Honeywell SpectrAlert Specifications

Field-Selectable Emergency Communications Devices
SpectrAlert® Advance emergency communications devices
the time- and money-saving benefits of the SpectrAlert
Advance line.
Emergency Communications Features:
• Plain or ALERT-printed white housings
• Clear or Amber lens strobes and speaker strobes
• Color lens attachments for use with clear lens wall or
ceiling strobes or clear dual strobe expander plates
• Dual Strobe Expander Plates for use with Strobe and
Speaker Strobe devices
• Meets DoD specification requirements
SpectrAlert Advance Features:
• Plug-in design for simplified installation and troubleshooting
• Mounting plate shorting spring easily tests wiring continuity
• Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
• Field-selectable candela settings of 15, 15/75, 30, 75, 95, 110,
115, 135, 150, 177, 185
• Rated from 32°F to 120°F (indoor devices); −40°F to 151°F
(NEMA 4X, IP56 weatherproof devices)
• Optional tamper-resistant Torx head screw
• Compatible with System Sensor synchronization protocol
• Listed for ceiling or wall mounting
Agency Listings
S4048 Speaker & Speaker Strobes
S4011 Horn Strobes** S5512 Strobes S3593 Strobes*
*(outdoor) **(indoor and outdoor)
7125-1653:188 Horn Strobe** 7125-1653:186 Strobes 7125-1653:187 Strobes* 7125-1653:198 Alert Strobes 7320-1653: 201 Speaker & Speaker Strobes** 7125-1653:186/ 7300-1653:198 SW-CLR ALERT
3023572 Horn Strobes** 3030863 Speaker &
Speaker Strobes
SpectrAlert Advance, the broadest and most versatile line of
notification devices available, includes a wide range of devices to
meet emergency communications application requirements.
ALERT-printed on white housings amber lens strobes and speaker
strobes provide visual signaling for emergency communications in
compliance with ANSI/ UL 1638 — Standard for General Signaling
Visible Appliances. Other Plain or ALERT-printed models provide clear
lenses for use with color lens strobe attachments (amber, blue, green,
and red) that easily attach to strobe and speaker strobe devices
without a candela derating.
In addition, SpectrAlert Advance emergency communications
devices include plain (non-printed) strobes, horn strobes, and
speaker strobes. These devices, along with ALERT-printed devices
and SpectrAlert Advance accessories, can meet a wide range
of requirements for indoor and outdoor applications, including
emergency communications, general signaling, severe weather, and
emergency response.
All SpectrAlert Advance emergency communications and general
signaling devices are compatible with the entire SpectrAlert Advance
line and include all the same time- and money-saving innovations.
For example, plug in design simplifies installation and reduces
costly ground faults, universal mounting plates with onboard
shorting springs test wiring continuity to speed installation and
protect devices from damage, and field-selectable settings provide
versatility and enable installers to quickly set each device to meet
application requirements.
SpectrAlert® Advance Specifications
Architectural/Engineering Specications
General
SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. SpectrAlert Advance speaker strobes shall mount to a 4 x 4 x 21/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes, horn strobes, and speaker strobes shall have field-selectable candela settings, including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185.
Strobe
The clear strobe shall be a System Sensor SpectrAlert Advance Model _ ____ _ _ listed to UL 1971 and shall be approved for fire protective service. Colored lens strobes shall be listed to ANSI/UL 1638 and shall be approved for Private Mode Emergency. Outdoor Strobe devices shall be listed to ANSI/UL 1638 for Private Mode Emergency. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model _ ____ __ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. The horn and horn strobe models shall operate on a coded or non-coded power supply.
Speaker Strobe Combination
The speaker strobe shall be a System Sensor SpectrAlert Advance Model _ ____ _ ____ listed to UL 1480 and UL 1971 and be approved for fire protective signaling systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. Speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Outdoor Products
SpectrAlert Advance outdoor strobes, horn strobes, and speaker strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151 degrees Fahrenheit. The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half-inch and three-fourths-inch conduit entries.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Color Lens Strobe Attachment
The System Sensor SpectrAlert Advance color lens attachments shall be approved for fire protective service as listed in UL 1638. The lens attachments shall only be used with (plain non-fire-printed) System Sensor strobe devices. They shall mount to any wall or ceiling strobe and be rated from minus 35 degrees to 151 degrees Fahrenheit.
Physical Specications
Standard Operating Temperature 32°F to 120°F
K Series Operating Temperature −40°F to 151°F
Humidity Range 10 to 93% non-condensing (indoor models)
Dimensions Wall-Mount Strobe and Horn Strobe (including lens)
SPS Speaker Strobe 6.0˝ L x 5.0˝ W x 4.7˝ D (including lens and speaker)
Dimensions Ceiling-Mount Strobe (including lens) 6.8˝ diameter x 2.5˝ D
Electrical/Operating Specications
Nominal Voltage (strobes and horn strobes) Regulated 12 DC/FWR or regulated 24 DC/FWR
Nominal Voltage (speakers) 25 V or 70.7 V (nominal)
Maximum Supervisory Voltage (speakers) 50 VDC
Operating Voltage Range 8 to 17.5 V (12 V nominal) or 17 to 33 V (24 V nominal)
Operating Voltage Range with MDL3 8.5 to 17.5 (12V nominal) or 16.5 to 33V (24V nominal)
Strobe Flash Rate 1 flash per second
Speaker Frequency Range 400 to 4,000 Hz
Speaker Power ¼, ½, 1, 2 watts
Speaker Sound Ouput
UL Reverberant (dBA @ 10 ft.) 2 W 1 W Wall-Mount SPS Series 85 82 79 76 Wall-Mount SPV Series 90 87 84 81
Ceiling-Mount SPC Series 86 83 80 77 Ceiling-Mount SPCV Series 90 87 84 81
AVDS11901
5.6˝ L x 4.7˝ W x 2.5˝ D
1
/2 W
1
/4 W
UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS)
8–17.5 Volts 16–33 Volts
Candela
Standard Candela Range 15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205
High Candela Range 135 NA NA 228 207
150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
8–17.5 Volts 16–33 Volts
DC Input
15 15/75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
16–33 Volts
DC Input
135 150 177 185 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Candela Derating/Outdoor Devices
Strobe Output (cd)
Horn Tones and Sound Output Data
Horn and Horn Strobe Output (dBA)
Listed Candela Candela rating at –40°F
15 15/75
Do not use below 32°F 30
75 44 95 70 110 110
Switch Position
1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 75 75 80 80 86 86 96 96 3 Temporal Low 71 71 76 76 81 79 94 89 4 Non-
115 115 135 135
5 Non-
150 150 177 177 185 185
For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table.
6 Non-
7
8
9
Settings 7, 8 and 9 are not available on 2-wire horn strobe.
DC FWR DC FWR
16–33 Volts
FWR Input
24-Volt Nominal Reverberant Anechoic
Sound Pattern dB
High
Temporal
Medium
Temporal
Low
Temporal
8–17.5 Volts
16–33 Volts
DC FWR DC FWR DC FWR DC FWR
82 82 88 88 93 92 100 100
78 78 85 85 90 89 98 98
73 74 81 81 86 84 96 92
Coded High 82 82 88 88 93 92 101 101 Coded Medium 78 78 85 85 90 89 97 98 Coded Low 74 75 81 81 85 83 96 92
AVDS11901
Ordering Information
Part No. Description
Alert Devices
SEP-SW Strobe Expander Plate, White, Amber Lens
SEP-SPSW Speaker Strobe Expander Plate, White,
Amber Lens
SEP-SW-P Strobe Expander Plate, Standard cd,
White, Plain
SEP-SPSW-P Speaker Strobe Expander Plate,
Standard cd, White, Plain SW-ALERT Wall, Strobe, Standard cd, White, Amber Lens
SWH-ALERT Wall, Strobe, High cd, White, Amber Lens
SW-CLR-ALERT Wall, Strobe, Standard cd, White, Clear Lens
SCW-CLR-ALERT Ceiling, Strobe, Standard cd, White, Clear Lens
SPSW-ALERT Wall, Speaker Strobe, Standard cd, White,
Amber Lens SPSCW-CLR-ALERT Ceiling, Speaker Strobe, Standard cd,
White, Clear Lens SPSW-CLR-ALERT Wall, Speaker Strobe, Standard cd, White,
Clear Lens SPSWK-CLR-ALERT Wall, Speaker Strobe, Standard cd, White,
Clear Lens, Outdoor SPSCWK-CLR-ALERT Ceiling, Speaker Strobe, Standard cd,
White, Clear Lens, Outdoor
Plain Wall Strobes
SR-P Standard cd, Red, Clear Lens
SRH-P High cd, Red, Clear Lens SW-P Standard cd, White, Clear Lens SWH-P High cd, White, Clear Lens SRK-P Standard cd, Red, Clear Lens, Outdoor SRHK-P High cd, Red, Clear Lens, Outdoor SWK-P Standard cd, White, Clear Lens, Outdoor SWHK-P High cd, White, Clear Lens, Outdoor
Plain Ceiling Strobe
SCW-P Standard cd, White, Clear Lens
Plain Wall Horn Strobes
P2R-P Standard cd, Red, Clear Lens P2W-P Standard cd, White, Clear Lens P2WH-P High cd, White, Clear Lens P2RK-P Standard cd, Red, Clear Lens, Outdoor P2RHK-P High cd, Red, Clear Lens, Outdoor
P2WK-P Standard cd, White, Clear Lens, Outdoor
P2WHK-P High cd, White, Clear Lens, Outdoor P4R-P Standard cd, Red, Clear Lens P4W-P Standard cd, White, Clear Lens
Part No. Description
Plain Ceiling Horn Strobes
PC2R-P Standard cd, Red, Clear Lens PC2W-P Standard cd, White, Clear Lens PC2WH-P High cd, White, Clear Lens
Plain Wall Speaker Strobes
SPSW-P Standard cd, White, Clear Lens SPSR-P Standard cd, Red, Clear Lens SPSWH-P High cd, White, Clear Lens SPSRH-P High cd, Red, Clear Lens SPSRV-P Standard cd, Red, High Volume, Clear Lens SPSWK-P Standard cd, White, Clear Lens, Outdoor SPSRK-P Standard cd, Red, Clear Lens, Outdoor
Plain Ceiling Speaker Strobes
SPSCW-P Standard cd, White, Clear Lens SPSCWH-P High cd, White, Clear Lens SPSCWV-P High Volume, White, Clear Lens SPSCWVH-P High cd, High Volume, White, Clear Lens SPSCWHK-P High cd, White, Clear Lens, Outdoor
Colored Lenses
LENS-A Wall-Mount Lens Attachment, Amber LENS-AC Ceiling-Mount Lens Attachment, Amber LENS-B Wall-Mount Lens Attachment, Blue LENS-BC Ceiling-Mount Lens Attachment, Blue LENS-G Wall-Mount Lens Attachment, Green LENS-GC Ceiling-Mount Lens Attachment, Green LENS-R Wall-Mount Lens Attachment, Red LENS-RC Ceiling-Mount Lens Attachment, Red
Notes: All -P models have a plain housing (no “FIRE” marking on cover).
All outdoor units with a “K” designation in the part number include a weatherproof back box. All “ALERT” models are printed as such.
For information on colored lenses, see data sheet AVDS004.
For information on Dual Strobe Expander Plates, see data sheet AVDS117.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
©2014 System Sensor.
AVDS11902 • 1/14