Operating range Operating range Max. pressure Type
(bar) (kPa) (bar)
0 – 0.25 0 – 25 0.75 SN 025-280
0 – 0.6 0 – 60 1.8 SN 06-280
0 – 1 0 – 100 3 SN 1-280
0 – 1.6 0 – 160 6.4 SN 2-280
0 – 2.5 0 – 250 7.5 SN 3-280
0 – 4 0 – 400 16 SN 4-280
0 – 6 0 – 600 18 SN 6-280
0 – 10 0 – 1000 30 SN 10-280
0 – 16 0 – 1600 48 SN 16-280
0 – 25 0 – 2500 70 SN 25-280
0 – 40 0 – 4000 80 SN 40-280
Degree of protection:
IP 65
s
The low-voltage plugs on SN transmitters
can be opened up. This simplifies fitting
and also means that the supply voltage and
output signal can be measured directly from
the opened plug.
As-delivered condition:
The transmitters are fully assembled in the
factory (sensor + evaluation module + cover)
and set to the nominal range. Additional
modules and external modules are supplied
separately.
Type series SN…-280
SN 280
Technical data
Electrical Plug connection
connection DIN 43650 PG 11
Supply voltage 12 V…30 V DC
Ambient temperature 0…+60°C
Material Housing: Makrolon
Sensor: 1.4571
Diaphragm: 1.4435
Degree of protection IP 65
Included accessories Plug DIN 43650
Pressure connection G 1/2 external
Wrench size 27
Installation Directly on
pressure line
Linearity ≤ 1% FS
Compensated range 0–100°C
Response time ≤ 10 ms
Max. medium –30…+110°C
temperature
Measuring principle Piezoresistive
Mounting Directly on
pressure line
Output signal 4…20 mA, imped-
ance
≤ (UB–10 V) / 0.02 A
Overall accuracy ≤ 1% FS
(fixed-point line)
Ambient temperature 0…60°C
Direction of action Rising pressure pro-
duces rising output
signal
Accessories Plug-in display
AZG 241
Pressure transmitters
for liquid and gaseous media. 2-conductor system
Product Summary
Connection scheme SN…-280
The power supply is connected to
terminals 1+ / 2–
75