Honeywell T2798I2000 User Manual

APPLICATION:
This standalone micro-controller based LCD temperature controller provides proportional plus integral (P+I) and on/off temperature control for commercial Heating, Ventilating & Air Conditioning System such as Hydronic Heating, Air Handling Unit, Heat Exchanger or Condensing Tower. This controller has a modulating analog 2 to 10Vdc or 4 to 20mA output and a 2A on/off output to realize various optional control functions including cool/heat changeover, heat/cool sequence control, emergency interlocking and auto-alarming control.
Table of Contents
Application………………………………………….1 Features…………………………………………….1 Specification………………………………………..2 Dimensions, Installation & Wiring Terminals..….3 Control Operation………………………………….4 Installer SetUp……………………………………..12
FEATURES:
PI (proportional plus integral) control action provides accurate, stable and comfortable temperature control.
Compatible with series 70 direct-coupled damper / valve actuator like ML7161, ML7174, ML7420 / ML7421series ML7425, ML7984 series, N20010, S10010, M7410E series, CN7505, CN7510 / CN72 series CN7220 & CN7234 also VC79 series etc.
Backlit LCD to display both setting and measured value.
Adjustable Zero Energy Band, On/Off Differential, Proportional Band and Temperature Offset.
Analog output can be forced manually to be convenient for installation & commissioning.
Optional 2 to 10Vdc or 4 to 20mA direct acting and reverse acting analog output.
Selectable internal and external temperature sensor.
Wide temperature control range (-20 to 110 °C by using external temperature sensor) is suitable for extreme temperature control such as steam and ice water.
Watch Dog Timer: to resume the controller from hanging condition.
Brownout effect to avoid malfunctioning and care on power ON and power OFF.
Pluggable terminal block allows pre-wiring outside of the controller.
Compact size and slim design provide elegant and attractive modern style appearance.
Page 1 of 18 APHITEMPCON001-11-04
SPECIFICATIONS:
IMPORTANT: The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor difference in performance can be expected if those conditions are changed.
MODEL: T2798I2000 Control Performance: This controller provides 4 to 20mA or 2 to 10Vdc Proportional plus Integral modulating control and 4(2) A On/Off control.
INPUTS:
1) Analog - 1 No. (Only PT1000)
2) Digital - 1 No. (Dry Contact) OUTPUTS:
1) Analog - 1 No.
2) Digital - 1 No.
SETPOINT RANGE: 5-50°C (internal temperature sensor)
-20-110°C (external temperature sensor)
POWER SUPPLY: AC24V ±20%, 50/60Hz, 2 VA.
ANALOG OUTPUT: 2 to 10Vdc OR 4 to 20mA.
DIGITAL OUTPUT: 2A, 24Vac
MOUNTING: Direct wall mounting with standard electrical mounting box [type-3 module].
TERMINALS: Plug-in screw terminals are suitable for 1.5 square mm wire.
OPERATING AMBIENT: 0-50°C, 5-80%RH.
Shipping & Storage:
-20 - 45°C, 5-95%RH ACCURACY: < / = +/- 0.30°C REMOTE SENSOR: RTD PT1000. Maximum 15m cable length (line resistance < 4.5Ω)
Enclosure: ABS Plastic, 2-piece. (IP30)
OPERATING PARAMETER: See TABLE 2 for installer selections.
Parameter Selection Zero Energy Band 1.5 or 3.0°C On/Off Differential 0.5 to 3.0°C (0.5°C
step change)
Proportional Band 2.0 to 19.0°C (0.1°C
step change)
Offset -3.0 to 3.0°C (0.5°C
step change)
Set Point Definition Heating, Cooling,
H/C midpoint, Heating/Alarming or Cooling/Alarming.
Main Sensor Remote or Internal
ACCESSORIES:
Duct Mount Remote Sensor PT1000. DIN Class B. Model # RSPT1000 Probe Length: 300mm (to be ordered separately)
Page 2 of 18 APHITEMPCON001-11-04
1234567
8
14
135
17
135
107.5
83.5
86.5
20
DIMENSIONS:
115
60
115
M3 Self Tapping screw
INSTALLATION:
The controller can be installed in any position on a flat surface using electrical box [Type-3 Module]. To measure room temperature by internal sensor and choosing wall mounting method, it is recommended to be installed 1.5m (about 5 ft.) above the floor in the area at average temperature conditions. For all kinds of mounting method, the product must be installed in an area with good air circulation.
Do not install the controller where it may be affected by:
Draughts or dead air spots behind doors
and in corners.
Hot or cold air from ducts. Radiant heat from sun or appliances. Concealed pipes and chimneys
WIRING TERMINAL:
1 & 2 – Relay Output 3 – 0Vac 4 – 24Vac 5 – Digital Input 6 – 2…10Vdc OR 4…20mA analog output 7 & 8 – PT1000 Remote Sensor
Page 3 of 18 APHITEMPCON001-11-04
CONTROL OPERATION:
Input1 –Remote Temperature Sensor
The controller has an integral sensing device mounted internally. It is also possible to install a remote room or duct return sensor at different locations. See wiring diagram. Note#1: The remote sensor should be PT1000 (Refer Accessories)
Input2- Emergency Input
Input2 is to connect with an On/Off dry contact for system error or emergency interlock control. If the contact is close, the controller will automatically close all output (or open to the maximum position in reverse mode) and cut off the power. The controller can only be restarted manually.
Note#2: If you don’t want to use the interlock function/emergency input please use a jumper wire to connect input2 (terminal no.5) and neutral port (Terminal no.3), see wiring diagram.
Output1-Modulating Analog Output (2 to 10Vdc or 4 to 20mA)
Output1 is modulating P+I analog 2 to 10Vdc or 4 to 20mA. It can be selected by Selector switch. The output signal is normal mode (2 to 10Vdc or 4 to 20mA) or reverse mode (10 to 2Vdc or 20 to 4mA) selectable.
Output2- On/Off digital Output (2A, 24Vac)
Output2 is digital output with 24VAC 2A Contact rating, nominal capacity. It provides On/Off control for electric heater, on/off valve actuator or fan etc. Output2 can provide limitation control through pre-setting a separate temperature limitation.
Page 4 of 18 APHITEMPCON001-11-04
Heat / Cool Changeover of Output1
Valve Open
Temperature Increase
Valve Close
Output1 is suitable for Heat/Cool changeover (manually) control in 2pipe AHU, Zoning control or Hydronic Heating application. Wiring connection is shown in fig. With cooling or heating selected, the user set point (SP) will be positioned at the middle of proportional band. The output percentage is proportional to the temperature measured and decided by proportional band. The proportional band can be set from 2.0°C to 19.0°C. The control logic is seen in Diagram 1.
Diagram 1:
100%
50%
0%
Wiring Diagram
Heating
sp
Cooling
Proportional band
Pt1000 sensor
24VAC
A/OD/I
8
PT1000 REMOTE SENSOR
4 - 20 mA
2 - 10 VDC
110VAC / 230VAC
1 2 3 4 5 6 7
L
24VAC
N
0VAC
E
POWER SUPPLY
0VAC
2-10VDC / 4-20mA
Actuator Unit
Add link between terminal No 5 & 3. Page 5 of 18 APHITEMPCON001-11-04
Note: If Emergency IP [D/I] not used then
Heating + Cooling Sequence control with Zero Energy Band
Z-Band
Output 2
Valve Open
Temperature Increase
Valve Close
Output 1
This kind of control requires Zero Energy Band (Z-Band). Z-Band is pre-set. For control purpose, the zero energy band is centered on the user set point (SP), so its value defines the effective heating (H SP) & cooling (C SP) set points. The cooling set point (C SP) will be positioned on the right side of Z-Band & the heating set point (H SP) on the left side of Z-Band. Z-Band can be set as 1.5°C or 3.0°C. Any change of set point will cause both heating and cooling set points to change in parallel. Either output1 or output2 can be used for cooling or heating control. The control logic is seen in Diagram 2 and 3.
Diagram 2: Heating + Cooling Sequence Control.
100%
0%
50%
Heating
H SP
SP
C SP
Cooling
Diff
Page 6 of 18 APHITEMPCON001-11-04
Loading...
+ 12 hidden pages