HONEYWELL SMARTDRIVE COMPACT User Manual

1 Honeywell
Ho
Honeywell
Quick Guide
Schnellanleitung
Guide Rapide
Constant and Variable torque
Variable Speed Drives
for Induction Motors
Konstant und Quadratisch
Moment Frequenzumrichter
für Elektrische Motoren
Couple Constant et Variable Convertisseur de fréquence
Pour Moteurs asynchrones
Subject to changes without notice / Änderungen vorbehalten / Sous réserve de modifications
Main Index
ENGLISH...........................................1
DEUTSCH ...................................... 22
FRANÇAIS........................................46
1 Honeywell
Index
1. SAFETY ......................................................................................2
2. INSTALLATION...........................................................................3
2.1 MECHANICAL INSTALLATION..................................................... 3
2.2 CABLING AND CONNECTIONS................................................... 5
2.2.1 Power cabling ..................................................................... 5
2.2.2 Control cabling .................................................................... 6
3. CONTROL I/O AND TERMINALS ..............................................7
4. NAVIGATION & STARTUP.........................................................9
4.1 THE MAIN MENUS OF SMARTDRIVE COMPACT ......................9
4.2 COMMISSIONING AND STARTUP WIZARD ............................... 10
4.2.1 Commissioning steps.......................................................... 10
4.2.2 Startup wizard ..................................................................... 10
4.2.3 Manual testing..................................................................... 12
5. MONITORING & PARAMETERS................................................13
5.1 MONITORING VALUES ................................................................ 13
5.2 QUICK SETUP PARAMETERS..................................................... 14
5.3 SYSTEM MENU PARAMETERS................................................... 16
6. FAULT TRACING........................................................................17
7. GENERAL DATA ........................................................................19
1-EN
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO
CARRY OUT THE ELECTRICAL INSTALLATION
!
Honeywell Safety 2
This quick guide includes the essential steps for easy
installation and setup of your SmartDrive Compact inverter.
Before commissioning your drive, read the complete
SmartDrive Compact User Manual available on the CD delivered with your

1. SAFETY

This quick guide contains clearly marked warnings which are intended for your per­sonal safety and to avoid any unintentional damage to the product or connected ap­pliances.
Please read these warnings carefully:
product or downloadable at:
http://ecc.emea.honeywell.com /inverter
The components of the power unit of the inverter are live when SmartDrive Compact is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor terminals -/+ are live when SmartDrive Com­pact is connected to mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the relay output terminals may have a dangerous control voltage present even when SmartDrive Compact is dis­connected from mains.
The earth leakage current of SmartDrive Compact inverters exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
See Chapter 7!
If the inverter is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1).
If SmartDrive Compact is disconnected from mains while run­ning the motor, it remains live if the motor is energized by the process. In this case the motor functions as a generator feed­ing energy to the inverter.
After disconnecting the inverter from the mains, wait until the fan stops and the indicators on the display go out. Wait 5 more minutes before doing any work on SmartDrive Compact con­nections.
The motor can start automatically after a fault situation, if autorestart function has been activated.
3 Installation Honeywell
12
MI2- 3MI1
=M 4
=M 5

2. INSTALLATION

2.1 MECHANICAL INSTALLATION

Product code
COMP230-P37-20 COMP230-P75-20 COMP400-P55-20 COMP400-P75-20 COMP400-1P1-20 COMP230-1P1-20 COMP230-1P5-20 COMP400-1P5-20 COMP400-2P2-20 COMP230-2P2-20 COMP400-3P0-20 COMP400-4P0-20 COMP400-5P5-20
Mechanical
size
MI1 66x157x98
MI2 90x195x102
MI3 100x251x109
Dimensions
WxHxD [mm]
Table 1: Mechanical size classes with SmartDrive Compact
There are two possible ways to mount SmartDrive Compact in the wall; either screw or DIN-rail mounting.
Figure 1: Screw mounting (left) and DIN-rail mounting (right)
NOTE! See the mounting dimensions on the back of the drive. Leave free space for cooling above (100 mm) and below (50 mm) SmartDrive Com-
pact!
2-EN
Honeywell Installation 4
2-EN
Figure 2: Attaching the PE-plate and cable support
5 Installation Honeywell
1~ (230V)
3~ (400V)
Motor out
MAINS
MOTOR
Strip the plastic cable coating for 360° earthing
L1 L 2/N L3 U/T1 V/ T2 W/T3R+ R-
1~ (230V)
3~ (400V)
MAINS
MOTOR
BRAKE RESISTOR
Str ip t he plas tic cable coating for 360
°
eart hing
External brake resi stor (4 00V)
Motor out

2.2 CABLING AND CONNECTIONS

2.2.1 Power cabling
Note! Tightening torque for power cables is 0.5 - 0.6 Nm
Figure 3: SmartDrive Compact power connections, MI1
Figure 4: SmartDrive Compact power connections, MI2 - MI3
2-EN
Honeywell Installation 6
Strip the plastic cable coating for 360°earthing
Control cable tightening torque: 0.4 Nm
2.2.2 Control cabling
Figure 5: Open the cover
2-EN
Figure 6: Install the control cables. See next page!
7 Control I/O Honeywell
Ω

3. CONTROL I/O AND TERMINALS

Ter mina l Signal Factory preset Description
1 +10Vref Ref. voltage out Maximum load 10 mA 2 AI1 Analog signal in 1
3 GND I/O signal ground 6 24Vout 24V output for DI's ± 20 %, max. load 50 mA 7 GND I/O signal ground 8 DI1 Digital input 1
9 DI2 Digital input 2 10 DI3 Digital input 3 A A RS485 signal A FB Communication Modbus B B RS485 signal B FB Communication Modbus 4 AI2 Analog signal in 2
mA
5 GND I/O signal ground 13 GND I/O signal ground 14 DI4 Digital input 4
15 DI5 Digital input 5 16 DI6 Digital input 6 18 AO Analog signal out
20 DO Digital signal out
22 RO 11 Relay out 1 23 RO 12
24 RO 21 Relay out 2 25 RO 22 26 RO 23
Table 1: Default I/O configuration and connections P) = Programmable function, see User manual, Parameters
Freq. reference
Start forward Start reverse Preset speed B0
PI actual value
Preset speed B1 Fault reset Disable PI control Output frequency
Active = READY
Active = RUN
Active = FAULT
P)
0 - +10 V Ri = 200 k (min)
P)
0 - +30 V Ri = 12 k min
P)
P)
P)
0(4) - 20 mA, Ri = 200
P)
0 - +30 V Ri = 12 k min
P)
P)
P)
0(4) - 20 mA, RL = 500
P)
Open collector, max. load 48V/50mA
P)
Max. switching load: 250Vac/2A or 250Vdc/ 0,4A
P)
Max. switching load: 250Vac/2A or 250Vdc/ 0,4A
3-EN
3-EN
Honeywell Control I/O 8
SmartDrive Compact I/O terminals:
9 Navigation & Startup Honeywell
Hz
Hz
FWD REV I/O KEY PAD BUS
REF
MON
PAR
FLT
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
REF
PA R
FLT
FAULTALARMSTOPREADY RUN
MON
PUSH
FWD REV I/O KEY PAD BUS
REF
PAR
FLT
FAUL TALARMSTO PREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAULTALARMSTOPREADY RUN
MON
PUSH
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAULTALARMSTOPRE ADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAULTALARMSTOPRE ADY RUN
MON
PUSH
FWD REV I/O KEYPAD BUS
REF
PAR
FLT
FAU LTALARMSTOPREAD Y R UN
MON
ROTATE
ROTATE
ROTATE
REFERENCE MENU
Displays the keypad reference value regardless of the selected control place.
MONITORING MENU
In this menu you can brow se t he monitoring values.
PAR A ME TE R MENU
In this menu you can browse and edit the parameters.
FAULT MEN U
Here you will be able to bro wse throu gh the faults occurred.
PUSH
FWD REV I/O KEY PAD B US
REF
MON
PAR
FLT
FAULTALARMSTOPREA DY R UN

4. NAVIGATION & STARTUP

4.1 THE MAIN MENUS OF SMARTDRIVE COMPACT

Figure 1: The main menu of SmartDrive Compact
4-EN
Honeywell Navigation & Startup 10

4.2 COMMISSIONING AND STARTUP WIZARD

4.2.1 Commissioning steps
1. Read safety instructions on page 1 6. Run the Startup wizard and set all neces-
2. Secure the grounding and check that cables comply with requirements
3. Check quality and quantity of cooling air 8. Run no-load tests without motor being con-
4. Check that all start/stop switches are in STOP position
5. Connect the drive to mains 10. SmartDrive Compact is now ready for use
Table 1: Commissioning steps
4.2.2 Startup wizard
SmartDrive Compact runs the startup wizard in first power-up. After that the wizard can be run by pressing STOP for 5 seconds in main menu. The following figures show the procedure.
NOTE! Running the startup wizard will always return all parameter settings to their factory defaults!
FAULTALARMSTOPREADY RUN
REF MON
PAR
FLT
Press STOP
1
for 5 seconds in main menu
REF
MON
PAR
FLT
sary parameters
7. Perform test run without motor, see the User Manual: http://ecc.emea.honeywell.com
nected to the process
9. Connect the motor to the process and per­form test run once again
Alternates in the display
FAULTALARMSTOPREADY RUN
REF
MON
PAR
rpm
FLT
Push to enter edit mode
2
3
Select motor nominal speed and push to confirm.
FAULTALARMSTO PREADY RUN
4-EN
PERFORM THE SAME
4
PROCEDURE FOR PAR. 1.4, MOTOR NOMINAL CURRENT
PERFORM DRIVE SETUP,
5
PAR. 13 .2, SEE NEXT PAGE
Figure 2: SmartDrive Compact startup wizard
11 Navigation & Startup Honeywell
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FAULTALARMSTOPREAD Y RUN
REF
MON
PAR
FLT
0Hz50
Hz
3s 3s
1,1 * I
400
V
*
50 Hz
0=
0=0=
0= Ai1
0-10V
20Hz50
Hz
20 s
400 50
Hz
0=
0=
0= 0=
Ai1
0-10V
20
Hz
50 Hz
5s
400
50 Hz
0=
1=
0=
0= Ai1
0-10V
0
Hz
50 Hz
1s
400
50 Hz
0=
0=1=
0= Ai1
0-10V
NMOT
I/O
I/O
I/O
I/O
V
*
V
*
V
*
P3.2P3.1 P4 .2 P4 .3
P1.7P1.1 P1 .2
P2.2 P2.3P1.15 P3.3P2.1
1
2
3
4
1,1 * I
NMOT
1,1* I
NMOT
1,5 * I
NMOT
5s
20s
1s
0
=Basic
*Indrivesof 208V...230V thisvalueis 230V
1
=Pumpdrive
2
=
3
= Conveyor
drive
Push to enter edit mode.
Select between 0 - 3, seebelow!
Selections:
Parameters affected:
P3. 2 M ax freq uenc y
P3.1 Min frequency
P4. 2 Acc. t ime (s) P4.3 D ec time (s)
P1.7 C urrent limit(A)
P2.2 Start function
P2.3 Stop fu nction
P1.15 Torque boost
P3. 3 I/O r eferenc e
P2.1 Control place
Startup wizard shows par 13.2 number.
Push t o confirm drive setup
P1.1 Motor Un (V) P1.2 M otor fn (H z)
Ramp Coast.Not
used
Ramp
Coas t .
Not
used
Ramp
Ramp
Not
used
Ramp
Coas t.Used
Fans
Figure 3: Drive setup
4-EN
Honeywell Navigation & Startup 12
4.2.3 Manual testing
1. Hold NAVIGATION WHEEL down for 5 seconds
Control Place automatically switches to manual control
2. Use the buttons for speed control
START and STOP for control
Move to reference menu REF
NAVIGATION WHEEL for adjusting the speed
3. Hold NAVIGATION WHEEL down for 5 seconds to return to remote control (I/O or fieldbus)
4-EN
13 Monitoring & Parameters Honeywell
°
°

5. MONITORING & PARAMETERS

Note! Complete parameter listing and descriptions are
given in SmartDrive Compact User Manual, available on
the CD delivered with the product and downlodable at:
http://ecc.emea.honeywell.com/inverter

5.1 MONITORING VALUES

Code Monitoring signal Unit ID Description
M1.1 Output frequency Hz 1 Frequency to the motor M1.2 Frequency reference Hz 25 M1.3 Motor shaft speed rpm 2 Calculated motor speed M1.4 Motor current A 3 Measured motor current M1.5 Motor torque % 4 Calculated actual/nominal torque of
M1.6 Motor power % 5 Calculated actual/nominal power of
M1.7 Motor voltage V 6 Motor voltage M1.8 DC-link voltage V 7 Measured DC-link voltage M1.9 Unit temperature
M1.10 Motor temperature
M1.11 Analogue input 1 % 13 AI1 value M1.12 Analogue input 2 % 14 AI2 value M1.13 Analogue output % 26 AO1 M1.14 DI1, DI2, DI3 15 Digital input statuses M1.15 DI4, DI5, DI6 16 Digital input statuses M1.16 RO1, RO2, DO 17 Relay/digital output statuses M1.17 PI setpoint % 20 In percent of the maximum process
M1.18 PI feedback % 21 In percent of the maximum actual
M1.19 PI error value % 22 In percent of the maximum error
M1.20 PI Output % 23 In percent of the maximum output
Table 1: SmartDrive Compact monitoring values (Complete parameter list and parameter descriptions can be found from Complete SmartDrive Compact User Manual available on product CD or at: http://ecc.emea.honeywell.com/inverter)
C
C
the motor
the motor
8 Heat sink temperature
Calculated motor temperature
reference
value
value
value
5-EN
5-EN
ϕ
Honeywell Monitoring & Parameters 14

5.2 QUICK SETUP PARAMETERS

Code Parameter Min Max Unit Default ID Note
P1.1 Motor nominal
voltage
P1.2 Motor nom. fre-
quency
P1.3 Motor nominal
speed
P1.4 Motor nominal
current
P1.5
Motor cos
P1.7 Current limit 0,2 x
P1.15 Torque boost 0 1 0 109 0 = Not used 1 = Used P2.1 Control place 1 3 1 125 1 = I/O termina
P2.2 Start function 0 1 0 505 0 = Ramp 1 = Flying start P2.3 Stop function 0 1 0 506 0 = Coasting 1 = Ramp P3.1 Min frequency 0,00 P3.2 Hz 0,00 101 P3.2 Max frequency P3.1 320 Hz 50,00 102 P3.3 I/O reference 0 4 3 117 0 = Preset Speeds (0-7)
P3.4 Preset speed 0 0,00 P3.2 Hz 5,00 124 Activated by digital inputs P3.5 Preset speed 1 0,00 P3.2 Hz 10,00 105 Activated by digital inputs P3.6 Preset speed 2 0,00 P3.2 Hz 15,00 106 Activated by digital inputs P3.7 Preset speed 3 0,00 P3.2 Hz 20,00 126 Activated by digital inputs
Table 2: Quick setup parameters (Complete parameter list and parameter descriptions can be found from Complete SmartDrive Compact User Manual available on product CD or at: http://ecc.emea.honeywell.com/inverter)
180 500 V 230
30 320 Hz 50,00 111 Check rating plate on the
300 20000rpm 1440 112 Default applies for a
AI
1,5 x
0,2 x
I
I
Nunit
Nunit
0,30 1,00 0,85 120 Check rating plate on the
2 x
I
Nunit
A 1,5 x
I
Nunit
110 Check rating plate on the
I
400
Nunit
Nunit
motor
motor
4-pole motor.
113 Check rating plate on the
motor
motor
107
2 = Keypad 3 = Fieldbus
1 = Keypad Reference 2 = Fieldbus Reference
3 = AI1 4 = AI2
15 Monitoring & Parameters Honeywell
Code Parameter Min Max Unit Default ID Note
P4.2 Acceleration time 0,1 3000 s 1,0 103 P4.3 Deceleration time 0,1 3000 s 1,0 104 P6.1 AI1 Signal range 0 3 0 379 0 = Voltage 0…10 V
P6.5 AI2 Signal range 2 3 3 390 2 = Current 0…20 mA
P10.4 Automatic restart 0 1 0 731 0 = Not used 1 = Used P13.1 Parameter
conceal
Table 2: Quick setup parameters (Complete parameter list and parameter descriptions can be found from Complete SmartDrive Compact User Manual available on product CD or at: http://ecc.emea.honeywell.com/inverter)
01 11150 = All parameters visible
1 = Voltage 2…10 V
3 = Current 4…20 mA
1 = Only quick setup
parameters visible
5-EN
5-EN
Honeywell Monitoring & Parameters 16

5.3 SYSTEM MENU PARAMETERS

Code Parameter Min Max Default Note
S1.1 Software package S1.2 Power SW version S1.3 SW version S1.4 Firmware interface S1.5 Application ID S1.6 Application revision S1.7 System load
S2.1 Communication status Format: xx.yyy
S2.2 Fieldbus protocol 0 1 0 0 = FB disabled 1= Modbus S2.3 Slave address 1 255 S2.4 Baud rate 0 5 5 0=300, 1=600, 2=1200,
S2.5 Number of stop bits 0 1 1 0=1, 1=2 S2.6 Parity type 0 0 0 0= None (locked) S2.7 Communication time-out 0 255 0 0= Not used, 1= 1 second,
S2.8 Reset communication sta-
tus
S3.1 MWh counter 0 1 0 S3.2 Power on days 0 1 0 S3.3 Power on hours 0 1 0
S4.1 Display contrast 0 15 7 Adjusts the display contrast S4.2 Restore factory defaults 0 1 0 1= Restores factory defaults
Table 3: System menu parameters
Software information (MENU PAR -> S1)
RS485 information (MENU PAR -> S2)
xx = 0 - 64 (Number of error
messages) yyy = 0 - 999 (Number of good messages)
3=2400, 4=4800, 5=9600,
2= 2 seconds, etc. 1= Resets par. S2.1
Total counters (MENU PAR -> S3)
User settings (MENU PAR -> S4)
17 Fault Tracing Honeywell

6. FAULT TRACING

Fault code Fault name Quick corrective actions
Overcurrent
1
Overvoltage Increase deceleration time (P4.3).
2
Earth fault - Check motor Cables- Check motor.
3
System fault
8
Undervoltage
9
Inverter under temperature
13
Inverter over temperature
14
Motor stalled
15
Motor overtemperature
16
Motor Underload
17
EEPROM checksum fault
22
Microcontroller watchdog fault
25
Internal bus communication
34
Application fault
35
- Check loading.
- Check cables.
- Check motor size.
Reset the fault and restart. Should the fault recur, contact the techni­cal support.
In case of temporary supply voltage break, reset the fault and restart. Check supply voltage.
Check that the product is operated in specified conditions.
- Check that the cooling air is not blocked.
- Check the ambient temperature.
- Make sure that the switching frequency is not too high in relation to ambient temperature and motor load (P1.16).
- Check motor
- Check that the pump or fan is not
blocked.
- Check that motor parameters are cor
rect (P1.1-P1.5).
- Decrease motor load.
FAN: check that belt is not broken. PUMP: check that pump is not dry.
Reset the fault and restart. Should the fault recur, contact the techni­cal support.
Reset the fault and restart. Should the fault recur, contact the techni­cal support.
Reset the fault and restart. Should the fault recur, contact the techni­cal support.
Reset the fault and restart. Should the fault recur, contact the techni­cal support.
6-EN
Honeywell Fault Tracing 18
Fault code Fault name Quick corrective actions
Analogue input Iin < 4mA (selected signal range 4 to 20
50
mA)
Fieldbus fault
53
Table 1: Fault codes. See User Manual for detailed fault descriptions
Check the control cabling
- Check installation.
- If installation is correct contact technical support
6-EN
19 General Data Honeywell

7. GENERAL DATA

Dimensions and weight
Supply network
Motor connection
Ambient conditions
EMC
Standards
Certificates and manufacturer’s declarations of conformity
Frame Height Width Depth (mm) Weight (kg)
MI1 156,5 65,5 98,5 0,55 MI2 195 90 101,5 0,70 MI3 262,5 100 108,5 0,99
Output voltage 0 - U Output current Continuous rated current IN at ambient tempera-
Ambient operating temperature
Storage temperature
Enclosure class IP20 Relative humidity 0…95% RH, non-condensing, non-corrosive, no
Altitude 100% load capacity (no derating) up to 1000m.
Immunity Complies with EN50082-1, -2, EN61800-3 Emissions Complies as standard with EN6 1800-3 Cate-
SmartDrive Compact cannot be used with corner grounded networks
in
ture max. +50ºC, overload 1.5 x I 10min
-10°C (no frost)…+50°C: rated loadability I
-40°C…+70°C
dripping water
1% derating for each 100m above 1000m; max. 2000m
gory C2 (Honeywell level H: normal public elec­tricity network requirements). Category C1 with external EMC-filter (Honeywell level C: special requirements for sensitive areas installations).
For EMC: EN61800-3, For safety: UL508C, EN61800-5-1
For safety: CB, CE, UL, cUL, For EMC: CE, CB, c-tick (see unit nameplate for more detailed approvals)
max. 1min/
N
N
7-EN
7-EN
Honeywell General Data 20
Cable and fuse requirements
380 - 500V
208 - 240V
- With above-mentioned fuses, the drive can be connected to power supply the short circuit current of which is max. 50kA
- Use cables with heat resistance of at least +70 C.
- The fuses function also as cable overload protection.
- These instructions apply only to cases with one motor and one cable connection from the inverter to the motor.
- To fulfil standard EN61800-5-1, the protective conductor should be at least 10mm2 Cu or 16mm Al. Another possibility is to use an additional protective conductor of at least the same size as the original one.
Frame Fuse
MI1 6 MI2 10 MI3 20 3*2.5+2.5 1.5-6 MI1 10 2*1.5+1.5 MI2 20 2*2.5+2.5 MI3 32 2*6+6 1.5-6
Mains cable
(A)
Cu (mm
3*1.5+1.5 1.5-4
Terminal cable min-max (mm
2
)
Main & earth Control & relay
1.5-4
0.5-1.5
2
)
21 General Data Honeywell
SmartDrive Compact power ratings
Mains voltage 208-240 V, 50/60 Hz, 1~ series
Motor
Rated loadability
Product code
COMP230-P25-20 1,7 2,6 0,25 4,2 MI1 COMP230-P37-20 2,4 3,6 0,37 5,7 MI1 COMP230-P55-20 2,8 4,2 0,55 6,6 MI1 COMP230-P75-20 3,7 5,6 0,75 8,3 MI1 COMP230-1P1-20 4,8 7,2 1,1 11,2 MI2 COMP230-1P5-20 7,0 10,5 1,5 14,1 MI2 COMP230-2P2-20 9,6 14,4 2,2 15,8 MI3
100% contin.
[ A ]
current I
N
150% overload
current [ A ]P[ kW ]
Mains voltage 380-480 V, 50/60 Hz, 3~ series
Rated loadability
Product code
COMP400-P37-20 1,3 2,0 0,37 2,2 MI1 COMP400-P55-20 1,9 2,9 0,55 2,8 MI1 COMP400-P75-20 2,4 3,6 0,75 3,2 MI1 COMP400-1P1-20 3,3 5,0 1,1 4,0 MI1 COMP400-1P5-20 4,3 6,5 1,5 5,6 MI2 COMP400-2P2-20 5,6 8,4 2,2 7,3 MI2 COMP400-3P0-20 7,6 11,4 3,0 9,6 MI3 COMP400-4P0-20 9,0 13,5 4,0 11,5 MI3 COMP400-5P5-20 12,0 18,0 5,5 14,9 MI3
100% contin­uous current
[ A ]
I
N
150% over­load current
Motor shaft
380-480V sup-
[ A ]
shaft
power
power
ply
P[ kW ]
Nomi-
nal input
current
[ A ]
Nominal
input
current
[ A ]
Mechanical
size
Mechan-
ical size
7-EN
Note: The input currents are calculated values with 100 kVA line transformer supply.