Honeywell SMV800 Installation Manual

Page 1
SMV800 SmartLine Multivariable Transmitter
Quick Start Installation Guide
Figure 1: Electronic housing components
34-SM-25-04, Revision 8, November 2020
This document provides descriptions and procedures for the quick installation of Honeywell’s family of SmartLine transmitters. The SmartLine Multivariable transmitter is available in a variety of models for measuring differential pressure, static press ur e, pro ces s temperature, volume and mass flow and Totalizer.
For full details refer to the man ual s listed below for protocols , us er Interface (HMI) operation, Install atio n, configuration, calib ra ti on , maintenance, parts, and safety and approvals etc. including options
Copyrights, Notices and Trademarks. Copyright 2020 by Honeywell Revision 8, November 2020
Trademarks SmartLine, SMV800 are U.S. registered trademarks of Honeywell Inc.
HART® is Trademarks of FieldComm Group™
Documentation
To access complete documentation, including language variants, scan the QR code below using your smart phone/device or QR code scanner.
Go to the APP store for your free Smartphone QR scanner
Or you can follow the URL to access the online SmartLine HUB page. The HUB page will contain direct links to open SmartLine product
documentation.
URL QR Code
https://hwll.co/SmartLineHUB
Installation ................................................................................................................... 1
Features and Options ................................................................................................. 1
Mounting the Transmitter ............................................................................................ 2
Bracket mounting ................................................................................................. 2
Mounting bracket ................................................................................................. 2
Rotating Transmitter Housing .............................................................................. 2
Leveling Transmitters with Small Absolute or Differential Pressure Spans .......... 2
Conduit Entry Connectors, Plugs and Adapters .......................................................... 3
Wiring Connections and Power Up ............................................................................. 3
Wiring Variations .................................................................................................. 4
Explosion-Proof Conduit Seal ..................................................................................... 5
Tri m the Transmitter .................................................................................................... 5
Set of Jumpers for Modbus ......................................................................................... 6
Configuration Guide .................................................................................................... 6
Appendix A. PRODUCT CERTIFICATIONS ............................................................... 7
A3. Hazardous Locations Certifications (MSG Code from Table V) .................... 8
MODBUS Communications ........................................................................................ 9
WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60oC USE WIRE
RATED 105oC ...................................................................................................... 9
Control Drawing ........................................................................................................ 10
Table 1: Conduit entry connectors and plugs .............................................................. 3
Table 2 - Conduit Adapters ......................................................................................... 3
Table 3: Wiring details for SMV Modbus Terminal block ............................................. 4
Table 4: AC Termination and Write Protect Jumpers for Modbus ............................... 6
Figure 1: Electronic housing components ................................................................... 1
Figure 2: Mounting brackets ....................................................................................... 2
Figure 3: Angle mounting bracket ............................................................................... 2
Figure 4: Rotating Transmitter Housing ...................................................................... 2
Figure 5: Using level to mount transmitter .................................................................. 2
Figure 6: Electronic Housing Conduit Entries ............................................................. 3
Figure 7: Two-wire power/current loop ........................................................................ 3
Figure 8: Terminal Block and Grounding Screw location ............................................ 3
Figure 9: Thermocouple connections .......................................................................... 4
Figure 10: RTD connections ....................................................................................... 4
Figure 11: Wiring details for SMV Modbus Terminal block ......................................... 4
Figure 12: Transmitter configuration via Modbus (RS-485) network port .................... 5
Figure 13: Jumper location HART ............................................................................... 6
Figure 14: Jumper settings HART ............................................................................... 6
Figure 15: Loading AC termination enable and write protect jumper for Modbus (RS-
485) ............................................................................................................................. 6
Table of Contents
Tables
Figures

Installation

Evaluate the site selected for the transmitter installation with respect to the process system design specifications and Honeywell’s published performance characteristics for your model. Temperature extremes can affect display quality. The display can become unreadable at temperature extremes; however, this is only a temporary condition. The display will again be readable when temperatures return to within operable limits.

Features and Options

The SMV800 is packaged in two major assemblies: the electronics housing and the meter body. The elements in the electronic housing respond to setup commands and execute the software and protocol for the different pressure m eas urem e nt t ypes. Figure 1 shows the assemblies in the electronics housing with available options. The meter body provides connection to a process system. Several physical interface configurations are available, as determined by the mounting and mechanical connections.
The SMV800 SmartLine multivariable transmitter measures differential pressure, static pressure (absolute or gauge), and process temperature. These measurements are used to calculate volumetric or mass flow rates. The measured values and calculated flow can be read by a connected Host. Available communication protocols are Honeywell Digitally Enhanced (DE), HART and Modbus RTU. Digi tal or analog (4-20ma) output modes are available. The SMV800 measures process temperature from an external RTD or thermocouple. Universal temperature input is available as a selectable feature with the device or as license enabled, field upgradable option. With Modbus protocol, Flow calculation capability also is available as selectable feature with the device or as license enabled, field upgradable option while this is a standard feature with HART and DE protocols
Device Variables
SMV800 supports 6 device variables:
1. Differential Pressure
2. Static Pressure
3. Process Temperature
4. Calculated Flow Rate
5. Totalizer
6. Meter Body Temperature.
For DE transmitters, Differential Pressure, Static Pressure, Process Temperature or Flow ma y be assig ne d to analog output. In HART transmitters, Differential Pressure, Static Pressure, Process Temperature, Flow and Totalizer may be mapped to device variables PV (analog output), SV, TV or QV and Meter Body temperature may be mapped to SV, TV or QV. All six variables are Modbus process variables.
SMV800 Quick Start Installation Guide 1
Page 2

Mounting the Transmitter

Mounting bracket

Transmitter models can be attached to a two-inch (50 millimeter) vertical or horizontal pipe using Honeywell’s optional angle or flat mounting bracket; alternately you can use your own bracket.
Typical bracket mount ed in st alla tions
Figure 2: Mounting brackets

Bracket mounting

Mounting bracket, see Figure 3 Rotate the transmitter housing, see Figure 4 Level a transmitter with small abs ol ut e or diff e re ntial pr ess ure sp ans , se e
Figure 5
Position bracket on 2-inch (50.8 mm) and install “U” bolt around pipe and through holes in bracket. Secure with nuts and lock washers provided.
Figure 3 Example - Angle mounting bracket secured to horizontal or
vertical pipe.
Figure 3: Angle mounting bracket

Rotating Transmitter Housing

Use a 2mm hex wrench to loosen the set screw on outside neck of transmitter one full turn. Rotate the transmitter housing to a maximum of 180 degree increment in left or right direction from center to position you require and tighten set scre w (1. 46 to 1 .68 Nm / 13 to 15 lb-in).

Leveling Transmitters with Small Absolute or Differential Pressure Spans

Mounting position of these transmitters is critical due to the smaller transmitter spans.
To minimize these positional effects on calibration (zero shift), take the appropriate mounting precautions that follow for the given transmitter model.
See figure below for suggestions on how to level the transmitter using a spirit balance.
To perform a Zero Trim after leveling, refer to Trim the Transmitter.
Figure 4: Rotating Transmitter Housing
For a model SMA810 or SMA845 transmitters, you must ensure that the transmitter is vertical when mounting it. You do this by leveling the transmitter side-to-side and front-to-back.
Mount transmitter vertically to assure best accuracy. Position a spirit balance on pressure connection surface of AP body.
Figure 5: Using level to mount transmitter
SMV800 Quick Start Installation Guide 2
Page 3

Conduit Entry Connectors, Plugs and Adapters

CONDUIT ENTRY PRECAUTIONARY NOTICE
AUTHORITIES AS APPLICABLE.
Step
Action
1
Remove the protective plastic cap from the threaded conduit entry.
3
Thread the appropriate size conduit connector or plug (M20
adapters or reducers will be used .
4
Tighten plugs per the following table.
M20 Conduit
Entry
½” NPT
Conduit Entry
Step
Action
1
Remove the protective plastic cap from the threaded conduit entry.
2
To ensure the environmental ingress rating on taper ed used.
3
Thread the appropriate size adapter (M20 or ½ NPT) into the conduit entry opening
½ to ¾ NPT
Adapter
power supply end.
Procedures It is the user/installer’s responsibility to install the transmitters in accordance with national and local code requirements. Conduit entry plugs and adapters shall be suitable for the environment, shall be certified for the hazardous location when required and acceptable to the authority having jurisdiction for the plant.
THE CONDUIT/CABLE GLAND ENTRIES OF THIS PRODUCT ARE SUPPLIED WITH PLASTIC DUST CAPS WHICH ARE NOT TO BE USED IN SERVICE. IT IS THE USER’S RESPONSIBILITY TO REPLACE THE DUST CAPS WITH CABLE GLANDS, ADAPTORS AND/OR BLANKING PLUGS WHICH ARE SUITABLE FOR THE ENVIRONMENT INTO WHICH THIS PRODUCT WILL BE INSTALLED. THIS INCLUDES ENSURING COMPLIANCE WITH HAZARDOUS LOCATION REQUIREMENTS AND REQUIREMENTS OF OTHER GOVERNING
Use the following procedures for installation.

Wiring Connections and Power Up

Summary
The transmitter (HART/DE) is designed to operate in a two-wire power/current loop with loop resistance and power supply voltage within the HART/DE operating range shown below.
Table 1: Conduit entry connectors and plugs
2 To ensure the environmental ingress protection rating on
tapered (NPT), a non-hardening thread sealant may be used.
or ½” NPT) into the conduit entry opening. Do not install conduit entry connectors or plugs in conduit entry openings if
Description Tool Torque
10mm Hex Wrench 32 Nm 24 Lb-ft 10mm Hex Wrench 32 Nm 24 Lb-ft
Table 2 - Conduit Adapters
threads (NPT), a non-hardening thread sealant may be
4 Tighten adapters as per the following table.
Description Tool Torque
1 ¼” Wrench 32Nm 24Lb-ft
Figure 6: Electronic Housing Conduit Entries
Note. No conduit connectors or plugs come installed in the housings. All
housings come with temporary plastic dust protectors (red) installed and are not certified for use in any installation.
After wiring the Transmitter as outline in the next sections, torque the screws to
1.1 Nm (10 lb-in)
Supply Voltage for SMV Modbus
Modbus (RS-485) Mod els : 9.5 V to 30 Vdc at terminals. Power Consumption: Average power consumption is 70 mW at 9.5 V
Supply. This includes RS-485 communication at 9600 baud rate at a rate of once per second without termination at room temperature.
Figure 7: Two-wire power/current loop
A minimum of 250 ohms of loop resistance is required to support communications. Loop resistance = barrier resistance., + wire resistance, =receiver resistance, +peripheral device resistance
Loop wiring is connected to the tr ans m i tt er b y attaching the positive (+) and negative (–) loop wires to the positive (+) and negative (–) terminals on th e transmitter terminal block in the electronics housing shown in Figure 8. Connect the loop power wirin g s hield to earth ground only at the power supply end.
Figure 8: Terminal Block and Grounding Screw location
As shown above, each transmitter has an internal terminal to connect it to earth ground. Optionally, a ground terminal can be added to the outside of the Electronics Housing. Screw terminals 1, 2, 3, 5, 6, 7 & 8 only required for single input, terminals 4 and 9 are only used for a Modbus dev ic e
CAUTION: For proper operation of the transmitter, grounding of the transmitter is mandatory. This minimizes the possible effects of noise on the output signal and affords protection against lighting and static discharge
An optional lightning terminal block can be installed in place of the non­lightning terminal block for transmitters that will be installed in areas that are highly susceptible to lightning strikes. As noted above, the loop power wiring shield shoul d onl y be co n nect ed to earth ground at the
SMV800 Quick Start Installation Guide 3
Page 4
Input Sensor Wiring
Loop Wiring (H ART/DE)
Step
Action
1
Remove the end cap cover from the terminal block end of the
3
Feed loop power leads through one end of the conduit
4
Connect the positive loop power lead to the positive (+)
5 6
Replace the end cap, and secure it in place.
Terminal
Number
Description
Wiring must comply with local co des, regulations and ordinances. Grounding may be required to meet various approval body certification, for example CE conformity. Refer to Appendix A of this document for details.
The HART/DE transmitter is designed to operate in a 2-wire power/current loop with loop resistance and power supply voltage within the operating range; see Figure 7.
With an optional remote meter (for HART/DE), the voltage drop for this must be added to the basic power supply voltage requirements to determine the required transmitter voltage and maximum loop resistance. Additional consideration is required when selecting intrinsic safety barriers to ensure that they will supply at least minimum transmitter voltage, including the re qui r ed 250 ohms of resistance (typically within the barriers) needed for digital communications.

Wiring Variations

The above procedures are used to connect power to a transmitter. For loop wiring and external wi rin g, det ai le d drawings are provided for transmitter installation in non-intrinsically safe areas and for intrinsically safe loops in hazardous area locations.
The screw terminals suitable for wirings up to (16AWG)
- Shielded, twisted-pair cable such as Belden 9318 or equivalent must be used for all signal/power wi rin g. Note: If solid core wire is used strip insulation 1/4 in (6 mm). Once inserted under the square washer the stripped portion should be contained under the squa re was he r. If m ult i-str an de d wir e is use d, a ferrule is to be used and the stripped wire should be in the insulated portion of the ferrule. The ferrule can be also used on the solid core wire.
- The cable shield must be connected at only one end of the cable. Connect it to the power supply side and leave the shield insulated at the transmitter side.
After wiring the Transmitter as outline in the next sections, torque the screws to 1.1 Nm (10 lb-in).
Connect the input sensors as shown in Figure 9 below:
RTD Connections
o Resistance temperature detector (RTD) measurements use the 3 or
4 wire approach. The transmitter determines by itself if a 3 or 4 wire
RTD is connected when powered up.
Figure 9: Thermocouple connections
Figure 10: RTD connections
2
Power Supply Wiring (Modbus) Procedure
1. See Figure 8, for parts locations. Loosen the end cap lock
2. Remove the end cap cover from the terminal block end of the
3. Feed twisted pair shielded power supply leads through one
4. Connect the positive power supply lead to the positive (+)
5. Modbus communication wires can be fed through the sam e
6. Feed input sensor wires through the 2nd conduit entrance and
7. Replace the end cap, and secure it in place.
See Figure 8, for parts locations.
electronics housing.
entrances on either side of the electronics housing. The transmitter accepts up to 16 AWG wire. Shield of the cable to be grounded on the supply/host side.
terminal and the negative loop power lead to the negative (-) terminal. Note that the transmitter is not polarity-sensitive.
Feed input sensor wires through the 2nd conduit entrance and connect wire.
using a 1.5 mm Allen wrench.
electronics housing.
end of the conduit entrances on either side of the electronics housing. The transmitter accepts up to 16 AWG wire. Shield of the cable to be grounded on the Supply/Host side.
terminal (Terminal #1) and negative power supply lead to the negative (-) terminal (Terminal #2). Note that the transmitter is not polarity-sensitive.
conduit that is being used for feeding power supply inputs. For details related to Modbus connection refer to Table 3 and the section on SMV Modbus Half-Duple x Modb us (R S-485) Wiring
Procedure.
connect wire.
Figure 11: Wiring details for SMV Modbus Terminal block
Table 3: Wiring de ta i ls for SM V Modbus Termina l bl ock
1 Power Supply input +ve 2 Power Supply input -ve (Return) 3 Modbus (RS-485) A 4 Modbus (RS-485) B 5 Temperature Sensor Input 6 Temperature Sensor Input 7 Temperature Sensor Input 8 Temperature Sensor Input 9 Modbus (RS-485) Common
SMV800 Quick Start Installation Guide 4
Page 5
SMV Modbus Transmitter Connection to a PC based Modbus
the integrated circuits in the Transmitter PWAs are vulnerable to damage by
Step
Action
1
Attach the transmitter to the mounting bracket but do not completely tighten the mounting bolts
2 3
Connect 24 Vdc power to the transmitter. For HART/DE, connect a digital voltmeter to monitor the PV output.
4
Use applicable communicator to establish communications with
PC application
5
While reading the transmitter’s output on a communication
mounting bolts.
6
The local display or applicable communicator can be used to
tightened.
7
If a SMV Modbus transmitter is directly hooked up to DC distributed lines, it is mandatory to use transmitters with lightening protection option. A wire from the earth ground clamp (ref. Figure 8) of transmitter must be connected to earth ground to make the lightening protection effective. Use a size 8 AWG or (8.37mm for this connection.
SMV Modbus Half-Duplex Modbus (RS-485) Wiring Procedure
The Modbus A, Modbus B & Modbus Common inputs are applied to terminals Terminal #3, Terminal #4 & Terminal #9 respectively. A 3-wire approach for Modbus communication is recommended to avoid potential difference related issues and to ensure error-free communication bet we en driv ers and receivers. For Modbus communication, minimum 24 AWG shielded twisted pair cable with nominal characteristic impedance of 120 ohms is recommended. Shield of the communication cable must be connected to chassis ground on host side.
Modbus RS-485 network recommends to use Termination on either side of the network. Typically, 120ohm DC termination on eit h er en ds (Host side & at last device) are provi ded.
Alternately “AC Termination” feature can be enabled internal to the device (refer Figure 12, Table 3), when transmitter is the last device in the network. In this case, external termination (if any) at the transmitter end needs to be removed.
Multiple termination (apart from both ends of the network), can cause communication failure. For improved performance, DC termination is recommended.
Ensure Power lines & Modbus Communication lines are not
swapped during installation/maintenance
2
) bare or green covered wire
.
After wiring the Transmit ter as o utli n e in the next sect io ns, tor q ue the screws to 1.1 Nm (10 lb-in)
(RS-485) Host
For configuration of the Transmitter using Laptop/PC bas e d application
following wiring recommendation are to be followed:
Supply voltage (9.5V to 30V DC) is to be fed between Terminal #1 & Terminal #2.
Sensor inputs can be connected on Terminal #5 to Terminal #8 as per the Sensor type
Isolated USB to RS-485 adaptor is recommended for connecting between PC based Host and Transmitter
Default configuration of Modbus communication parameters unless otherwise changed is: Baud rate – 9600 bps, Parity – None and Device address - 247.
Before connectin g t o the PC bas ed H os t the device needs to be
disconnected from external host (if any).
Isolated RS-485 USB adaptor is recommended when connecting
the transmitter to PC.
Figure 12: Transm it ter co nfi g urat io n via M od bus (RS-485) network
port
(Refer to Table 3: Wiring details for SMV Modbus Terminal block)
ATTENTION: Please take appropriate steps to avoid ESD damage;
stray static discharges.

Explosion-Proof Conduit Seal

When installed as explosion proof in a Division 1 Hazardous Location, keep covers tight while the transmitter is energized. Disconnect power to the transmitter in the non-ha zard ous area prior to removing end caps for service.
When installed as non-incendive equipment in a Division 2 hazardous location, disconnect power to the transmitter in the non-hazardous ar ea, or determine that the location is non-hazardous befo re disconnecting or connecting the transmit t er wi re s.
Transmitters installed as explosionproof in Class I, Division 1, Group A Hazardous (classified) locations in accordance with ANSI/NFPA 70, the US National Electrical Code, with ½ inch conduit do not require an explosionproof seal for installation. If ¾ inch conduit is used, a LISTED explosionproof seal to be installed in the conduit, within 18 inches (457.2 mm) of the transmitter.

Trim the Transmitter

Procedure to trim the transmitter
For a transmitte r wit h a small differential pressure spa n, you must ensure that the transmitter is vertical when mounting it. You do this by leveling the transmitter side-to-side and front-to-back. See Figure 5 for suggestions on how to level the transmitter using a spirit balance. You must also zero the transmitter by following the steps in this table.
Connect a tube between the input connections in the high pressure (HP) and low pressure (LP) heads to eliminate the effects of any surrounding air currents.
the transmitter. For DE transmitter use the SmartLine Configuration Toolkit (SCT3000). For HART, use MCT404-FDC applic a tion or oth er HA R T Communicator with ap plic a ble H on e yw ell DD's.
For MODBUS, use Honeywell’s SmartLine Modbus manager
tool or a voltmeter, position the transmitter so the output reading is at or near zero, and then completely tighten the
perform the zero corrects. This corrects the transmitter for any minor error that may occur after the mounting bolts are
Remove the tube from between the input connections, the power, and the digital voltmeter or communication tool.
SMV800 Quick Start Installation Guide 5
Page 6
SET JUMPERS FOR HART/DE
Step
Action
1
Turn OFF transmitter power.
2
Loosen the end-cap lock, and unscrew the end cap from the electronics side of the transmitter housing.
3
If applicable, carefully depress the tabs on the sides of the
preferred orientation of the display module in the window.
4
5
Screw on the end cap and tighten the end-cap lock.
6
Turn ON transmitter power.
Jumper Settings
Description
Write Protect = ON (Protected)
Figure 14: Jumper settings HART
Step
Action
1
Turn OFF transmitter power.
2
Loosen the end-cap lock, and unscrew the end cap from the electronics side of the transmitter housing.
3
If applicable, carefully depress the tabs on the sides of the
preferred orientation of the display module in the window.
4
Set the AC Termination jumper to the desired action and the jumper positioning.
5
Screw on the end cap and tighten the end-cap lock.
6
Turn ON transmitter power.
AC termination = OFF
Protected)
AC termination = ON
Protected)
AC termination = ON
(Protected)
AC termination = OFF
(Protected)
Setting failsafe direction and write protect jumpers
The SmartLine Multivariable transmitter (DE or HART) provides two jumpers to set the desired failsafe action and write protect option. See
Figure 13.
The top jumper on the electronics module sets the failsafe direction. The default setting is up-scale failsafe. Upscale drives the loop to a value greater than 21mA while down scale drives the loop to a value less than 3.8mA. You can change the failsafe direction by moving the failsafe jumper (top jumper) to the desired position (UP or DOWN). The bottom jumper sets the write protect. The default setting is OFF (Un-protected). When set to the ON (Protected) position, changed configuration parameters cannot be written to the transmitter. When set to the OFF (Un-protected) position, changed configuration parameters can be written to the transmitter.
ATTENTION: Electrostatic Discharge (ESD) hazards. Observe precautions for handling electrostatic sensitive devices.
display module and pull it off. If necessary, move the interface connector from the communication module to the display module to provide the
Set the failsafe jumper (top jumper) to the desired action (UP or DOWN). And the write protect jumper (Bottom jumper) to the desired behavior (Protected or Unprotected) See Figure 14 for jumper positioning.
Figure 13: Jumper location HART
Failsafe = UP (High) Write Protect = OFF (Not Protected)
Failsafe = DOWN (Low) Write Protect = OFF (Not Protected)
Failsafe = UP (High) Write Protect = ON (Protected)
Failsafe = DOWN (Low)

Set of Jumpers for Modbus

The SmartLine Multivariable Modbus transmitter provides two jumpers to set the desired AC Termination setting and write protect option. See
Figure 15.
ATTENTION: Electrostatic Discharge (ESD) hazards. Observe precautions for handling electrostatic sensitive devices
display module and pull it off. If necessary, move the interface connector from the communication module to the display module to provide the
write protect jumper to the des ir ed be h av ior (Se e Figure 15 for
Table 4: AC Termination and Write Protect Jumpers for Modbus
Jumper Arrang em ents Description
(Disabled) Write Protect = OFF (Not
(Enabled) Write Protect = OFF (Not
(Enabled) Write Protect = ON
(Disabled) Write Protect = ON

Configuration Guide

This transmitter comes with a standard factory configuration. Consult the nameplate for basic information. Reconfiguration for your particular application can be accomplished by following instructions in the Transmitter User’s manual. This can be found by following the website URL or QR code on page 1 of this document.
Figure 15: Load i n g AC ter m i nation enable a nd wr it e protect jumper
for Modbus (RS-485)
SMV800 Quick Start Installation Guide 6
Page 7

Appendix A. PRODUCT CERTIFICATIONS

SIL 2/3
IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV Nord Sys Tec GmbH & Co. KG
2010; IEC61508-3: 2010.
A1. Safety Instrumented Systems (SIS) Installations
For Safety Certified Installations, please refer to SMV800 SmartLine Multivariable Safety Manual 34-SM-25-05 for installation procedure and system requirements.
Certification
A2. European Directive Information (CE Mark)
under the following standards: IEC61508-1: 2010; IEC 61508-2:
SMV800 Quick Start Installation Guide 7
Page 8
MSG CODE/ AGENCY
TYPE OF PROTECT ION
Electrical
Parameters
Ambient
Temperature
Explosion proof:
IIIC T 95oC..T 115oC Db
Intrinsically Safe:
T4 Ga
Non-Incendive and
T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Standards: FM 3600:2018; ANSI/ ISA 60079-0: 2013; FM
2003 ; ANSI/ IEC 60529 : 2004
Explosion proof:
T 95oC..T 115oC Db
Intrinsically Safe:
Ex ia IIC T4 Ga
Non-Incendive and
Class I Zone 2 AEx nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Standards:
CSA C22.2 No 25:2017; CSA No 61010 CSA C22.2 No 213: 2017; CSA C22.2 No 60529:2016; CSA C22.2 No 60079 11:2014; CSA C22.2
12.12.01:2017; ANSI/UL 61010 0:2013(R2017); ANSI/ UL 60079 ANSI/ UL 60079 60079 2017; UL 913:2015; UL 916: 2015; FM3615: 2006; FM 3616: 2011; FM 3600: 2011; ANSI/UL 50E: 2015
Flameproof:
T 115oC Db
Intrinsically Safe:
II 1 G Ex ia IIC T4 Ga
Non Sparking and
II 3 G Ex ic IIC T4 Gc
Note 2
Standards: EN 60079-0: 2018; EN 60079-1 :2014; EN 60079-11: 2015/A1: 2018
Enclosure: IP66/ IP67
Intrinsically Safe:
Ex ia IIC T4 Ga
Non Sparking:
Ex ic IIC T4 Gc
Flameproof: Ex tb IIIC T 95oC.. T 115 oC Db
Enclosure: IP66/ IP67
Standards: IEC 60079-0: 2017; IEC 60079-1:2014; IEC 60079-11:
2011; IEC 60079-7: 2018; IEC 60079-31: 2013; IEC 60079-26: 2014
Intrinsically Safe: Ex ia IIC T4 Ga
Non Sparking: Ex ic IIC T4 Gc
Flameproof:
Ex tb IIIC T 95oC..T 115 oC Db
Enclosure: IP66/ IP67
Intrinsically Safe: Ex ia IIC Ga
Non Sparking: Ex ic IIC T4 Gc
Flameproof:
Ex tb IIIC T 95oC..T 115 oC Db
Enclosure: IP66/ IP67
Standards: ABNT NBR IEC 60079-0:2013 (IEC 60079-0:2011); ABNT
26:2006);
ABNT NBR IEC 60079-31:2014 (IEC 60079-31:2013).
Intrinsically Safe:
Ex ia IIC T4 Ga
T4: -50oC to 70oC
Non Sparking: Ex nA IIC T4 Gc
Flameproof:
Db
Enclosure: IP66/ IP67
Flameproof:
Ex tD A21 T 95oC..T 115oC
Intrinsically Safe:
Ex ia IIC Ga
Ex d IIC T6..T5 Ga/Gb Ex tb IIIC T 95oC..T 115oC Db
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Intrinsically Safe: Ex ia IIC T4 Ga
Non Sparking: 2 Ex nA IIC T4 Gc
Enclosure : IP 66/67
II 1/ 2 G Ex db IIC T6..T5 Ga/Gb
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
T4: -50 ºC to 70ºC
FISCO
Enclosure : IP 66/67
1/ ATEX and
IECEx
Combined ATEX and IECEX See codes C and D
HART and DE
Voltage= 11 to 42 V
Current = 4-20 mA Normal (3.8 – 23 mA Faults)
A3. Hazardous Locations Certifications
(MSG Code from Table V)
Class I, Division 1, Groups A, B, C, D Class I, Zone 0/1, AEx db IIC T6..T5 Ga/Gb
A/ FM ApprovalsTM
Dust Ignition Proof:
Class II, Division 1, Groups E, F, G; Suitable for Division 1, Class III; Class II, Zone 21, AEx tb
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G Class I Zone 0 AEx ia IIC
Intrinsically Safe:
Class I, Division 2, Groups A, B, C, D Class I Zone 2 AEx nA IIC T4 Gc Class I Zone 2 AEx ic IIC
3615:2018; ANSI/ ISA 60079-1 :2015; FM 3616: 2011 ; ANSI/ ISA 60079-31 :2015; FM 3610:2018; ANSI/ ISA 60079-11 :2014; FM 3810 : 2018; ANSI/ ISA 60079-26 :2017; FM 3611:2018; ANSI/ ISA 60079-15 : 2013; ANSI/ ISA 61010-1: 2004;NEMA 250 :
Note 1
Note 2 T4: -50oC to 70oC
Note 1 T4: -50oC to 85oC
T95 oC /T5: -50 ºC
to 85ºC
T6: -50 ºC to 65ºC
B/ CSA­Canada
Class I, Division 1, Groups A, B, C, D
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G Suitable for Division 1, Class III; Zone 0/1, Ex db IIC T6..T5 Ga/Gb Class I, Zone 0/1, AEx db IIC T6..T5 Ga/Gb Ex tb IIIC T 95oC.. T 115oC Db Class II, Zone 21, AEx tb IIIC
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G;
Intrinsically Safe:
Class I, Division 2, Groups A, B, C, D Ex nA IIC T4 Gc
CSA C22.2 No 0: 2010 (R2015); CSA C22.2 No. 0-M91;
-1: 2012 (R2017); CAN/ CSA-C22.2 N o.157: 1992(R20 16);
-0:2015; CSA C22.2 No 60079-1: 2016; CS A C22.2 60079-
-31 :2015; ANSI/ IEC 60529-2004(R2011); ANSI/UL 122701:
60079-15:2016; CSA C22.2 60079-31:2015; ISA
-15:2013(R2017); ANSI/ UL 60079-26 :2017; ANSI/ UL
Note 1
Note 2 T4: -50oC to 70oC
Note 1 T4: -50oC to 85oC
C22.2 No 30M; 1986(R2016);CSA C22.2
-1: 2016; ANSI/ UL 60079-
-1:2015; ANSI/ UL 60079-11:2014;
T5: -50 oC to 85oC T6: -50 oC to 65 oC
Sira 15ATEX2039X II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T 95oC..
Sira 15ATEX2039X
C/
ATEX
IECEx
Intrinsically Safe:
Sira15ATEX4040X II 3 G Ex ec IIC T4 Gc
2012; EN 60079-31: 2014; EN 60079-26 :2015; ; EN 60079-7:
IECEx SIR 15.0022X
IECEx SIR 15.0022X Ex ec IIC T4 Gc
D/
Ex db IIC T6..T5 Ga/Gb
E/
SAEx (South Africa)
Ex ec IIC Gc
Ex db IIC T6..T5 Ga/Gb
Note 1
Note 2 T4: -50oC to 70oC
Note 1
Note 2
Note 1
Note 2 (ic)
Note 1
Note 2
Note 1
Note 2 (ic)
Note 1
T5/ T95oC: -50 ºC to
85ºC
T6: -50 ºC to 65ºC
T4: -50oC to 85oC
T4: -50oC to 70oC
T4: -50oC to 85oC
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
T4: -50oC to 70oC
T4: -50oC to 85oC
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
G/
NEPSI
(CHINA)
H/
KOSHA
(Korea)
I/
EAC Ex
(Russia,
Belarus and
Kazakhstan)
K/
UATR
(Ukraine)
Notes
1. Operating Parameters:
2. See Control Drawing 50128060, on Page 10. Intrinsically Safe Entity Parameters
Ex d IIC T6..T5 Ga/Gb Ex tb IIIC Db T 95oC..T 115 oC
Ex d IIC T6..T5
Intrinsically Safe: Ex ia IIC T4 Ga
Note 2 Note 1 T4: -50oC to 85oC
Note 1
Note 1
Note 2 T4: -50oC to 70oC
Note 1 Note 2 T4: -50 ºC to 70ºC Note 1 T4: -50oC to 85oC
Note 1
Note 2
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
T4: -50oC to 45oC
Ex ec IIC T4 Gc
F/
INMETRO
(Brazil)
SMV800 Quick Start Installation Guide 8
Ex db IIC T6..T5 Ga/Gb
NBR IEC 60079-1:2009 (IEC 60079-1:2007); ABNT NBR IEC 60079­11:2013 (IEC 60079-11:2011); ABNT NBR IEC 60079-15:2012 (IEC 60079-15:2010); ABNT NBR IEC 60079-26:2008 (IEC 60079-
Note 2
Note 1
Note 2 (ic)
Note 1
T4: -50oC to 70oC
T4: -50oC to 85oC
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Page 9

MODBUS Communications

MSG AGENCY
TYPE OF PROTECT ION
Ambient Temperature
Explosion proof:
T 95o.. T 115oC Db
C
Non-Incendive
Class I Zone 2 AEx nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Standards: FM 3600:2018; FM 3610: 2018; ANSI/ ISA 60079-0:
1: 2004;NEMA 250 : 2003 ; ANSI/ IEC 60529 :
2004
Explosion proof:
T 115oC Db
Non-Incendive
Class I Zone 2 AEx nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Standards: CSA C22.2 No 0: 2010(R2015); CSA C22.2 No. 94-M91;
26: 2016;
-
2006; FM 3600: 2011; ANSI/UL 50E: 2015
Flameproof: Non Sparking
Standards: EN 60079-0: 2018; EN 60079-1 :2014; EN 60079-31: Enclosure: IP66/ IP67
Non Sparking:
T4: -50oC to 85oC
Flameproof: Ex tb IIIC T 95oC.. T 115 oC Db
Enclosure: IP66/ IP67
Standards: IEC 60079-0: 2017; IEC 60079-1 :2014;
W/ ATEX
Combined ATEX and IECEX Voltage= 9 to 32 V
Current= 30 mA
A4. Marking ATEX Directive
Protection type Temperature Class
T4
Ex ia
Ta = -50°C to 70°C or -50°C to 45°C Tp = -40 to 125°C
Ex ic
Ta = -50°C to 85°C or -50°C to 45°C Tp = -40 to 125°C
Protectio n type
Temperature Class
T4
T5
T6
Ex db
Ta = -50 to 85°C Tp = -40 to 125°C
Ta = -50 to 85°C Tp = -40 to 100°C
Ta = -50°C to 65°C Tp = -40 to 85°C
A.5 continued …
Protection type Temperature Class
T95°C…115°C/T4
Ex tb and Ex ec
Ta = -50 to 85°C Tp = -40 to 115°C
CODE/
Class I, Division 1, Groups A, B, C, D Class I, Zone 0/1, AEx db IIC T6..T5 Ga/Gb
Dust Ignition Proof:
Class II, Division 1, Groups E, F, G; Suitable for Division 1, Class III; Class II, Zone 21, AEx tb IIIC
6/ FM ApprovalsTM
Class I, Division 2, Groups A, B, C, D
2013; FM 3615:2018; ANSI/ ISA 60079-1 :2015; FM 3616 : 2011 ; ANSI/ ISA 60079-31 :2015; FM 3810 : 2018; ANSI/ ISA 60079­26 :2017; FM 3611:2018; ANSI/ ISA 60079-15 : 2013; FM 3810 : 2005; ANSI/ ISA 61010-
T95 oC /T5: -50 ºC to 85º
T6: -50 ºC to 65ºC
T4: -50oC to 85oC
810/
ATEX
9/
IECEx
Sira 15ATEX2039X II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T 95oC..T 115oC Db
Sira 15ATEX4040X II 3 G Ex ec IIC T4 Gc
2014; EN 60079-26 :2015; ; EN 60079-7: 2015/A1: 2018
IECEx SIR 15.0022X Ex ec IIC T4 Gc
Ex db IIC T6..T5 Ga/Gb
IEC 60079-7: 2018; IEC 60079-31: 2013; IEC 60079-26: 2014
T5/ T95oC: -50 ºC to
85ºC
T6: -50 ºC to 65ºC
T4: -50oC to 85oC
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Class I, Division 1, Groups A, B, C, D
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G Suitable for Division 1, Class III; Zone 0/1, Ex db IIC T6..T5 Ga/Gb Class I, Zone 0/1, AEx db IIC T6..T5 Ga/Gb Ex tb IIIC T 95oC..T 115oC Db Class II, Zone 21, AEx tb IIIC T 95oC..
7/ CSA­Canada And USA
Class I, Division 2, Groups A, B, C, D Ex nA IIC T4 Gc
CSA C22.2 No 25:2017; CSA C22.2 No 30M; 1986(R2016);CSA No 61010-1: 2012(R2017); CSA C22.2 No 213: 2017; CSA C22.2 No 60529:2016; CSA C22.2 No 60079-0:2015; CSA C22.2 No 60079­1:2016;; CSA C22.2 60079-15:2016; CSA C22.2 No 60079­CSA C22.2 60079-31:2015; ANSI/UL 12.12.01:2017; ANSI/UL 61010 1: 2016; ANSI/ UL 60079-0:2013(R2017); ANSI/ ISA 60079-1:2015; ANSI/ UL 60079-15:2013(R2017); ANSI/ UL 60079-26 :2017; ANSI/ UL 60079-31 :2015; ANSI/IEC 60529: 2004(R2011); ANSI/ UL 913:2015; ANSI/ UL 916: 2015; ANSI/ UL 122701: 2017; FM 3615:
General: The following information is provided as part of the labeling of the transmitter:
A.5 Conditions of Use” for Ex Equipment”, Hazardous Location Equipment or “Schedule of Limitations”:
Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the equipment. The user shall then check the box [] adjacent to the type of protection used on the equipment certification nameplate. Once a type of protection has been checked on the nameplate, the equipment shall not then be reinstalled using any of the other certification types.
Intrinsically Safe: Must be installed per drawing 50128060 The enclosure is manufactured from low copper, aluminum alloy. In rare cases,
ignition sources due to impact and friction sparks could occur. This shall be considered during installation, particularly if the equipment is installed in a Zone 0/ Division 1 location.
The applicable temperature class, ambient temperature (Ta) range and process temperature (Tp) range of the equipment when installed with type protection “Ex ia” and “Ex ic” are as follows:
Flameproof “db” and Explosionproof - The applicable temperature class, ambient temperature (Ta) range and process temperature (Tp) range of the equipment when installed with type protection “Ex db” are as follows:
The Transmitter can be installed in the boundary wall between an area of EPL Ga/ Class I Zone 0/ Category 1 and the less hazardous area, EPL Gb/ Class I Zone 1/ Category 2. In this configuration, the process connection is installed in EPL Ga/ Class I Zone 0/ Category 1, while the transmitter housing is located in EPL Gb/ Class I Zone 1/ Category 2.
SMV800 Quick Start Installation Guide 9
• Name and Address of the manufacturer
• Notified Body identification: DEKRA Quality B.V., Arnhem, the Netherlands
and IECEx
T5: -50 oC to 85oC
T6: -50 oC to 65 oC
T4: -50oC to 85oC
Notes
Operating Parameters:
FM Approval: Carbon disulphide is excluded for Ex d installations as the enclosure has a volume greater than 100 cm3.
FM Approval: For information on flameproof joint dimensions and repair,
The installer shall provide transient over-voltage protection external to the
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
Dust ignition “tb” enclosure and non-sparking “ec” - The applicable temperature class, ambient temperature (Ta) range and process temperature (Tp) range of the equipment when installed with type prot ection “Ex tb” and “Ex ec” are as follows :
Non-Incendive Equipment: Division 2: This equipment is suitable for use in a Class I, Division 2, Groups A, B, C,
D; T4 or Non-Hazardous Locations Only WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE
PRESENT WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR
USE IN HAZARDOUS LOCATIONS
ALL PROTECTIVE MEASURES: WARNING: FOR CONNECTION I N AMBIENTS ABOVE 60oC USE WIRE RA TED 105oC
Maximum permissible working pressure is 207 bar (3,000 psig). If a charge-generating mechanism is present, the exposed painted metallic part on the
enclosure is capable of storing a level of electrostatic charge that could become incendive for IIC/ Groups A, B, C or D gases. Therefore, the user/installer shall implement precautions to prevent the build-up of electrostatic charge, e.g. earthing the metallic part.
This is particularly important if the equipment is installed in a zone 0/ Division 1 location. Cleaning of the painted surface shall only be done with a damp cloth.
See codes 8 and 9
contact the manufacturer using instructions given in the user’s manual.
equipment such that the voltage at the supply terminal of the equipment does not exceed 140 % of the voltage rating of the equipment.
Page 10

Control Drawing

SMV800 Quick Start Installation Guide 10
Page 11
For more information
Process Solutions
Honeywell
2101 City West Blvd,
Honeywell Control Systems Ltd
Shanghai City Centre, 100 Jungi Road
www.honeywellprocess.com
ASIA PACIFIC (TAC) hfs-tac-support@honeywell.com
9015
EMEA, Phone: + 80012026455 or +44 (0)1202645583. FAX: +44 (0) 1344 655554
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
Australia Honeywell Limited, Phone: +(61) 7-3846 1255, FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36, Toll Free Fax: 1300-36-04-70 China – PRC – Shanghai, Honeywell China Inc. Phone: (86-21) 5257-4568, Fax: (86-21) 6237-2826
Singapore, Honeywell Pte Ltd. Phone: +(65) 6580 3278. Fax: +(65) 6445-3033 South Korea, Honeywell Korea Co Ltd. Phone:+(822)799 6114. Fax:+(822) 792
Email: (Sales) sc-cp-apps-salespa62@honeywell.com or (TAC) hfs-tac-support@honeywell.com
Web: Knowledge Base search engine http://bit.ly/2N5Vldi
AMERICAS, Honeywell Process Solutions, Phone: 1-800-423-9883,
or 1-215/641-3610. (TAC) hfs-tac-support@honeywell.com. Sales 1-800-343-0228. Email: (Sales) ask-ssc@honeywell.com
Web: Knowledge Base search engine http://bit.ly/2N5Vldi
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties,
expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice.
The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.
While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product
in the application.
To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager
Houston, USA, TX 77042
Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
Shanghai, China 20061
34-SM-25-04, Rev.8 November 2020
2020 Honeywell International Inc.
Loading...