This quick guide includes the essential steps for easy
installation and setup of your SmartDrive Compact inverter.
Before commissioning your drive, read the complete
SmartDrive Compact User Manual available on the CD delivered with your
1. SAFETY
This quick guide contains clearly marked warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read these warnings carefully:
product or downloadable at:
http://ecc.emea.honeywell.com /inverter
The components of the power unit of the inverter are live when
SmartDrive Compact is connected to mains potential. Coming
into contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W (T1, T2, T3) and the possible
brake resistor terminals -/+ are live when SmartDrive Compact is connected to mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential.
However, the relay output terminals may have a dangerous
control voltage present even when SmartDrive Compact is disconnected from mains.
The earth leakage current of SmartDrive Compact inverters
exceeds 3.5mA AC. According to standard EN61800-5-1, a
reinforced protective ground connection must be ensured.
See Chapter 7!
If the inverter is used as a part of a machine, the machine
manufacturer is responsible for providing the machine with a
main switch (EN 60204-1).
If SmartDrive Compact is disconnected from mains while running the motor, it remains live if the motor is energized by the
process. In this case the motor functions as a generator feeding energy to the inverter.
After disconnecting the inverter from the mains, wait until the
fan stops and the indicators on the display go out. Wait 5 more
minutes before doing any work on SmartDrive Compact connections.
The motor can start automatically after a fault situation, if
autorestart function has been activated.
Table 1: Mechanical size classes with SmartDrive Compact
There are two possible ways to mount SmartDrive Compact in the wall; either screw
or DIN-rail mounting.
Figure 1: Screw mounting (left) and DIN-rail mounting (right)
NOTE! See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm) and below (50 mm) SmartDrive Com-
pact!
2-EN
Honeywell Installation 4
2-EN
Figure 2: Attaching the PE-plate and cable support
5 Installation Honeywell
1~ (230V)
3~ (400V)
Motor out
MAINS
MOTOR
Strip the
plastic cable
coating for
360° earthing
L1 L 2/N L3U/T1 V/ T2 W/T3R+ R-
1~ (230V)
3~ (400V)
MAINS
MOTOR
BRAKE
RESISTOR
Str ip t he
plas tic
cable
coating
for 360
°
eart hing
External brake
resi stor (4 00V)
Motor out
2.2 CABLING AND CONNECTIONS
2.2.1 Power cabling
Note! Tightening torque for power cables is 0.5 - 0.6 Nm
Figure 3: SmartDrive Compact power connections, MI1
Figure 4: SmartDrive Compact power connections, MI2 - MI3
2-EN
Honeywell Installation 6
Strip the plastic
cable coating for
360°earthing
Control cable
tightening
torque: 0.4 Nm
2.2.2 Control cabling
Figure 5: Open the cover
2-EN
Figure 6: Install the control cables. See next page!
7 Control I/O Honeywell
Ω
3. CONTROL I/O AND TERMINALS
Ter mina lSignalFactory presetDescription
1 +10Vref Ref. voltage outMaximum load 10 mA
2 AI1Analog signal in 1
3 GNDI/O signal ground
6 24Vout 24V output for DI's± 20 %, max. load 50 mA
7 GNDI/O signal ground
8 DI1Digital input 1
9 DI2Digital input 2
10 DI3Digital input 3
A ARS485 signal AFB Communication Modbus
B BRS485 signal BFB Communication Modbus
4 AI2Analog signal in 2
mA
5 GNDI/O signal ground
13 GNDI/O signal ground
14 DI4Digital input 4
15 DI5Digital input 5
16 DI6Digital input 6
18 AOAnalog signal out
20 DODigital signal out
22 RO 11 Relay out 1
23 RO 12
24 RO 21 Relay out 2
25 RO 22
26 RO 23
Table 1: Default I/O configuration and connections
P) = Programmable function, see User manual, Parameters
Freq. reference
Start forward
Start reverse
Preset speed B0
PI actual value
Preset speed B1
Fault reset
Disable PI control
Output frequency
Active = READY
Active = RUN
Active = FAULT
P)
0 - +10 V Ri = 200 k
(min)
P)
0 - +30 V Ri = 12 k min
P)
P)
P)
0(4) - 20 mA, Ri = 200
P)
0 - +30 V Ri = 12 k min
P)
P)
P)
0(4) - 20 mA, RL = 500
P)
Open collector, max. load
48V/50mA
P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
3-EN
3-EN
Honeywell Control I/O 8
SmartDrive Compact I/O terminals:
9 Navigation & Startup Honeywell
Hz
Hz
FWD REV I/O KEY PAD BUS
REF
MON
PAR
FLT
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
REF
PA R
FLT
FAULTALARMSTOPREADY RUN
MON
PUSH
FWD REV I/O KEY PAD BUS
REF
PAR
FLT
FAUL TALARMSTO PREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAULTALARMSTOPREADY RUN
MON
PUSH
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAULTALARMSTOPRE ADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAULTALARMSTOPRE ADY RUN
MON
PUSH
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAU LTALARMSTOPREAD Y R UN
MON
ROTATE
ROTATE
ROTATE
REFERENCE
MENU
Displays the
keypad reference
value
regardless of
the selected
control place.
MONITORING
MENU
In this menu
you can
brow se t he
monitoring
values.
PAR A ME TE R
MENU
In this menu
you can
browse and
edit the
parameters.
FAULT MEN U
Here you will
be able
to bro wse
throu gh the
faults occurred.
PUSH
FWD REV I/O KEY PAD B US
REF
MON
PAR
FLT
FAULTALARMSTOPREA DY R UN
4. NAVIGATION & STARTUP
4.1 THE MAIN MENUS OF SMARTDRIVE COMPACT
Figure 1: The main menu of SmartDrive Compact
4-EN
Honeywell Navigation & Startup 10
4.2 COMMISSIONING AND STARTUP WIZARD
4.2.1 Commissioning steps
1. Read safety instructions on page 1 6. Run the Startup wizard and set all neces-
2. Secure the grounding and check that
cables comply with requirements
3. Check quality and quantity of cooling air 8. Run no-load tests without motor being con-
4. Check that all start/stop switches are in
STOP position
5. Connect the drive to mains10. SmartDrive Compact is now ready for use
Table 1: Commissioning steps
4.2.2 Startup wizard
SmartDrive Compact runs the startup wizard in first power-up. After that the wizard
can be run by pressing STOP for 5 seconds in main menu. The following figures
show the procedure.
NOTE! Running the startup wizard
will always return all parameter
settings to their factory defaults!
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
Press STOP
1
for 5 seconds
in main menu
REF
MON
PAR
FLT
sary parameters
7. Perform test run without motor, see the
User Manual: http://ecc.emea.honeywell.com
nected to the process
9. Connect the motor to the process and perform test run once again
Alternates
in the display
FAULTALARMSTOPREADY RUN
REF
MON
PAR
rpm
FLT
Push to enter edit mode
2
3
Select motor
nominal speed
and push
to confirm.
FAULTALARMSTO PREADY RUN
4-EN
PERFORM THE SAME
4
PROCEDURE FOR PAR. 1.4,
MOTOR NOMINAL CURRENT
PERFORM DRIVE SETUP,
5
PAR. 13 .2, SEE NEXT PAGE
Figure 2: SmartDrive Compact startup wizard
11 Navigation & Startup Honeywell
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FAULTALARMSTOPREAD Y RUN
REF
MON
PAR
FLT
0Hz50
Hz
3s 3s
1,1 *
I
400
V
*
50
Hz
0=
0=0=
0=
Ai1
0-10V
20Hz50
Hz
20 s
400 50
Hz
0=
0=
0=0=
Ai1
0-10V
20
Hz
50
Hz
5s
400
50
Hz
0=
1=
0=
0=
Ai1
0-10V
0
Hz
50
Hz
1s
400
50
Hz
0=
0=1=
0=
Ai1
0-10V
NMOT
I/O
I/O
I/O
I/O
V
*
V
*
V
*
P3.2P3.1P4 .2 P4 .3
P1.7P1.1 P1 .2
P2.2 P2.3P1.15P3.3P2.1
1
2
3
4
1,1 *
I
NMOT
1,1*
I
NMOT
1,5 *
I
NMOT
5s
20s
1s
0
=Basic
*Indrivesof 208V...230V
thisvalueis 230V
1
=Pumpdrive
2
=
3
= Conveyor
drive
Push to enter
edit mode.
Select between
0 - 3, seebelow!
Selections:
Parameters
affected:
P3. 2 M ax freq uenc y
P3.1 Min frequency
P4. 2 Acc. t ime (s)
P4.3 D ec time (s)
P1.7 C urrent limit(A)
P2.2 Start function
P2.3 Stop fu nction
P1.15 Torque boost
P3. 3 I/O r eferenc e
P2.1 Control place
Startup wizard
shows par 13.2
number.
Push t o
confirm
drive setup
P1.1 Motor Un (V)
P1.2 M otor fn (H z)
Ramp Coast.Not
used
Ramp
Coas t .
Not
used
Ramp
Ramp
Not
used
Ramp
Coas t.Used
Fans
Figure 3: Drive setup
4-EN
Honeywell Navigation & Startup 12
4.2.3 Manual testing
1. Hold NAVIGATION WHEEL down for 5 seconds
• Control Place automatically switches to manual control
2. Use the buttons for speed control
• START and STOP for control
• Move to reference menu REF
• NAVIGATION WHEEL for adjusting the speed
3. Hold NAVIGATION WHEEL down for 5 seconds to return to remote control
(I/O or fieldbus)
4-EN
13 Monitoring & Parameters Honeywell
°
°
5. MONITORING & PARAMETERS
Note! Complete parameter listing and descriptions are
given in SmartDrive Compact User Manual, available on
the CD delivered with the product and downlodable at:
http://ecc.emea.honeywell.com/inverter
5.1 MONITORING VALUES
CodeMonitoring signalUnitIDDescription
M1.1 Output frequencyHz1 Frequency to the motor
M1.2 Frequency referenceHz25
M1.3 Motor shaft speedrpm2Calculated motor speed
M1.4 Motor currentA3 Measured motor current
M1.5 Motor torque%4Calculated actual/nominal torque of
M1.6 Motor power%5Calculated actual/nominal power of
M1.7 Motor voltageV6Motor voltage
M1.8 DC-link voltageV7 Measured DC-link voltage
M1.9 Unit temperature
M1.10 Motor temperature
M1.11 Analogue input 1%13 AI1 value
M1.12 Analogue input 2%14 AI2 value
M1.13 Analogue output %26 AO1
M1.14 DI1, DI2, DI315 Digital input statuses
M1.15 DI4, DI5, DI616 Digital input statuses
M1.16 RO1, RO2, DO17 Relay/digital output statuses
M1.17 PI setpoint%20 In percent of the maximum process
M1.18 PI feedback%21 In percent of the maximum actual
M1.19 PI error value%22 In percent of the maximum error
M1.20 PI Output%23 In percent of the maximum output
Table 1: SmartDrive Compact monitoring values (Complete parameter list and
parameter descriptions can be found from Complete SmartDrive Compact User
Manual available on product CD or at: http://ecc.emea.honeywell.com/inverter)
C
C
the motor
the motor
8 Heat sink temperature
Calculated motor temperature
reference
value
value
value
5-EN
5-EN
ϕ
HoneywellMonitoring & Parameters 14
5.2 QUICK SETUP PARAMETERS
CodeParameterMin Max Unit Default IDNote
P1.1 Motor nominal
voltage
P1.2 Motor nom. fre-
quency
P1.3 Motor nominal
speed
P1.4 Motor nominal
current
P1.5
Motor cos
P1.7 Current limit0,2 x
P1.15 Torque boost010109 0 = Not used 1 = Used
P2.1 Control place131125 1 = I/O termina
P3.4 Preset speed 00,00 P3.2 Hz5,00 124 Activated by digital inputs
P3.5 Preset speed 10,00 P3.2 Hz 10,00 105 Activated by digital inputs
P3.6 Preset speed 20,00 P3.2 Hz 15,00 106 Activated by digital inputs
P3.7 Preset speed 30,00 P3.2 Hz 20,00 126 Activated by digital inputs
Table 2: Quick setup parameters (Complete parameter list and parameter descriptions
can be found from Complete SmartDrive Compact User Manual available on product
CD or at: http://ecc.emea.honeywell.com/inverter)
180 500V230
30320 Hz 50,00 111 Check rating plate on the
300 20000rpm 1440 112 Default applies for a
AI
1,5 x
0,2 x
I
I
Nunit
Nunit
0,30 1,000,85 120 Check rating plate on the
2 x
I
Nunit
A1,5 x
I
Nunit
110 Check rating plate on the
I
400
Nunit
Nunit
motor
motor
4-pole motor.
113 Check rating plate on the
motor
motor
107
2 = Keypad
3 = Fieldbus
1 = Keypad Reference
2 = Fieldbus Reference
3 = AI1
4 = AI2
15 Monitoring & Parameters Honeywell
CodeParameterMin Max Unit Default IDNote
P4.2 Acceleration time 0,1 3000 s1,0103
P4.3 Deceleration time 0,1 3000 s1,0104
P6.1 AI1 Signal range030379 0 = Voltage 0…10 V
P6.5 AI2 Signal range 233390 2 = Current 0…20 mA
P10.4 Automatic restart010731 0 = Not used 1 = Used
P13.1 Parameter
conceal
Table 2: Quick setup parameters (Complete parameter list and parameter descriptions
can be found from Complete SmartDrive Compact User Manual available on product
CD or at: http://ecc.emea.honeywell.com/inverter)
0111150 = All parameters visible
1 = Voltage 2…10 V
3 = Current 4…20 mA
1 = Only quick setup
parameters visible
5-EN
5-EN
HoneywellMonitoring & Parameters 16
5.3 SYSTEM MENU PARAMETERS
CodeParameterMin Max DefaultNote
S1.1Software package
S1.2Power SW version
S1.3SW version
S1.4Firmware interface
S1.5Application ID
S1.6Application revision
S1.7System load
Output voltage0 - U
Output currentContinuous rated current IN at ambient tempera-
Ambient operating
temperature
Storage
temperature
Enclosure classIP20
Relative humidity0…95% RH, non-condensing, non-corrosive, no
Altitude100% load capacity (no derating) up to 1000m.
ImmunityComplies with EN50082-1, -2, EN61800-3
EmissionsComplies as standard with EN6 1800-3 Cate-
SmartDrive Compact cannot be used with corner
grounded networks
in
ture max. +50ºC, overload 1.5 x I
10min
-10°C (no frost)…+50°C: rated loadability I
-40°C…+70°C
dripping water
1% derating for each 100m above 1000m; max.
2000m
gory C2 (Honeywell level H: normal public electricity network requirements). Category C1 with
external EMC-filter (Honeywell level C: special
requirements for sensitive areas installations).
For EMC: EN61800-3,
For safety: UL508C, EN61800-5-1
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed approvals)
max. 1min/
N
N
7-EN
7-EN
Honeywell General Data 20
Cable and fuse
requirements
380 - 500V
208 - 240V
- With above-mentioned fuses, the drive can be connected to power supply the short
circuit current of which is max. 50kA
- Use cables with heat resistance of at least +70 C.
- The fuses function also as cable overload protection.
- These instructions apply only to cases with one motor and one cable connection
from the inverter to the motor.
- To fulfil standard EN61800-5-1, the protective conductor should be at least 10mm2
Cu or 16mm Al. Another possibility is to use an additional protective conductor of
at least the same size as the original one.