Description of Devices .............................................................................................................................. 9
Figure 5: Key position of wall module ..................................................................................................................... 15
Figure 7: Model number and Sylk bus address ...................................................................................................... 16
Figure 8: Contractor mode default home screen .................................................................................................... 17
Figure 9: Home screen Roomtemp ........................................................................................................................ 17
Figure 10: Home screen Room Setpoint, Roomtemp............................................................................................. 17
Figure 11: Home screen Outside Room Temperature ........................................................................................... 18
Figure 12: Home screen Room, Room Setpoint Temperature ............................................................................... 18
Figure 13: Set View More First screen ................................................................................................................... 18
Figure 14: Parameter group Sensors ..................................................................................................................... 20
Figure 17: Parameter Status Htg Out ..................................................................................................................... 22
Figure 18: Parameter Status Clg Out ..................................................................................................................... 22
Figure 19: Parameter Status Damper .................................................................................................................... 22
Figure 20: Parameter Status Dmd Limit ................................................................................................................. 22
Figure 21: Parameter Status Trmnl Ld ................................................................................................................... 23
Figure 22: Parameter Status Aux Econ .................................................................................................................. 23
Figure 23: Parameter Status Free Mod .................................................................................................................. 23
Figure 24: Parameter Status Free Dtg ................................................................................................................... 23
Figure 25: Parameter Status Fan ........................................................................................................................... 24
Figure 44: Parameter Snsr Cal Zio T Of ................................................................................................................. 31
Figure 45: Parameter Snsr Cal Zio H Of................................................................................................................. 31
Figure 46: Parameter Wm Config Units .................................................................................................................. 31
Figure 47: Parameter Wm Config Type .................................................................................................................. 31
Figure 58: Parameter Wm Config Efclg HI ............................................................................................................. 34
Figure 59: Parameter Wm Config Efclg Lo ............................................................................................................. 34
Figure 60: Parameter Cnfg Ctl Hp Type ................................................................................................................. 35
Figure 61: Parameter Cnfg Ctl Clg Type ................................................................................................................ 35
Figure 70: Parameter Cnfg Di Di 1 ......................................................................................................................... 39
Figure 71: Parameter Cnfg In Spe Temp................................................................................................................ 40
Figure 72: Parameter Cnfg In Spe Rh .................................................................................................................... 40
Figure 73: Parameter Cnfg In Spe CO2 .................................................................................................................. 41
Figure 74: Parameter Cnfg In Dischair ................................................................................................................... 41
Figure 75: Parameter Cnfg In Mixedair................................................................................................................... 42
5
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 76: Parameter Cnfg In Od Temp ................................................................................................................. 42
Figure 77: Parameter Cnfg In Occ Snsr ................................................................................................................. 43
Figure 78: Parameter Cnfg In Window ................................................................................................................... 43
Figure 82: Parameter Cnfg Out Clg Stg1 ............................................................................................................... 46
Figure 83: Parameter Cnfg Out Clg Stg2 ............................................................................................................... 46
Figure 84: Parameter Cnfg Out Clg Stg3 ............................................................................................................... 47
Figure 85: Parameter Cnfg Out Hp Chang ................................................................ ............................................. 47
Figure 86: Parameter Cnfg Out Htg Stg1 ............................................................................................................... 48
Figure 87: Parameter Cnfg Out Htg Stg2 ............................................................................................................... 48
Figure 88: Parameter Cnfg Out HtgStg3 ................................................................................................................ 49
Figure 89: Parameter Cnfg Out Fan Out ................................................................................................................ 49
Figure 90: Parameter Cnfg Out Damper ................................................................................................................ 50
Figure 91: Parameter Time Time ........................................................................................................................... 50
Figure 92: Parameter Set Time Hours ................................................................................................................... 51
Figure 93: Parameter Set Time Min ....................................................................................................................... 51
Figure 94: Parameter Set Date Year ...................................................................................................................... 51
Figure 95: Parameter Set Date Month ................................................................................................................... 51
Figure 96: Parameter Set Date Day ....................................................................................................................... 52
Figure 100: Tenant mode home screen ................................................................................................................. 54
Figure 101: Tenant mode Fan Auto ....................................................................................................................... 55
Figure 102: Tenant mode Fan On .......................................................................................................................... 55
Figure 103: Tenant mode Fan Off .......................................................................................................................... 55
Table 3: List of applicable literature ................................................................ ........................................................ 12
Sylk™ bus for use with Sylk-enabled sensors.
120 controllers per Q7751A, B router when
configured as a repeater.
Field configurable for control, input, and output
functions using the NIAGARA FRAMEWORK®
software.
Built-in zone control functions include a remote
wMarkall module interface and a scheduler.
All wiring connections are made to removable
terminal blocks to simplify controller installation
and replacement.
For more information, refer below mentioned
documents as shown in Table 1:
Table 1: Stryker reference documents
General
The CUL6438SR-CV1 is part of the Stryker family.
The controllers are Free Topology Transceiver
(FTT) LONMARK®-certified devices designed to
control HVAC equipment. This is advanced system
feature that allows state-of-the-art, commercial
building control. Each controller is configurable
using the NIAGARA FRAMEWORK® software.
The Stryker controllers require the Stryker feature
to be licensed in the WEBpro workbench tool and
the WEBs AX JACE Controller for programming. It
can download to any brand of the Niagara
Workbench or JACE controller.
Controllers are used in VAV (Variable Air Volume)
and CVAHU (Constant Volume Air Handling Unit)
control applications. Each controller contains a host
microcontroller to run the main HVAC application
and a second microcontroller for LONWORKS®
network communications. Each controller provides
flexible, universal inputs for external sensors, digital
inputs, and a combination of analog outputs and
digital outputs.
9
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Form No.
Title
63-1322—02
Zio®/Zio Plus LCD Wall
Modules Wall Module
Specification Data
62-0271-07
Zio®/Zio Plus LCD Wall
Modules Wall Module
Installation Instructions
63-2719
LCD Wall Modules Wall
operating guide
Note:Refer to the Zio/Zio plus LCD Wall
Modules Operating Guide (form 63-
2719) for information about customizing
the wall module configuration in the
WEBs-AX Workbench, such as
modifying the default Home screens or
creating your own application.
Zio®/Zio Plus LCD Wall
Modules
Figure 2: Zio/Zio Plus LCD Wall Modules
General
The TR70 Series Zio (TR70/TR70-H, TR71/TR71H) and Zio Plus (TR75/TR75-H) are 2-wire, nonpolarity sensitive, and Sylk bus communicating wall
modules for use with Spyder® and Comfort Point™
programmable controllers.
All models have a space-temperature sensor,
network bus jack, and an LCD panel with three soft
keys and two Up/Down adjustment keys. The TR7H, TR71-H and TR75-H models include an onboard humidity sensor.
Features
The TR70 Series wall modules include:
Ability to control tenant access to controller
parameters via password protection.
Ability to assign labels for enumerated values.
Customized parameter access, by using the
Honeywell WEBs-AX Workbench tool.
Ability to link setpoint limits to a network
variable.
Programmable for: home screen options,
tenant access, contractor access, optional
password protection to contractor mode,
access to controller parameters, Setpoint,
override, fan, and other parameters.
Ability to access and adjust most parameters in
the programmable controller.
TR75 can access and adjust the controller
schedule.
Ability to balance the VAV system from the wall
module.
Home screen can display one out of three
following parameters: temperature setpoint,
room temperature, room humidity, outdoor
humidity, outdoor temperature, and time, or
virtually any one of parameters in the
controller.
Network bus jack.
Simple 2-wire terminal connection to the
programmable controller (includes power) and
an optional 2-wire terminal connection for the
network. All connections are polarity
insensitive.
Permanent retention of user configuration,
including Setpoints after a power outage.
For more information, refer below mentioned
documents as shown in Table 2
Table 2: Zio reference documents
Control Application
Stryker CVAHU systems in commercial buildings
typically incorporate a packaged air handler system
that delivers a constant volume of air at
preconditioned temperatures to the zone being
served. Each zone is usually serviced by a
separate AHU; however, sometimes two or more
AHUs service the same zone. The Stryker CVAHU
can control staged or modulating heating and
cooling coils, mixed air economizer dampers, and
the system fan. Control of heat pump units, where
the compressor(s) is used for both cooling and
heating, is also provided. The zone the Stryker
CVAHU services can use a TR71/75 for space
temperature sensing and an S-bus and LON bus
network access for users via Zio and front end
graphics respectively.
10
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 3 shown below is typical Stryker CVAHU control application.
Figure 3: Typical Stryker CVAHU control application
Control Provided
The Stryker CVAHU Controller is designed to
control a single air handler to maintain the unit’s
space temperature at the current Setpoint. Heating
and cooling control are provided for either staged or
modulating equipment. Up to three stages of
mechanical cooling and up to three stages of
heating are allowed. Modulating outputs can be
either floating type such as a series 60 control, or
pulse width modulated (PWM) control. The
economizer dampers can be controlled directly with
floating or PWM outputs, or indirectly using a digital
output as an enable/disable signal to a packaged
economizer controller. The economizer enable
function, determines when to allow outdoor air for
free, cooling, can be configured, to one of the
strategies based on the inputs. When the
economizer position is controlled from the Stryker
CVAHU, the minimum position setting (for
ventilation requirements) is adjusted based on
indoor air quality (IAQ) needs in the space. IAQ
monitoring is provided through either a CO2 sensor
or a digital input from a space-mounted IAQ limit
switch.
For heat pump configurations, up to three
compressors can be controlled, along with up to
three stages of auxiliary heat, and a heat/cool
change over valve. Including the supply fan, a
combination of these items may not exceed eight
outputs in a Stryker CVAHU. The Stryker CVAHU
Controller can monitor a space-mounted occupancy
sensor, and a door/window contact. These inputs
affect the operational mode of the controller.
The Stryker CVAHU Controller allows other
controllers in the system to use the physical inputs
and outputs. A digital input and an analog input can
be configured to read switch states and voltage
sensor values, respectively, and send them out
over the S and LON-bus network.
11
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Form No.
Title
63-4529—03
Stryker™ Lon Configurable
VAV/CVAHU Controller
Specification Data
Zio®/Zio Plus LCD Wall Modules
Wall Module Specification Data
62-0271-07
Zio®/Zio Plus LCD Wall Modules
Wall Module Installation
Instructions
63-2719
LCD Wall Modules Wall
operating guide
209541B
LONWORKS® Bus Wiring
Guidelines/ Termination Module
Installation Instructions
Note:
All models have a space-temperature
sensor, network bus jack, and an LCD
panel with three soft keys and two up/down
adjustment keys. The TR70-H, TR71-H
and TR75-H models include an onboard
humidity sensor.
Products Covered
This System Engineering Guide describes how to
configure Stryker CVAHU controller via TR71/75
Zio wall module.
Stryker CVAHU Controllers and related accessories
to typical applications are as follows:
This manual is divided into two basic parts:
introduction and configuration.
The Introduction provides information for Stryker
LON configurable CVAHU controller and TR70
series Zio/Zio Plus LCD wall modules, control
application, control provided, product covered, and
abbreviations.
Configuration steps provide information for the
engineering of Stryker LON configurable CVAHU
controller by TR70 series Zio/Zio Plus LCD wall
modules using its various function keys.
The organization of the manual assumes a project
is being engineered from installation to finish.
Applicable Literature
List of documents containing information related to
the configurable lighting controllers as shown in
Table 3.
Table 3: List of applicable literature
For additional CVAHU Stryker and Zio wall module
latest documents and updates visit
http//www.customer.honeywell.com
And search for CVAHU Stryker and Zio wall module
respectively.
Product Names
Stryker LON CVAHU controller is available as one
model.
CUL6438SR-CV1: Constant volume air handling
unit controller from Stryker LON family.
The TR70 series Zio wall module is available in four
models:
TR70
TR70H
TR71
TR71H
The TR70 series Zio Plus wall module is available
in two models.
TR75
TR75H
Other products:
Q7751A, B: Router (configured as a repeater)
Q7752A, B: Serial interface adapter
209541B: Termination module.
12
Device
Agency
Comments
CUL6438SR-CV1
controller
UL
Tested and listed under UL916 (Standard for open energy
management equipment) with plenum rating. File number E87741
cUL
Listed (E87741).
CSA
LR95329-3 listed.
FCC
Meets FCC Part 15, Subpart B, Class B (radiated emissions)
requirements.
Meets Canadian standard C108.8 (radiated emissions).
CE
Conforms to the following requirements per European
Consortium standards:
EN 61000-6-1; 2001 (EU immunity)
EN 61000-6-3; 2001 (EU emissions)
Zio®/Zio Plus LCD
wall modules
TR70, TR71, TR75
with Sylk® bus
UL
(Not applicable.)
cUL
(Not applicable.)
CSA
(Not applicable.)
FCC
(Not applicable.)
CE
(Not applicable.)
Agency Listings
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Table 4: Agency listing
13
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Abbreviations
AHU: Air Handling Unit. The central fan system
includes the blower, heating equipment, cooling
equipment, ventilation air equipment, and other
related equipment.
CO: Carbon Monoxide. Occasionally used as a
measure of indoor air quality.
CO2: Carbon Dioxide. Often used as a measure of
indoor air quality.
CPU: Central Processing Unit
cUL: Underwriters Laboratories Canada
CVAHU: Constant Volume Air Handling Unit; refers to
a type of air handler with a single-speed fan that
provides a constant amount of supply air to the space
it serves.
Echelon: The Company that developed the LON®
bus and the Neuron® chips used to communicate on
the E-bus.
Economizer: Mixed-air dampers that regulate the
quantity of outdoor air that enters the building. In cool
outdoor conditions, fresh air is used to supplement
the mechanical cooling equipment. Since this action
saves energy, the dampers are often referred to as
economizer dampers.
EMI: Electromagnetic Interference. Electrical noise
that can cause problems with communications
signals.
EMS: Energy Management System; refers to the
controllers and algorithms responsible for calculating
optimum operational parameters for maximum energy
savings in the building.
Enthalpy: The energy content of air measured in
BTUs per pound (Kilojoules per Kilogram).
Firmware: Software stored in a nonvolatile memory
medium such as an EPROM.
Floating Control: Floating Control utilizes one digital
output to pulse the actuator open, and another digital
output to pulse it closed.
FTT: Free Topology Transceiver.
IAQ: Indoor Air Quality. It refers to the quality of the
air in the conditioned space, as it relates to occupant
health and comfort.
I/O: Input/Output; the physical sensors and actuators
connected to a controller.
I * R: I times R or current times resistance; refers to
Ohm’s Law: V = I x R.
K: Degrees Kelvin.
NV: Network Variable; a Stryker CVAHU parameter
that can be viewed or modified over the Lon/S-bus
network.
PWM: Pulse Width Modulated output; allows analog
modulating control of equipment using a digital output
on the controller.
RTD: Resistance Temperature Detector; refers to a
type of temperature sensor whose resistance output
changes according to the temperature change of the
sensing element.
TPT: Twisted Pair Transceiver.
VA: Volt Amperes; a measure of electrical power
output or consumption as applied to an AC device.
Vac: Voltage alternating current; AC voltage rather
than DC voltage.
VAV: Variable Air Volume; refers to either a type of
air distribution system, or VAV Box Controller that
controls a single zone in a variable air volume delivery
system.
Constructions of
Controller and Wall
Module
For more details, refer to the following literature:
63-4529–03: Stryker™ Lon Configurable
VAV/CVAHU Controller Specification Data
62-2029–02: Stryker™ Lon Configurable
Strykers are configured by the new TR71/75 wall
modules. Nearly every configuration parameter is
available at the Zio wall module, so configuration and
even balancing is done by simply powering up the
controller, connecting a Zio and then configuring the
parameters available. After configuration is done via
the Zio, an Integrator perform an upload and the
configuration is added to the WEBs-AX station
database.
Since Stryker has the capability to utilize Zio, an
installer uses a conventional sensor on all installed
Stryker units, and then uses a single Zio to configure
as many Stryker’sas desired. Since the Zio’s program
and configuration are stored in the Stryker, each time
the Zio is connected to a new Stryker, it gets its
program from that device.
This document serves as a configuration guide for an
installer who is configuring a Stryker CVAHU
controller via a TR71 or TR75 wall module.
Parameters are grouped into logical categories rather
than on a large list. To access the “contractor” mode
for configuration, press the up, down and middle keys
simultaneously. During this time the model number
and firmware revision of the TR71/75 are displayed.
You are then prompted to enter a password (default
0000).
Compatibility
The TR70 Series LCD Wall Modules operate with the
Sylk Enhanced Stryker controller. The TR71/TR75
can replace a TR70 in an installation where an
upgrade to WEBs- AX or Stryker or reprogramming is
not desired. Features like scheduling, additional
memory, etc. are not available. Likewise, a TR71 is
replaced by another TR71 or TR75 without
reprogramming required. A TR75 can only be
replaced with a TR75 where no reprogramming is
desired.
Contractor Mode:
Introduction
Contractor mode: You can navigate to the desired
category of parameters. You can then begin
configuring and viewing information from the device.
Each screen below has a brief explanation of the
data; values within the contractor mode are only
visiable in English (U.S.) units of measure.
Temperatures however can be shown on the home
screen as C or F.
Contractor mode allows access to the Setup function
of the wall module. To enter and exit the setup
function – press the up and down arrow keys and the
middle soft key all at the same time (see key positions
of wall module as shown in Figure 5).
Figure 5: Key position of wall module
Contractor mode allows advanced options (such as
modifying configured parameters) using the soft keys.
Contractor mode also allows for customizing the
tenant’s view including setting the tenant’s Home
screen and controlling the tenant’s “view more”
access, which can provide the tenant with a view of
the configured parameters.
15
STRYKER CVAHU ZIO CONFIGURATION GUIDE
IMPORTANT:
1. Make sure the TR70 Series wall module is
properly mounted and properly wired and
connected to the programmable controller.
2. Refer to the Zio™ LCD wall modules TR70 Series with Sylk™ bus – installation
instructions, form no. 62 – 0271, for
specific installation requirements.
Initial Power-Up
Upon initial power-up before configuring the wall
module, the LCD screen of the wall module will
display status as “PLEASE LOAD”. As shown in
Figure 6, the startup screen of the wall module where
the status is displayed.
And also illustrates all the possible LCD Wall Module
display elements. Only those elements pertinent to
the current configuration and status actually display.
Controller features not supported by Zio
configuration
Wall module: Zio
Center setpoint source: Zio
Center setpoint: disabled (controller ignores
center setpoint value
Center setpoint high limit: 100
Center setpoint low limit: –10
Room temperature source: Zio (TR71/75)
Figure 6: TR70 Series Wall Module - LCD screen
This phrase alternates with any onboard sensor
display such as temperature. The TR71/TR75 also
display the firmware revision number, model number
and Sylk bus address as shown in Figure 7.
Figure 7: Model number and Sylk bus address
On power-up, screen displays revision and Zio model
number.
16
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Contractor Mode:
Configuration Steps
The Contractor Mode screen as shown in Figure 8
Figure 8: Contractor mode default home screen
The three soft keys on the contractor home screen
provide the following three options
1. Set home screen
2. Set view more
Figure 9: Home screen Roomtemp
Home screen: ROOMTEMP
Description: Default home screen displays room
temperature (setpoint is not adjusted from this home
screen as shown in Figure 10)
3. Parameters
Set Home Screen
SET HOME SCREEN allows the contractor to choose
among multiple home screen options for the tenant.
The tenant’s home screen choices are created by the
configuration wizard and downloaded to the wall
module. Each wall module may have different home
screen choices. The contractor, using the soft keys,
may choose which home screen is to be used. He
may configure the Tenant view to show a subset (or
none) of the configured parameters.
When the contractor clicks the SET HOME SCREEN
soft key, the display changes as shown in the Figure
9 to Figure 12. The soft keys change to DONE,
CANCEL, and NEXT as per configuration
requirement.
Click NEXT soft key to cycle through the
configured home screens.
Click DONE soft key when the desired home
screen to be set as default home screen for
Tenant view.
The CANCEL soft key exits the home screen
display without saving any changes.
Figure 10: Home screen Room Setpoint,
Roomtemp
Home screen: ROOM SETPOINT, ROOMTEMP
Description: Displays room temperature and
effective room temperature setpoint (setpoint is not
adjusted from this home screen)
17
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Note:Click NEXT, DONE, and CANCEL to do
YES or NO configuration for below
mentioned parameters.
Figure 11: Home screen Outside Room
Temperature
Home screen: OUTSIDE ROOMTEMPERATURE
Description: Displays outside air temperature and
room temperature (setpoint is not adjusted from this
home screen)
Figure 12: Home screen Room, Room Setpoint
Temperature
Home Screen: ROOM, ROOM SETPOINT
TEMPERATURE
Description: Displays room temperature and room
setpoint temperature (setpoint is adjusted from this
home screen)
Set View More
SET VIEW MORE allows the contractor to provide
parameter access (view only or adjustable) to the
tenant’s VIEW MORE soft key.
Click SET VIEW MORE soft key to display the first
configured parameter as shown in Figure 13.
Figure 13: Set View More First screen
The soft keys changes to DONE, CANCEL, and
NEXT as per configuration requirement.
The Up and Down arrow keys switch the
parameter between YES and NO (view or no
view in tenant mode).
oYES means that the tenant has access to
the parameter on the VIEW MORE screen.
oNO means that the tenant does not have
access to the parameter.
oIf NO is selected for all parameters, then the
VIEW MORE soft key does not display in
tenant mode.
Click NEXT soft key to cycle through the
configured VIEW MORE screen’s next parameter
or category
Click DONE soft key to save configuration
changes.
Click CANCEL soft key to exit VIEW MORE
without saving any changes.
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.