Thermostatic Radiator Valves and Actuators
T104A T104B T104C T104F T104V
3 5/16 (84) MAX.
2 1/8
(54)
M9708B
2-1/8
(54)
1 (25)
2 (50)
TOP
CAPILLARY TUBE LENGTH
6 FT. 6 IN. (2 m) OR 16 FT. (5 m)
M3208A
2-5/32
(55)
2-1/8 (54)
2-31/32 (75)
1-13/16
(46)
CAPILLARY TUBE LENGTH
4 FT. 6 IN. (1.37 m)
M3221C
CAPILLARY TUBE
LENGTH 4 FT. 6 IN. (1.37 m)
2-31/32 (75)
2-5/32
(55)
2-1/8 (54)
1-13/16
(46)
3 5/16
(84)
MAX.
2 1/8 (54)
M9731
3
(86)
3
8
M3215A
2
(51)
H
4
T104V
T104 High Capacity Thermostatic Radiator Valve Actuators
Provide precise and automatic control of room temperature in twopipe systems by modulating the flow of hot water or steam through
free-standing radiators, convectors and other heating units with
high capacity requirements.
• Continually monitor and adjust room temperature for consistent
comfort and relief from under-heating and overheating.
• Designed with the higher capacity normally required by North
American heating systems.
Dimensions in inches (millimeters)
• Valve seat disc, which is made of resilient material (EPDM), ensures
tight shutoff on steam or hot water systems.
• Nickel-plated bronze casted body with working parts in cartridge
insert for ease of service.
• Controls include sensor, setpoint dial and valve actuator;
components may be integral or connected by capillary tubes.
• Require no electrical connections.
• Meet ASHRAE Standard 102-1989.
• 40 mm collar diameter.
Controls
Hydronic
70-6910 235
Thermostatic Radiator Valves and Actuators
Application: High Capacity Thermostatic Radiator Actuator
Used With Valve: V110
Product Number Application Type
T104A1040 Self-contained controller with sensor, setpoint dial and valve
T104B1038 Controller with combined remote setpoint and sensor
T104B1046 Controller with combined remote setpoint and sensor
T104C1036 Controller with remote setpoint and sensor normally
T104F1512 Thermostatic radiator valve controller for use with V110
T104V1422 Self-contained controller with sensor, setpoint dial and valve
actuator in one unit. Adjustable limits. Mount horizontal. Not
for use inside enclosures or in locations with restricted
airflow around sensor. For V110 valves.
mounted on a wall. Setpoint/sensor connect with a capillary
tube to an actuator, which mounts on the valve body. For
V110 valves.
mounted on a wall. Setpoint/sensor connect with a capillary
tube to an actuator, which mounts on the valve body. For
V110 valves.
mounted with setpoint dial mounted on outside cabinet or
enclosure; sensor mounted beneath heating coils in cold air
return. Double capillaries. For V110 valves.
series valves. With remote temperature sensing and
integral set point. Adjustable limits.
actuator in one unit. Locks to valve body. Rugged design.
Adjustable setpoint under locking cap. Factory set at 68 F
(20 C). Mounts horizontal. Not for use in enclosures. For
V110 valves.
Collar Diameter: 40 mm
Temperature
Capillary Length
——43 F to
6 ft. 8 in. 2 m 48 F to
16 ft 4.9 m 48 F to
Tw o
4 1/2 ft
6 ft. 8 in. 2 m 43 F to
——43 F to
Tw o
1.4 m
Range Sensor Setpoint
79 F
79 F
79 F
48 F to
79 F
79 F
79 F
6 C to
Integral Integral Adjustable
26 C
9 C to
Remote Remote —
26 C
9 C to
Remote Remote —
26 C
9 C to
Remote Remote —
26 C
6 C to
Remote Remote Adjustable
26 C
6 C to
Integral Integral Vandal Proof
26 C
Comments(ft) (m) (F) (C) Integral or Remote
Limits
Limits
T104 Thermostatic Radiator Valves Parts and Accessories
Product Number Description Used With
P110V1003 Replacement Locking Ring for T104V1422 only (package of 5) T104V1422;
G111B1053 Bulb guard to protect remote temperature sensors on T104C and T104F controls only T104C; T104F
V2000 Series Valve Bodies Cross Reference to V100 Series
Use T100 Actuators With New V2000 Series Valve Bodies
V2000 Series
(Current)
V2040DSL15 V100D 1056 1/2 in. TRV Straight Body, Female NPT Inlet, Male NPT Tailpiece Outlet
V2040DSL20 V100D 1064 3/4 in. TRV Straight Body, Female NPT Inlet, Male NPT Tailpiece Outlet
V2040DSL25 V100D 1072 1in. TRV Straight Body, Female NPT Inlet, Male NPT Tailpiece Outlet
V2043DSL15 V100D 5057 1/2 in. TRV Straight Body, Female NPT Inlet, Sweat Tailpiece Outlet
V2043DSL20 V100D 5065 3/4 in. TRV Straight Body, Female NPT Inlet, Sweat Tailpiece Outlet
V2040ESL15 V100E 1055 1/2 in. TRV Vertical Body, Female NPT Inlet, Male NPT Tailpiece Outlet
V2040ESL20 V100E 1063 3/4 in. TRV Vertical Body, Female NPT Inlet, Male NPT Tailpiece Outlet
V2040ESL25 V100E 1071 1 in. TRV Vertical Body, Female NPT Inlet, Male NPT Tailpiece Outlet
V2043ESL15 V100E 5056 1/2 in. TRV Vertical Body, Female NPT Inlet, Sweat Tailpiece Outlet
V2043ESL20 V100E 5064 3/4 in. TRV Vertical Body, Female NPT Inlet, Sweat Tailpiece Outlet
V2040ASL15 V100F 1054 1/2 in. TRV Horizontal, Female NPT Inlet, Male NPT Tailpiece Outlet
V2040ASL20 V100F 1062 3/4 in. TRV Horizontal, Female NPT Inlet, Male NPT Tailpiece Outlet
V2040ASL25 V100F 1070 1” TRV Horizontal, Female NPT Inlet, Male NPT Tailpiece Outlet
V200LDSL15 V100G 5054 1/2 in. TRV Straight Body, Sweat Inlet, Sweat Outlet No Tailpiece
V200LDSL20 V100G 5062 3/4 in. TRV Straight Body, Sweat Inlet, Sweat Outlet No Tailpiece
V2042HSL10 V100P 1046 1/8 in. TRV (1/2 in. Body With 1/8 in. Adapter) Male NPT Inlet, Female NPT Outlet. One Pipe Steam
V2043HSL10 Y100P 1001
VS1200SL01 Replacement Cartridge New V2000 Series
V100 Series
(Obsolete) Product Description
1/8 in. TRV (1/2 in. Body With 1/8 in. Adapter) Male NPT Inlet, Female NPT Outlet. One Pipe Steam Includes
SA123A1003
236 customer.honeywell.com 70-6910