T4039A,B,D-M,S,V
LineVoltage Cooling and
Heating-CoolingThermostats
T4039 Thermostats Control Line Voltage Valves of a fan coil unit in cooling, manual changeover heat- ing-cooling, or automatic changeover heating-cool- ing systems. One or two valves may be controlled directly by the thermostat. The fan switch (where applicable) controls air circulation.
■1-, 2-, or 3-speed manual fan control available.
■Positive deadspot separates heating-cooling circuits in automatic models. Remote changeover switch is required to separate circuits in manual changeover heating-cooling models.
■Scale range is approximately 55° F to 95° F [13° to 35° C] in 10° F [6° C] increments from 75° F [24° C] midpoint. Scale is marked COOL-WARM.
■Cooling circuit breaks in FAN-OFF position to reduce condensation problems in the fan coil unit.
■Color-coded leadwires.
■All models can be mounted on standard vertical outlet boxes. Models with manual switching can be mounted on 4 in. square junction boxes or 2- ganged outlet boxes.
■Adjustable range stops limit temperature adjustment or lock at selected setpoint.
■Models available with separate power source for fan and thermostat.
CONTENTS |
|
Specifications ................................................. |
2 |
Ordering Information ..................................... |
2 |
Installation ..................................................... |
5 |
Operation ....................................................... |
8 |
Checkout ......................................................... |
8 |
J. H. • Rev. 10-92 • ©Honeywell Inc. 1992 • Form Number60--22241—8
T4039A,B,D-M,S,V
SPECIFICATIONS • ORDERING INFORMATION
Specifications
MODELS:
|
Manual |
|
System |
Switchinga |
Model |
Cooling Only |
Off-Onb |
T4039A |
Cooling Only |
Hi-Med-Lo |
T4039B |
|
Off-Onb |
|
Heating-Coolingc |
— |
T4039D |
|
Off-Ond |
|
Heating Coolingc |
Off-Hi-Lob |
T4039E |
|
— |
|
Heating-Coolingc |
Hi-Med-Lo |
T4039F |
|
Off-Onb |
|
Automatic Heating-Cooling |
None |
T4039G |
Automatic Heating-Cooling |
— |
T4039H |
|
Off-Ond |
|
Automatic Heating-Cooling |
Off-Hi-Lob |
T4039J |
Automatic Heating-Cooling |
Off-Hi-Lod |
T4039K |
|
— |
|
Automatic Heating-Cooling |
Hi-Med-Lob |
T4039L |
|
Off-On |
|
Autoamtic Heating-Cooling |
Hi-Med-Lo |
T4039M |
|
Off-Ond |
|
Automatic Heating-Cooling |
Hi-Med-Lo |
T4039S |
|
Heat-Off-Coold |
|
Automatic Heating-Cooling |
Hi-Lo |
T4039V |
|
Off-Ond |
|
aSee Fig. 4 for arrangements of switches.
bOFF breaks cooling circuit and fan circuit.
cRemote changeover switch required.
dOFF breaks both heating and cooling circuits and fan circuit.
ELECTRICAL RATINGS:
A. Thermostat (valve load).
|
Normal (A) |
Inrush (B) |
120 Vac |
0.32 |
1.00 |
240 Vac |
0.16 |
0.50 |
277 Vac |
0.14 |
0.43 |
|
|
|
B. Fan Switch
|
Full Load (A) |
Locked Rotor (A) |
120 Vac |
5.5 |
33.0 |
240 Vac |
2.75 |
16.5 |
277 Vac |
2.4 |
14.4 |
10A |
Resistive at 125 Vac |
|
5A |
Resistive at 240 Vac |
|
4.2A |
Resistive at 277 Vac |
|
|
|
|
TEMPERATURE SETTING RANGE: Approximately 55° F to 95° F [13° C to 35° C]; marked COOLWARM in 10° F [6° C] increments from 75° F [24° C]
midpoint.
DIFFERENTIAL: Approximately 2° F [1° C] at midscale. On automatic heating-cooling models, the differential from make of one contact to make of the opposite contact is 7° F [4° C] maximum with a positive deadspot.
DIMENSIONS: See Figs. 1 and 2.
Ordering Information
When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the TRADELINE Catalog or price sheets for complete ordering number, or specify—
1. Model number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1.Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directly).
2.Home and Building Control Customer Satisfaction Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales and Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
2
FINISH: Silver bronze. T4039M is available in white.
MOUNTING: Models without manual switching mount on standard vertical outlet boxes. Models with manual switching mount on 4-in. square junction boxes or 2-ganged outlet boxes. Manual switching models may
T4039A,B,D-M,S,V
SPECIFICATIONS
also mount on a standard vertical outlet box if local codes permit. See Fig. 3.
UNDERWRITERS LABORATORIES, INC. LISTED: File No. E4436, Vol. 2, dated 3-19-73; Guide No. XAPX.
Fig. 1—Mounting dimensions in in. [mm] of T4039 models with manual switching.
Fig. 2—Mounting dimensions in in. [mm] of T4039 models without manual switching.
3 |
60-2241—8 |