Honeywell SS2 Specifications

Fire Sentry SS2-AM & SS2-AML SPECIFICATIONS
Multi-Spectrum Digital Electro-Optical Fire and Flame Detector
General Specifications Sensitivity 60 ft. to a 1 sq. ft. n-heptane fire Response Time 3.9 milliseconds to explosive fire Field-of-View 120 degrees cone of vision (60 degrees from on axis). Spectral Sensitivity Ultraviolet: 185 to 260 nanometers
Wide Band Infrared: 0.7 to 3.5 micrometers Visible: 400 to 700 nanometers
Input Power 24 Vdc nominal (20.5 to 34 Vdc) Power Consumption 56 mA normal operation
68 mA alarm condition
Output Relays Fire Alarm Relay: NO & NC contacts
Latching / Non-Latching, factory set Normally de-energized Fault Relay: NO & NC contacts Normally energized Relay contact ratings: 0.5A at 120 Vac, 1.0a at 24 Vdc
Operating Temperature -40° to 185°F (-40° to 85°C) Humidity Range 10 to 90% RH, non-condensing Vibration MIL.STD.810C Weight 3.8 pounds - Aluminum
7.6 pounds - 316 Stainless Steel Housing Copper-free aluminum (less than 0.4%) powder coated NEMA4, NEMA4X-IP66, tamper resistant with integral dual 3/4” NPT conduit openings
316 Stainless steel housing available Electrical Certifications Explosion-proof
Class I, Div. 1 & 2, Groups A, B, C and D Class II, Div. 1 & 2, Groups E, F and G Class III
Mounting Swivel bracket assembly (SM4-optional); 316 Stainless Steel Warranty Two years from factory shipping date
Maximum Sensitivity
Field of View, Horizontal and Vertical Sensitivity to 1 sq. ft. nHeptane Pan Fire
Find out more
www.honeywellanalytics.com Toll-free: 800.538.0363
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract.
SS01151B_v1 3/13 © 2013 Honeywell Analytics
General Dimensions
Side and Back Views (All Dimensions in Inches)