element 
provides fast response to temperature changes. Any 
Honeywell T7000 Standard Series no display (blank) 
cover can be used. Indicate cover selection when 
ordering sensor.
T7006 Duct Sensor:
The T7006 Duct Sensor measures air temperature in a 
duct. The platinum sensing element is in the tip of a 
brass probe.
❑ Sensor with 11-7/8-in. (301.6-mm) probe 
❑ Sensor with 4-3/8-in. (111.1-mm) probe
❑ T7007 Remote Bulb Sensor:
The T7007 Remote Bulb Sensor measures the 
temperature in applications where other sensors are not 
appropriate such as outdoor air temperature and strap-on 
pipe sensing. The sensor can also be used in ducts where 
standard duct sensors are not practical. The platinum 
sensing element is in a sealed probe attached to an oil 
resistant cable.
T7008 Immersion Sensor:
The T7008 Immersion Sensors detect temperatures of 
heated or chilled water, or other fluids. The platinum 
sensing element is in the tip of a sealed, corrosionresistant brass probe. The T7008 sensors have 1/2 in—14 
NPSC straight pipe threads and mounts in a well for tank 
or pipe installation.
❑ T7008A1042 High Temperature Sensor 
❑ T7008A1059 Chilled Water Sensor-higher accuracy
sensing element, hermetically sealed to prevent 
damage due to moisture from condensation.
2-1/8
(54)
2-1/8
(54)
3/8
(10)
1-13/16
(46)
T7006C: 11-7/8 (301.6) 
 T7006D: 4-3/8 (111.1)
2-5/8 (67)
1/2"-14 NPSL 
STRAIGHT PIN 
THREADS
1-3/8
(35)
T7005
3/8 (10)
T7006
T7007
5 (127)
T7008
3/8 (10)
4
(102)
34-1/2 (877)
(102)
4
2-1/8
(54)
2-1/8
(54)
C3963-3
74-2921—1
2

T7005, T7006, T7007, AND T7008 PLATINUM SENSORS
Sensor Specifications:
Models
T7008 Immersion Sensor
Data
Application Room and area
Mounting Directly on wall Directly on duct Sun Shield/Bulb
Lead Wires Two 22 AWG (0.38 sq mm) wires for
Operating 
Temperature
Ambient Humidity 95% rh, noncondensing 100% Condensing 
Coefficient 4.8 ohms/F (8.6 ohms/K) — positive temperature coefficient 
Sensing Element Platinum-Film Platinum-film in
Sensor 
Resistance
T7005 Space
Sensor
air temperatures
low resistance splicing
35 to 149F  
(1.7 to 65C)
3474 ohms at 75F (23.9C)
T7006C&D Duct
Sensor
Air temperature 
in ducts
–40 to 160F
(–40 to 71C)
brass tube
T7007 Remote
Bulb Sensor High Temperature Chilled Water
Outdoor air and 
pipe temperature 
sensing
Holder for outdoor 
air use, or Strapon Kit or clamp on 
pipe sensing
Oil resistance 
cable with two 18 
AWG (0.81 sq mm) 
wires for low 
resistance splicing
Platinum-film Platinum-film in brass tube
High temperature 
fluid system such 
as hot water
1/2 in. — NPSC straight pipe threads  
into well
Two 18 AWG  
(0.81 sq mm) wires 
for low resistance 
splicing
70 to 392F 
(–21 to 200C)
Fluid systems 
requiring high or 
accuracy such as 
chilled water or where 
condensation in the 
sensor may occur
Two 18 AWG  
(0.81 sq mm) wires for 
low resistance 
splicing
20 to 225F 
(6.7 to 108C)
Accessories:
T7005 Space Sensor:
Cover, Satin Chrome:
❑ Vertical Mount with Logo, 14004406-300 
❑ Horizontal Mount with Logo, 14004406-400 
❑ Vertical or Horizontal no Logo, 14004406-800
Cover, Beige:
❑ Vertical Mount with Logo, 14004407-300 
❑ Horizontal Mount with Logo, 14004407-400
❑ Vertical or Horizontal no Logo, 14004407-800 
❑ Finish Plate, Black: 14002136-004 
❑ Finish Plate, Beige: 14002136-005 
❑ Wall Mounting Ring: 14004458-001 
❑ Adapter Plate: 14001496-001 
❑ Standoff Ring: 14000885-005
T7007 Remote Bulb Sensor:
❑ Installation Kit (all pipes): 14503800 
❑ Installation Kit (uninsulated pipe): 14503801 
❑ Sun Shield/Bulb Holder: 107323A
T7008 Immersion Sensor:
❑ Copper Well: 23904A 
❑ Heat Conductive Compound (required for use with well):
107408 (4 oz) or equivalent
3
74-2921—1

Home and Building Control
Honeywell Inc. 
Honeywell Plaza 
P.O. Box 524 
Minneapolis MN 55408-0524
Honeywell Latin American Division
Miami Lakes Headquarters 
14505 Commerce Way Suite 500 
Miami Lakes FL 33016
Home and Building Control
Honeywell Limited-Honeywell Limitée 
155 Gordon Baker Road 
North York, Ontario 
M2H 3N7
Honeywell Europe S.A.
3 Avenue du Bourget 
1140 Brussels 
Belgium
Honeywell Asia Pacific Inc.
Room 3213-3225 
Sun Hung kai Centre 
No. 30 Harbour Road 
Wanchai 
Hong Kong
74-2921—1   Rev. 4-97
Printed in U.S.A. on recycled paper 
containing at least 10% post-consumer paper fibers
Helping You Control Your World
®