Honeywell T104F User Manual

Thermostatic Control
The T104F Thermostatic Control is used with a V110 Valve Body to control radiators, convectors, baseboard heating units, or other heating units with standard capacity requirements. The control is self-powered and requires no electrical connection. The T100A includes a setpoint dial and valve actuator, connected by a capillary tube to a sensor. The T104F Control attaches to the valve body by threaded connections and may be mounted at any angle. Install the remote sensor beneath the heating coils in the cold air re­turn, or on a nearby wall where the air flow is not restricted.
The setpoint dial has reference marks (1-6). The control has a low limit of 43°F (6°C) when the dial is turned fully clockwise to the frost protection mark*. The red button indicates the 68°F (20°C) setpoint limit. Higher settings may be made by holding in the button while turning. The thermo­static sensor is protected by a safety spring against tempera­tures to 125°F (52°C).
T104F
3
2
M9730
Specifications
MATERIALS OF CONSTRUCTION:
Body: Industrial grade plastics with low thermal
conductivity. Fastening Ring: Plated brass. Internal Parts: Brass thermostat capsule, other metals.
TEMPERATURE RANGE: 43° to 79°F (6° to 26 °C). MAX. SENSOR TEMPERATURE: 125°F (52°C). MAX. OVERALL DIMENSIONS: 2-1/8 in. (54 mm) wide,
3-5/16 in. (84 mm) long. See Fig. 1.
CAPILLARY LENGTH: 6 ft. 8 in. (2 m). TEMPERATURE SETTINGS:
These are the setpoint temperatures, which correspond
to the setpoint dial reference marks, under ideal conditions. Factors affecting the temperature at the sensor vary for each installation. It may be necessary to adjust the setpoint higher or lower to obtain the desired space temperature.
Temperature 0 *123456
°F Off 43 46 54 61 68 73 79
°C Off 6 8 12 16 20 23 26
Fig. 1—T104F dimensions in in. (mm).
2 1/8 (54)
M9731
AVAILABLE VALVE BODIES:
See Fig. 2.
3 5/16 (84) MAX.
1 62-3047
C. H. • 12-94 • ©Honeywell Inc. 1994 • Form Number 62-3047
Fig. 2—V110 Valve Bodies.
VALVE BODIES
V110D
V110E
V110F
M9735
Fig. 3—T104A,B,C,V Thermostatic Controls.
4
5
3
3
2
2
1
OTHER AVAILABLE T100 THERMOSTATIC CONTROLS (See Fig. 3):
T104A Control with internal sensor. T104B Control with remote sensor/setpoint. T104C Control with remote sensor and remote setpoint. T104V Control with internal sensor and tamper-resistant
setpoint and mounting.
ACCESSORY
A104F1007 Limit Pins. G111B1053 Bulb guard for protection of sensor when
mounted on the wall.
4
5
3
2
1
T104B T104CT104A T104V
Installation
IMPORTANT: The T104F can be mounted inside an enclo-
sure if the sensor is located a minimum of 3 in. (76 mm)
beneath the heating coils in the cold air return. Coil
excess capillary tubing beneath and away from the
62-3047 2
M9736
heating coils. Take care not to break, kink or sharply bend the capillary tubing.
When mounting the T104F, make sure the bosses on the T104F base fit securely into the valve body grooves. Firmly hand tighten the knurled ring. Improper mount­ing can cause overheating. Refer to Fig. 4 for typical installations.
Fig. 4—Typical installations.
18 INCH
MINIMUM
M9734
Settings and Calibration
The T104F Control includes an adjustable range limit-
ing pin (order additional pins separately). The pin is fac­tory-set to limit the low range of the control to the frost protection (*) setting (see Fig. 5). The pin can be moved to a different low or high limit setting and lock point, or it can be removed. Use a second pin if both low and high limit settings are desired.
Fig. 5—Temperature settings.
ADJUSTMENT RANGE SETTING
°C
OFF OFF
°F
01
6
4384612541661206823732679
SCALE MARKING
*
23
Setting the Limit
To set a limit different from the factory setting, proceed
as follows:
1. Determine the desired temperature range limit or lock­ing temperature. Select the appropriate number on the ad­justment knob to match the desired temperature setting. See Fig. 5.
1PIN REQUIRED.
2
FACTORY SETTING.
TEMP.
4
56
2
1
1
PIN POS.
3
NONE
4a
4b
4b
4b + *
5
5 + *
*
RANGE
°F
43 - 79
61 - 79
OFF - 79
68
72
0 - 68
43 - 68
0 - 73
43 - 73
TEMP.
RANGE
°C
6 - 26
16 - 26
OFF - 26
20
22
0 - 20
6 - 20
0 - 23
6 - 23
M9729
3 62-3047
2. Lift the end cap off the adjustment knob. See Fig. 6.
Fig. 6—Lift the end cap off the adjustment knob.
3. Remove the adjustment knob from the actuator as
2
ACTUATOR
ADJUSTMENT KNOB
END
3
CAP
M9715
follows:
a. Turn the adjustment knob so the desired knob setting
is aligned with the white line on the actuator base.
b. Pull the knob off the head or use a screwdriver inserted
into one of the slots to pry off the knob. See Fig. 7.
Fig. 7—Remove the knob from the actuator.
4. Push the limit pin up and slide it into the slot that
BASE
ACTUATOR HEAD
ARM CLIP (3)
M9714
SCREWDRIVER SLOT (2)
WHITE LINE
CALIBRATION INDENT
RED BUTTON
corresponds with the desired temperature limit. If the lower limit remains at the frost protection mark (*), insert an additional pin in the slot that corresponds with the second limit.
Example 1:
If the desired temperature range is 43° to 73°F (6° to 23°C), leave the pin in the slot marked * and add one pin in slot 5.
Example 2:
If the desired temperature range is OFF to 68°F (23 °C), move the pin to slot 5. No additional pin is required.
5. To replace the adjustment knob, realign the knob setting in step 3a with the white line on the base and push the knob toward the base. Make sure the three arm clips snap into place at the top of the adjustment knob. If the actuator was turned with the adjustment knob off, recalibrate the control according to the instructions in Recalibrate T104F Control section.
6. Replace the end cap.
Locking the Control at a Single Temperature
1. Determine the desired locking temperature. Select the appropriate number on the adjustment knob to match the desired temperature setting. See Fig. 5.
2. Lift the end cap off the adjustment knob. See Fig. 6.
3. Remove the adjustment knob from the actuator as follows:
a. Turn the adjustment knob so the desired knob setting
is aligned with the white line on the actuator base.
b. Pull the knob off the head or use a screwdriver inserted
in one of the slots to pry off the knob. See Fig. 7.
4. Insert the pin in slot 4a for 68°F (20°C) or slot 4b for 72 °F (22°C).
Fig. 8—Insert the pin in the slot to set the limit range.
LIMIT PIN
*
FIXED STOP
LIMIT PIN REMOVED
WHITE LINE
34a4b5
POSITION
(SEE FIG. 5)
PIN
M9723
5. To replace the adjustment knob, align the knob setting from step 3a with the white line on the base and push the knob toward the base. Make sure the three arm clips snap in place at the top of the adjustment knob.
6. Replace the end cap.
Recalibrate T104F Control
1. Lift the end cap off the adjustment knob. See Fig. 6.
2. Pull the knob off the head or use a screwdriver inserted in one of the slots to pry off the knob. See Fig. 7.
3. Turn the actuator head clockwise until the head stops (Fig. 7). The calibration indent should be aligned approxi­mately with the white line on the base when the head stops. If the indent is 180 degrees from the white mark, unscrew the head completely from the base and rethread the head to the base so that it is aligned with the white mark. Turn the act­uator head clockwise until the head stops. Complete removal of the head from the base is required only if the actuator was previously dismantled.
NOTE: The distance between the actuator head and the static
portion of the control should be approximately 3/8 in. (9 mm).
4. Turn the actuator head counterclockwise approxi­mately one turn until the calibration indent on the head aligns with the white line on the base. For the 72 °F (22°C) single temperature setting, align the indent with the center of the adjustable limiting pin.
5. Replace the adjustment knob by aligning the red button with the white line on the base and pushing the knob toward the base. For the 72°F (22°C) single temperature setting, align the red button with the center of the adjustable limiting pin. Make sure the three arm clips snap in place at the top of the adjustment knob.
6. Replace the end cap.
62-3047 4
Troubleshooting
Sympton Possible Cause Solution
All sections of the radiator are not heating.
Underheating. 1. Sensor is in the wrong location. 1. Change the sensor location or change the control
Overheating. 1. Sensor is in the wrong location. 1. Change the sensor location or change the control
Chattering or knocking.
1. Many radiators are over-sized and all sections are not required to heat up to maintain the set room temperature.
2. Excess capillary tube is coiled above or too near the heat source.
3. Flow through the valve is in the wrong direction.
4. Inadequate system temperature or pressure.
5. Steam traps are defective. 5. Repair or replace the traps.
6. Air lock in the hot water system. 6. Open the valve fully to allow air to pass. Install
7. Scale or debris is blocking flow. 7. Flush the system. Do not use oil base additives.
8. Heating cabinet dampers are closed. 8. Open or remove the dampers.
2. Control is not properly installed. 2. Set the bosses in the grooves and tighten the
3. Capillary tube is broken, kinked, or bent sharply.
4. Dirt or scale is under the seat, preventing tight shutoff.
5. Flow through the valve is in the wrong direction, damaging the valve seat.
6. Steam traps are defective. 6. Repair or replace the traps.
7. Excessive differential pressure is forcing the valve open (hot water systems).
1. Flow through the valve is in the wrong direction.
2. Vacuum in the system. 2. For steam—check traps and vents. For hot water—
3. Excessive differential pressure. 3. Install a differential pressure regulator (D146A) to
4. Binding of piping. 4. Make sure there is adequate space for piping.
1. System is operating properly.
type. See installation instructions.
2. Coil excess capillary tube below or away from the heat source.
3. Check the arrow on the valve body. It should be in the direction of the flow. Change the valve direction or flow direction.
4. Check the operating and limiting controls on the boiler. Check the circulating pump and isolating valves.
vents.
Clean strainer insert in steam applications.
type.
knurled ring to the valve body.
3. Replace the control.
4. Remove the control from the valve body, allowing the valve to open fully and flush away scale and debris. Reinstall the control and turn fully clock­wise. If the valve does not fully close, remove con­trol and cartridge using a cartridge changer tool or service socket (isolate valve from system if not using changer tool). Inspect and clean valve seat area and disc. Always use a strainer insert in steam applications.
5. Check the arrow on the valve body. It should be in the direction of the flow. Change the valve direction or flow direction. Remove the valve cartridge and inspect for damage to the seat disk.
7. Install a differential pressure regulator (D146A) to maintain less than 117 kPa (17 psi) differential between supply and return pipes.
1. Check the arrow on the valve body. It should be in the direction of the flow. Change the valve direction or flow direction.
check expansion tank operation and location.
maintain less than 117 kPa (17 psi) differential between supply and return pipes.
5 62-3047
Honeywell Braukmann Honeywell Braukmann Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9
62-3047 6
Printed in Germany www.honeywell.ca/braukmann
QUALITY IS KEY
Loading...