Honeywell SPM Data sheet

SPM Flex SPECIFICATIONS
Chemcassette® Tape-Based Gas Detector
General Specifications
Detection Technique Chemcassette tape-based with advanced self monitoring optics design
Dimensions Height: 13.2 in. (33.6 cm); Width: 7.2 in. (18.3 cm);
Depth without handle: 6.4 in. (16.3 cm); Depth with handle: 9.5 in. (24.1 cm)
5
Mounting screws Concrete: equivalent), add 0.25 in. to length when mounting bracket with sun shield Wood: add 0.25 in. to length when mounting bracket with sun shield
Battery type Lithium ion
Battery life Approximately 70% of its original capacity after 300 full charge/discharge cycles
Operating Temperature 0ºC to 40ºC for most gases/applications
Operating Humidity 0-100% RH for unit (Sample RH limited per tape/calibration). Sample line requires additional hardware
to remove moisture in high RH conditions where condensing may occur. The sample must be non-condensing. Dry conditions may require humidification.
/16 in x 2 in vibration-resistant stud anchor for concrete (McMaster-Carr 94475A185 or
5
/16 in. x 2 in. flange head lag screw for wood (McMaster-Carr 95526A375 or equivalent),
Flow System Automatic flow control with bypass system, 250 or 500 cc/min at tape, higher flow at inlet to reduce sample time (internal bypass system); sample up to 100 ft
Local Alarms/Status Visual: LEDs for alarm, normal condition and fault Audible: User selectable: Off, Low ~75 dB at 1 m, Medium ~85 dB at 1 m, High >90 dB at 1 m
Interface 4 large buttons, 3.5 in. Color LCD TFT display, web server
Data Logging Rolling up to 3 months (15 sec. with no gas reading, 1 sec. when reading gas), Event history
(1500 events – approx. 1 year)
Maximum inlet/ outlet pressure differential
Relays 250 V, 6 A maximum
Wire gauges Minimum: 24; Maximum: 14
USB 2.0 or later
Indoor/outdoor use? Both (the power supply is indoor only)
Operating Altitudes -1,000 to 3,000 ft. above sea level: standard; 3,000 ft. to 6,000 ft. above sea level:
requires adjustment by Honeywell Analytics
Ingress Protection rating IP65
External switch or circuit breaker requirement Meet or exceed all local codes and regulations (description & location)
The overall maximum load on the pump between the inlet and the exhaust should not exceed 10 inches H
O
2
Ventilation requirements Mount with no obstructions within 4 in. (10 cm) of either side or within 2 in. (5 cm) above and below the detector
Electrical
Power supply Universal Line powered (90-260 VAC 50/60 Hz) for battery charger & non-classified use. Battery: 6+ hours
under typical conditions – acts as battery back-up in fixed applications
Power consumption ~1.9 A at 24 VDC (including battery-charging current)
Power adaptor Manufacturer: FSP Group
Model: FSP135-AAAN1 Input: 100-240 VAC, 2 A, 50-60 Hz Output: 24 VDC, 5.62 A CCN: QQGQ (E190414) Mark of conformity: UL listed
Communications
Relays: Alarm 1, Alarm 2, Fault (user configurable for normally open/closed) 4-20mA Ethernet (with Modbus TCP/IP and web server) USB port (for memory stick configuration/data transfer) Communications connector and optional communications cable: 60 V, 5 A maximum
4-20 mA Output Defaults and Ranges
Inhibit 2 mA, programmable from 1.5-3.5 mA in 0.5 mA increments
Maintenance 3 mA, programmable from 1.5-3.5 in 0.5 increments
Instrument Fault 1 mA or less, not programmable (will be driven under 1 mA)
Over-Scale 21.5 mA, programmable 21-22 mA
4-20 mA Configurations Sink, source, isolated
Storage Conditions
Detector 0°C to 40°C, 0-100% RH non-condensing
Chemcassette cartridges See the label on the Chemcassette cartridge for storage conditions
Certifications
Detector UL 61010-1, 3rd Edition, 2012-05 (ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL,
AND LABORATORY USE - Part 1: General Requirements CAN/CSA-C22.2 No. 61010-1, 3rd Edition, 2012-05, (ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE - Part 1: General Requirements) IEC 61010-1:2010, 3rd Edition FCC approval for RFID board + Canadian and European
Battery UL/cUL Recognition to UL 2054 + 60950-1 IEC 62133 1st Edition CB Certification
UN Test Report to UN 38.3
Self-declared European CE Mark on detector for:
EMC, LVD, ROHS, WEEE
Detectable Gases
Opti­mum
Temp
Range
11
(ºC)
90 0-40
90 0-35
90 0-35
90 0-40
90 0-35
90 0-40
Optimum
%RH Range
for Best
Accuracy
10-70% RH
30-70% RH
30-70% RH
34-50% RH
40-50% RH
10-60% RH
10-75% RH
15-75% RH
30-50% RH
20-50% RH
15-60% RH
40-50% RH
40-50% RH
15-75% RH
30-50% RH
20-50% RH
15-60% RH
40-50% RH
40-50% RH
30-55% RH
5-75% RH
0-85% RH
10-70% RH
5-90% RH
0-90% RH
5-90% RH
5-90% RH
1-90% RH
1-95% RH
25-65% RH
5-80% RH
15-85% RH
15-90% RH
20-75% RH
10-70% RH
15-70% RH
25-90% RH
15-90% RH
35-50% RH
7,8
5, 6, 9
5, 6, 9
Family Gas Range TLV
Arsine (AsH
) 0.5-500ppb 5 ppb 1 ppb 2.5 ppb 5 ppb 55
3
at 2 TLV
(sec)
Max.
Sample
Tubing Length
(m)
Sample Line
Particulates
2
Filter
ChemCassette
(14d)
Default Alarm
1
LAL
A1 A2 Name
Response
Time (T50)
Gas Conc.
P/N
P/N
(30d)
10
P/N
(90d)
Allowable Days After
First Use
Phosphine (PH3) 3-3000 ppb 300 ppb 5 ppb 150 ppb 300 ppb 6
Diborane (B2H6) 5-1000 ppb 100 ppb 10 ppb 50 ppb 100 ppb 14
Hydrides
Silane (SiH4) 0.03 - 50 ppm 5 ppm 0.05 ppm 2.5 ppm 5 ppb 13
30 A
Flex CC XP Hydrides
1265­4000
1265-
n/a
3000
Germane (GeH4) 50-2000 ppb 200 ppb 100 ppb 100 ppb 200 ppb 245
Hydrogen
Selenide (H2Se)
Hydrogen
Sulphide (H2S)
Hydrogen Fluoride
(HF)
Hydrogen
Chloride (HCl)
Hydrogen
Bromide (HBr)
Mineral
Acids
Boron Trifluoride
(BF3)
Nitric Acid (HNO
Sulfuric Acid
(H2SO4)
Hydrogen Fluoride
(HF)
Hydrogen
Chloride (HCl)
Mineral
Acids
(export
unre-
stricted)
Hydrogen
Bromide (HBr)
Boron Trifluoride
(BF3)
Nitric Acid (HNO
Sulfuric Acid
(H2SO4)
Chlorine (Cl
Chlorine (Cl2) 0.01-5 ppm 0.5 ppm 0.05 ppm
Oxidizers
Fluorine (F
Nitrogen Dioxide
(NO
Chlorine Dioxide
(ClO2)
Ammonia (NH
Dimethylamine (DMA, H2Cl2Si)
Amines
Tetrakis (Dimeth-
ylamido) Titanium
(TDMAT, C8H24N4Ti)
Trimethylamine
(TMA, C3H9N)
Phosgene Phosgene (COCl2) 2-2000 ppb 100 ppb 5 ppb 50 ppb 100 ppb 15 30 A
Toluene
Diisocyanate (TDI,
C
9H6N2O2
Methylene Bisphe-
Diisocya-
nyl Isocyanate
nates
(MDI, C15H10N2O2)
Hexamethylene
Diisocyanate
(HDI, C
8H12N2O2
Hydrazine (N
Hydrazines
CH
Dimethyl Hydrazine
(UDMH, C
Monomethyl
Hydrazine (MMH,
Hydrogen Cyanide (HCN) 0.2-30 ppm 4.7 ppm 0.5 ppm 2.4 ppm 4.7 ppm 15 30 A
Sulphur Dioxide (SO2) 10-2500 ppb 250 ppb 25 ppb 120 ppb 250 ppb 12 30 B, C
Ozone (O3) 20-1000 ppb 100 ppb 25 ppb 50 ppb 100 ppb 55 5 no filter Flex CC Ozone
Hydrogen Peroxide (H2O2) 0.1-3 ppm 1 ppm 0.2 ppm 0.5 ppm 1.0 ppm 27 5 no filter
1 Source: ACGIH 2014. 2 A = 780248 (disposable), B = 1830-0055 (filter membrane 0235-1072 must be replaced every 30 days), C = 1991-0147 (disposable) Outside of RH range:
3 Tends to have lower response at higher humidities. 4 Tends to increase sensitivity at higher humidities (due to the chemistry of the reaction). 5 Tends to under-report at higher humidities (typically >75% RH) due to the gas characteristics to adhere or decompose on contact with water/moisture. The response seems to be lower but the actual gas concentration under these high humidity condi-
tions will be lower than expected. 6 Tends to under-report in dry conditions (<25-30% RH). 7 Depending on the combination of temperature and humidity, even within the ranges specified above, a unit’s performance efficiency can be influenced due to condensation, physical tape material changes, or optical changes. Consult Honeywell Analytics’
Service Department. 8 Refer to TechNotes 971131 (Chemcassette 9 Prolonged exposure to high levels of HBr (2xTLV or above) can condense in the system and may require purging with dry gas.
10 For information about the expiration date of the ChemCassette, refer to the 11 The number of days elapsed from the Chemcassette cartridge’s installation. When that limit is reached, the detector will issue a maintenance fault. Honeywell Analytics recommends then replacing the cartridge. However, if it has been removed and properly
stored in the interim, the user has the option of clearing the maintenance fault and continuing to use the cartridge. Advance the tape two turns when resuming monitoring.
2-500 ppb 50 ppb 5 ppb 25 ppb 50 ppb 14
0.001-9.999 1 ppm 0.005 ppm 0.5 ppm 1 ppm 7
ppm
0.02-20 ppm 0.5 ppm 2 ppm STEL-C 0.03 ppm 1 ppm 2 ppm 7
0.02-20 ppm 2 ppm STEL-C 0.03 ppm 1 ppm 2 ppm 5
0.02-10 ppm 2 ppm STEL-C 0.03 ppm 1 ppm 2 ppm 5
0.05-10 ppm 1 ppm
)
0.02-20 ppm 2 ppm 4 ppm STEL 0.05 ppm 1 ppm 2 ppm 15 3
3
5-750 ppb 50 ppb
2015 NIC (0.1ppm
TWA; 0.7ppm STEL/C)
3
0.2mg/m
0.1 ppm 0.5 ppm 1.0 ppm 5
10 ppb 25 ppb 50 ppb 2000 0.1 No filter
0.4-20 ppm 0.5 ppm 2 ppm STEL-C 0.4 ppm 1 ppm 2 ppm 7
0.02-20 ppm 2 ppm STEL-C 0.03 ppm 1 ppm 2 ppm 5
0.02-10 ppm 2 ppm STEL-C 0.03 ppm 1 ppm 2 ppm 5
0.05-10 ppm 1 ppm
)
0.02-20 ppm 2 ppm 4 ppm STEL 0.05 ppm 1 ppm 2 ppm 15 3
3
5-750 ppb 50 ppb
) 0.005-5 ppm 0.5 ppm 0.02 ppm
2
) 0.01-10 ppm 1 ppm 0.1 ppm OSHA PEL 0.05 ppm 0.5 ppm 1.0 ppm 5 10
2
0.03-10 ppm 0.2 ppm 0.05 ppm 0.1 ppm 0.2 ppm 56 30
)
2
2015 NIC (0.1ppm
TWA; 0.7ppm STEL/C)
3
0.2mg/m
0.1 ppm 0.5 ppm 1.0 ppm 5
10 ppb 25 ppb 50 ppb 2000 0.1 No filter
0.25
0.5 ppm 7 30 B, C
ppm
0.25
0.5 ppm 9 30
ppm
20-1000 ppb 100 ppb 25 ppb 50 ppb 100 ppb 36 10
) 0.01-150 ppm 25 ppm 0.05 ppm
3
12.5 ppm
25 ppm 5
0.5-50 ppm 5 ppm 0.1 ppm 2.5 ppm 5 ppm 10
0.01-20 ppm n/a 0.05 ppm 1 ppm 2 ppm 14
0.3-50 ppm 5 ppm 0.05 ppm 2.5 ppm 5 ppm 10
0.5-200 ppb 1 ppb
)
2015 NIC (1ppb TWA;
5ppb STEL)
0.6 ppb 1 ppb 2 ppb 10
0.5-200 ppb 5 ppb 0.6 ppb 2.5 ppb 5 ppb 10
0.5-150 ppb 5 ppb 0.6 ppb 2.5 ppb 5 ppb 30
)
) 3-1000 ppb 10 ppb 5 ppb 5 ppb 10 ppb 220 3
2H4
3-2000 ppb 10 ppb 5 ppb 5 ppb 10 ppb 11 0 5
)
6N2
3-2000 ppb 10 ppb 5 ppb 5 ppb 10 ppb 11 0 5
)
2H8N2
®
-based Instrument Accuracy and Precision) and 1998-0219 (Protocol for Testing Gas Detectors).
Review > Chemcassette
section on page 36 of the SPM Flex User Manual.
5
B, C
5
B, C
B, C
30 B, C
0.15 no filter
no filter
Flex CC XP Mineral Acids
Flex CC-U XP Mineral Acids
Flex CC XP Chlorine
Flex CC Fluorine/Oxidizers
Flex CC XP Ammonia
Flex CC XP Phosgene
Flex CC Diisocyanates
Flex CC Hydrazines
Flex CC Hydrogen Cyanaide
Flex CC Sulfur Dioxide
Flex CC Hydrogen Peroxide
1265­4001
1265­4012
1265­4002
1265­4004
1265­4003
1265­4007
1265­4006
1265­4008
1265­4009
1265­4005
1265-
4011
1265­4010
1265-
n/a
3001
1265-
n/a
3012
1265-
n/a
3002
1265-
n/a 30 0-40
3004
1265-
n/a
3003
1265-
n/a
3007
1265-
n/a 30 0-40
3006
1265-
n/a 30 0-40
3008
n/a n/a 15 0-30
1265-
n/a 30 0-40
3005
1265-
n/a 30 0-40
3011
1265-
n/a 30 0-40
3010
4, 6
4, 6
4, 6
4, 6
4, 6
4, 6
4, 6
5, 6
5, 6
5, 6
4, 6
4, 6
5, 6
5, 6
5, 6
4, 6
4, 6
4, 6
5, 6
4
4
4
4
4
4
4
4
4
Honeywell Analytics Gas Detection Offerings
Honeywell Analytics gas detectors protect people, assets and environment from toxic and combustible gas hazards, helping to create safer, more comfortable, secure and productive environments. Our strength derives from Honeywell’s leadership in sensor technology; in fact Honeywell operates four sensor manufacturing plants, supplying an entire industry with its core detective element.
Commercial
Gas detection from standalone units to fully engineered, multi-point systems, all offering cost-effective regulatory compliance.
» Applications: parking structures,
chillers, mechanical rooms, office towers, commercial buildings, shopping centers, swimming pools, golf courses, schools and universities, laboratories
Find out more: www.honeywellanalytics.com
Contact Honeywell Analytics:
Americas
Honeywell Analytics Inc. 405 Barclay Blvd. Lincolnshire, IL USA 60069 Tel: 847.955.8200 Toll free: 800.538.0363 Fax: 847.955.8210 detectgas@honeywell.com
Technical Services ha.service@honeywell.com
www.honeywell.com
Industrial
Renowned Sieger and Manning gas detection systems with advanced electrochemical, infrared and open path sensing technologies.
» Applications: oil and gas, cold
storage, water/wastewater treatment, chemicals, engine rooms, plastics and fibers, agriculture, printing and light industrial
High Tech/Government
Reliable gas and chemical detection including infrared spectroscopy (MST) with no cross interference, to Chemcassette paper-based solutions (MDA Scientific) offering detection down to parts per billion.
» Applications: semiconductor
manufacturing, aerospace propulsion, specialty chemicals industry, research laboratories, emergency response
Europe, Middle East, Africa
Life Safety Distribution AG Javastrasse 2 8604 Hegnau Switzerland Tel: +41 (0)44.943.4300 Fax: +41 (0)44.943.4398 gasdetection@honeywell.com
Portables
Single or multi-gas detectors ranging from compact, lightweight designs for personal protection to systems-based, networkable instrumentation for industrial hygiene.
» Applications: underground utility
and electricity ducts, boiler rooms, post-fire sites, sewers, industrial plants, industrial hygiene, first responder teams, remote fleets
Technical Services
24/7 global network includes post-sales service and Systems Integration teams.
» Emergency call out, service
contracts, on/off-site repair, training and commissioning
» Complete range of spares,
consumables and accessories
Asia Pacific
Honeywell Analytics, Asia Pacific #701, Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Tel: +82 (0)2 6909.0300 Fax: +82 (0)2 2025.0329 analytics@honeywell.com
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract.
SS01138-EN_v5 10/15 © 2015 Honeywell International Inc.
Loading...