Honeywell SLC Installation Manual

Intelligent Control Panel
SLC
Wiring Manual
Document 51309 9/17/2014 Rev:
P/N 51309:P4 ECN 14-790
P4
2 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauth orized use of this document is strictly prohibited.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014

Table of Contents

Section 1: Introduction.............................................................................................................8
1.1: Scope..............................................................................................................................................................8
1.1.1: Reference Documentation ...................................................................................................................9
1.2: Overview......................................................................................................................................................10
1.3: Polling Protocols .........................................................................................................................................10
1.3.1: Available Protocols............................................................................................................................10
1.3.2: Protocol Use ......................................................................................................................................10
1.4: Devices ........................................................................................................................................................11
1.4.1: Isolator Modules................................................................................................................................11
1.4.2: Monitor Modules...............................................................................................................................11
1.4.3: Control Modules................................................................................................................................11
1.4.4: Relay Modules...................................................................................................................................11
1.4.5: Multiple Input/Output Modules.........................................................................................................11
1.4.6: Intelligent Detectors ..........................................................................................................................11
1.4.7: Manual Pull Station...........................................................................................................................12
1.4.8: Wireless Gateway..............................................................................................................................12
1.4.9: 300 Series Addressable Devices........................................................................................................13
1.5: SLC Capacity...............................................................................................................................................13
1.6: SLC Performance.........................................................................................................................................13
1.7: Surge Suppression........................................................................................................................................13
1.8: LED Operation.............................................................................................................................................13
Section 2: Wiring Requirements............................................................................................14
2.1: Wire Sizing..................................................................................................................................................14
2.1.1: CLIP (Classic Loop Interface Protocol) Mode..................................................................................14
2.1.2: LiteSpeed Mode.................................................................................................................................14
2.2: Measuring Resistance & Length..................................................................................................................15
2.2.1: Two-Wire SLC - Style 4 (Class B)....................................................................................................15
2.2.2: Four-Wire SLC Style 6 & 7 (Class A) ..............................................................................................16
2.3: Shield Wire Termination...................................................... ........................................................................17
2.4: Control Panel Terminal Blocks....................................................................................................................18
2.4.1: MS-9200............................................................................................................................................18
2.4.2: MS-9600, MS-9600LS, & MS-9600UDLS.......................................................................................18
2.4.3: MS-9200UDLS (Software Version 3.0)............................................................................................19
2.4.4: MS-9200UD & MS-9200UDLS (Versions 1 and 2).........................................................................19
2.4.5: MS-9050UD ......................................................................................................................................20
Section 3: SLC Circuits without Isolators ............................................................................21
3.1: Overview......................................................................................................................................................21
3.2: NFPA Style 4 SLC.......................................................................................................................................21
3.3: NFPA Style 6 SLC.......................................................................................................................................22
Section 4: SLC Circuits with Isolators..................................................................................23
4.1: Fault Isolator Devices..................................................................................................................................23
4.1.1: Isolating an SLC Branch....................................................................................................................23
4.1.2: Wiring an Isolator Module ................................................................................................................24
4.2: NFPA Style 4 SLC Using Isolator Modules ................................................................................................25
4.3: NFPA Style 6 SLC Using Isolator Modules ................................................................................................27
4.4: NFPA Style 7 SLC Using Isolator Modules ................................................................................................28
Section 5: Monitor Modules...................................................................................................29
5.1: Descriptions.................................................................................................................................................29
5.1.1: Addressable Monitor Modules ..........................................................................................................29
5.1.2: Zone Interface Modules.....................................................................................................................31
5.1.3: Dual Monitor Module........................................................................................................................33
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 5
Table of Contents
5.1.4: Mini Monitor Module........................................................................................................................33
5.2: Installation....................................................................................................................................................33
5.2.1: Setting an SLC address for a Single Point Module ...........................................................................34
5.2.2: Setting an SLC address for a Multi-Point Module ............................................................................35
5.3: MMF-300 Wiring Diagrams........................................................................................................................36
5.3.1: Wiring a NFPA Style B IDC with an MMF-300...............................................................................36
5.3.2: Wiring a NFPA Style D IDC with an MMF-300 ..............................................................................37
5.3.3: MMF-300 Wiring for Emergency Alarm System Applications........................................................38
5.4: MMF-300-10 Wiring Diagrams...................................................................................................................39
5.4.1: Wiring a NFPA Style B IDC with an MMF-300-10 .........................................................................39
5.4.2: Wiring a NFPA Style D IDC with an MMF-300-10.........................................................................40
5.5: MDF-300 Wiring Diagrams.........................................................................................................................41
5.5.1: Wiring a NFPA Style B IDC with an MDF-300 ...............................................................................41
5.6: MMF-302 Wiring Diagrams........................................................................................................................42
5.6.1: Wiring a NFPA Style B IDC with an MMF-302...............................................................................42
5.6.2: Wiring a NFPA Style D IDC with an MMF-302 ..............................................................................43
5.7: MMF-302-6 Wiring Diagrams.....................................................................................................................44
5.7.1: Wiring a NFPA Style B IDC with an MMF-302-6 ...........................................................................44
5.7.2: Wiring a NFPA Style D IDC with an MMF-302-6 ...........................................................................45
Section 6: Control Modules ...................................................................................................46
6.1: Description...................................................................................................................................................46
6.2: CMF-300 Installation...................................................................................................................................46
6.2.1: Setting an SLC address for a CMF-300 Module ...............................................................................46
6.2.2: Wiring a Notification Appliance Circuit (NAC) with a CMF-300....................................................46
6.3: Wiring a CMF-300 Module .........................................................................................................................47
6.3.1: Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules .........................................47
6.3.2: Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules .........................................48
6.4: CMF-300-6 Installation ...............................................................................................................................48
6.4.1: Cabinet Installation............................................................................................................................48
6.4.2: Setting an SLC address for an CMF-300-6 Module..........................................................................48
6.4.3: Setting NACs as Style Y or Style Z...................................................................................................49
6.4.4: Disabling Unused Module Addresses................................................................................................49
6.4.5: Short Circuit Protection.....................................................................................................................49
6.4.6: Features Not Supported .....................................................................................................................50
6.4.7: Circuit Board Information .................................................................................................................50
6.5: Wiring a CMF-300-6 Module......................................................................................................................51
6.5.1: Wiring a Style Y NAC (Two-Wire) .................................................................................................51
6.5.2: Wiring a Style Z NAC (Four-Wire)...................................................................................................52
Section 7: Relay Modules ......................................................................................................53
7.1: Description...................................................................................................................................................53
7.2: CRF-300 Installation & Wiring...................................................................................................................53
7.2.1: Setting an SLC address for a CRF-300 Module ................................................................................53
7.2.2: Wiring a CRF-300 Module (Form-C Relay) ....................................................................................53
7.3: CRF-300-6 Circuit Board Information ........................................................................................................54
7.4: CRF-300-6 Installation & Wiring................................................................................................................54
7.4.1: Cabinet Installation............................................................................................................................54
7.4.2: Setting an SLC address for a CRF-300-6 Module.............................................................................55
7.4.3: Disabling Unused Module Addresses................................................................................................55
7.4.4: Wiring a CRF-300-6 Module (Form-C Relay)..................................................................................55
Section 8: Multiple Input/Output Modules............................................................................57
8.1: Description...................................................................................................................................................57
8.2: CDRM-300 Installation & Wiring...............................................................................................................57
8.2.1: Setting an SLC address for a CDRM-300 Module............................................................................57
8.2.2: Wiring a CDRM-300 Module (Form-C Relay)................................................................................58
6 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Table of Contents
Section 9: Intelligent Detector Bases and Wireless Gateway.............................................59
9.1: Description...................................................................................................................................................59
9.2: Setting the Detector Address .......................................................................................................................59
9.3: Wiring a Detector Base................................................................................................................................60
9.4: Wiring an Isolator Base ...............................................................................................................................61
9.5: Wiring a Relay Base....................................................................................................................................61
9.6: Wiring a Sounder Base................................................................................................................................62
9.7: Wiring the W-GATE....................................................................................................................................62
9.7.1: SLC Connections...............................................................................................................................62
9.7.2: W-GATE Powered by the SLC....................................................... ..................................................63
9.7.3: W-GATE Powered by a Regulated, External +24VDC Power Source.............................................64
Section 10: Addressable Beam Detectors............................................................................65
10.1: Description.................................................................................... .............................................................65
10.2: Installation and Wiring..............................................................................................................................65
10.2.1: Setting an SLC Address for a Beam Detector.................................................................................65
10.2.2: Wiring a Beam Detector..................................................................................................................66
Section 11: Addressable Manual Pull Station......................................................................67
11.1: Description.................................................................................................................................................67
11.2: Installation..................................................................................................................................................67
11.2.1: Setting an SLC address....................................................................................................................67
11.2.2: Wiring a Manual Pull Station..........................................................................................................67
Appendix A: Power Considerations......................................................................................68
A.1: Supplying Power to 24 VDC Detectors and NACs ....................................................................................68
A.1.1: Resistance and Size...........................................................................................................................68
A.2: Supervising 24 VDC Power........................................................................................................................69
Appendix B: Surge Suppression ...........................................................................................71
B.1: Introduction.................................................................................................................................................71
B.2: Installation...................................................................................................................................................71
B.2.1: Wiring Diagram for MS-9200 ..........................................................................................................72
B.2.2: Wiring Diagram for MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, and
MS-9050UD ................................................................................................................................................73
Appendix C: Terminal Conversion Charts for New & Legacy Devices..............................74
C.1: CRF-300......................................................................................................................................................74
C.2: CMF-300 and MMF-302 ............................................................................................................................75
C.3: MMF-300....................................................................................................................................................76
C.4: MDF-300.....................................................................................................................................................77
Appendix D: Intelligent Detector Base Layouts for Legacy Devices.................................78
D.1: B350LP or B501 Detector Base..................................................................................................................78
D.2: B224BI Isolator Base.................................................................................................................................79
D.3: B224RB Relay Base ...................................................................................................................................79
D.4: B501BH(-2) and B501BHT(-2) Sounder Bases............................................................................... ..........80
Appendix E: Canadian Versions of SLC Devices ................................................................82
Index.........................................................................................................................................84
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 7

1.1 Scope

CMF-300
Legacy Version Module
(Vertical Rotary Dial)
CMF-300
Newer Version Module
(Horizontal Rotary Dial)

Section 1: Introduction

This document describes the operation, installation and wiring of various Signaling Line Circuit (SLC) devices when used with the Fire-Lite MS-9200/MS-9200E, MS-9600/MS-9600E, MS­9600LS/MS-9600LSC/MS-9600LSE, MS-9600UDLS/MS-9600UDLSE, MS-9200UD/MS­9200UDE, MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC, and MS-9050UD/MS­9050UDC/MS-9050UDE control panels. It also provides basic information that applies to Fire•Lite SLC loops in general, such as the branch resistance measurements.
NOTE: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, or MS-9050UD includes the MS-9200E, MS-9200UDE, MS-9200UDLSE, MS-9200UDLSC, MS-9600E, MS-9600LSE, MS-9600LSC, MS-9600UDLSE, MS-9050UDC, or MS-9050UDE respectively unless otherwise specified.
Additional information about the specific control panel and the modules and detectors referenced in this document can be found in the respective installation manual as listed in Table 1.1, “Reference Documentation”.
Currently, there are two styles of modules available, legacy version and newer version. The obvious difference between the two styles is the orientation of the rotary dials. Refer to the diagram below for an example of each.
NOTE: Only the MMF-300, MMF-302, CRF-300, CMF-300, and MDF-300 modules are available as newer type modules. Both the legacy and newer versions share the same part numbers. The newer version modules will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the modules. Refer to “Terminal Conversion Charts for New & Legacy Devices” on page 74 for additional information.
8 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Scope Introduction
Currently, there are two styles of detector bases available, legacy version and newer version. The obvious difference between the two styles is the orientation of the screw terminals. Refer to Section 9 and Appendix D for an illustration of each.
NOTE: Only the B501 Detector Base, B210LP Detector Base (replacement base for B350LP), B224RB Relay Base, and B224BI Isolator Base are available as newer type bases. Both the legacy and newer versions share the same part numbers. The newer version bases will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the bases. Refer to “Intelligent Detector Base Layouts for Legacy Devices” on page 78 for additional information.

1.1.1 Reference Documentation

The table below accommodates a list of document sources containing additional information regarding the devices used on a Signaling Line Circuit:
For information on... Refer to... Part Number
MS-9200/MS-9200E Instruction Manual 51003 MS-9600/MS-9600E Instruction Manual 51335 MS-9200UD/MS-9200UDE Instruction Manual 51906 MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC Instruction Manual 52750 MS-9600LS/MS-9600LS(C/E) & MS-9600UDLS/MS9600UDLSE Instruction Manual 52646 MS-9050UD/MS-9050UDC/MS-9050UDE Instruction Manual 52413 Compatible Devices Device Compatibility Document 15384 Wireless Sensor Network Instruction Manual LS10036-000FL-E BG-12LX Pull Station Installation Instructions I56-3655 MMF-300 Monitor Module Installation Instructions I56-1191 / I56-3653 MMF-300-10 Monitor Module Installation Instructions I56-1873 MMF-301 Mini Monitor Module Installation Instructions I56-1193 / I56-3654 MMF-302 Monitor Module Installation Instructions I56-1192 / I56-3652 MMF-302-6 Interface Module Installation Instructions I56-1900 MDF-300 Dual Monitor Module Installation Instructions I56-0013 / I56-3665 CMF-300 Control Module Installation Instructions I56-1189 / I56-3650 CMF-300-6 Control Module Installation Instructions I56-1874 CRF-300 Relay Module Installation Instructions I56-1190 / I56-3651 CRF-300-6 Relay Module Installation Instructions I56-1875 CDRM-300 Multiple Input/Output Module Installation Instructions I56-3726 I300 Isolator Module Installation Instructions I56-1381 ISO-6 Isolator Module Installation Instructions I56-4096 AD350 Multicriteria Detector Installation Instructions F300-17-00 AD355 Multicriteria Detector Installation Instructions I56-3660 SD350 & SD350T Photo Detector Installation Instructions I56-0035 SD355 & SD355T Photo Detector Installation Instructions I56-3660 CP350 Ionization Detector Installation Instructions I56-0036 CP355 Ionization Detector Installation Instructions I56-3656 H350 Heat Detector Installation Instructions I56-0038 H350R Heat Detector w/ROR Installation Instructions I56-0037 H355 Heat Detector (135 H355R Heat Detector w/ROR Installation Instructions I56-3657 H355HT Heat Detector (190 D350P Duct Detector Installation Instructions F300-10-00 D350PL(A) Duct Detector - low flow Installation Instructions I56-1975
°) Installation Instructions I56-3657
°) Installation Instructions I56-3657
Table 1.1 Reference Documentation
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 9
Introduction Overview
For information on... Refer to... Part Number
D350RP Duct Detector w/Relay Installation Instructions I56-0047 D350RPL(A) Duct Detector w/Relay - low flow Installation Instructions I56-1974 D355PL Duct Detector - low flow Installation Instructions I56-3255 BEAM355(S) Addressable Beam Detector Installation Instructions I56-2425 B210LP Plug-in Detector Base Installation Instructions I56-3739 B501 Detector Base Installation Instructions I56-0357 / I56-3738 B501BH Sounder Detector Base Installation Instructions I56-0491 B501BH-2 Sounder Detector Base Installation Instructions I56-2813 B501BHT Temporal Sounder Detector Base Installation Instructions I56-1367 B501BHT-2 Temporal Sounder Detector Base Installation Instructions I56-2819 B200SR Sounder Detector Base Installation Instructions I56-3387 B200SR-LF Low Frequency Sounder Detector Base Installation Instructions I56-4152 B224RB Relay Detector Base Installation Instructions I56-2815 / I56-3737 B224BI Isolator Detector Base Installation Instructions I56-0725 / I56-3736
Table 1.1 Reference Documentation

1.2 Overview

Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to “Surge Suppression” on page 71.

1.3 Polling Protocols

The MS-9200UDLS, MS-9600LS, and MS-9600UDLS support LiteSpeed protocol or Classic Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E, and MS-9050UD support Classic Loop Interface Protocol (CLIP) only.

1.3.1 Available Protocols

LiteSpeed is a communication protocol that greatly enhances the speed of communication between analog intelligent devices. Only the MS-9200UDLS, MS-9600LS, and MS-9600UDLS are capable of operating in LiteSpeed mode. This is the default mode of operation for these FACPs.
CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-LiteFireWarden addressable fire alarm control panels can operate in CLIP mode. This is the default mode of operation for all other FACPs.

1.3.2 Protocol Use

Use one of the following options with LiteSpeed/CLIP mode:
1. Program all modules and detectors on an FACP as LiteSpeed.
2. Program all modules and detectors on an FACP as CLIP.
NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP mode of operation. Communication protocols cannot be split between SLC loops.
When switching between polling protocols, the loop circuit must be powered down for at least 30 seconds to reset the devices.
10 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Devices Introduction

1.4 Devices

1.4.1 Isolator Modules

Isolator Modules permit a zone of detectors and modules to be fault isolated from the remainder of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Style 7 circuit.
I300 - Single fault isolator module ISO-6 - Six fault isolator module

1.4.2 Monitor Modules

Addressable modules that allow the control panel to monitor entire circuits of conventional alarm initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and supervisory devices.
MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises. MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally open
contact device circuits. MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style B
wired devices. This module does not have an LED.
MMF-302 - Monitors a single IDC of two-wire smoke detectors. MMF-302-6 - An addressable module that provides an interface between the control panel and six
(6) Style B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors. MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.

1.4.3 Control Modules

Through the CMF-300 addressable control module, the control panel can selectively activate a Notification Appliance Circuit (NAC).
CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B) or three (3) Style Z (Class A) NACs.

1.4.4 Relay Modules

The CRF-300 addressable relay module provides the control panel with a dry-contact output for activating a variety of auxiliary devices.
CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.

1.4.5 Multiple Input/Output Modules

The CDRM-300 addressable multiple input/output module monitors two (2) Style B input devices and provides two (2) independent Form-C relay contacts.

1.4.6 Intelligent Detectors

AD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 11
Introduction Devices
CP350 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle’.
CP355 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle’.
D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air velocity rating is 500 to 4,000 feet per minute.
D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity
rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec). D355PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to
the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
1
- An addressable detector using a thermistor sensing circuit for fast response. H350R
H350
incorporates a thermal rate of rise of 15°F (9.4°C)/minute.
1
- An addressable 135° fixed temperature heat detector using a thermistor sensing circuit for
H355
fast response. H355R incorporates a thermal rate of rise of 15° F (9.4° C)/minute.
1
H355HT
- An addressable 190° fixed temperature heat detector using a thermistor sensing circuit
for fast response. SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing
optical sense technology. The SD350T includes a 135° F fixed thermal sensor. SD355 - An addressable photoelectric smoke detector which provides smoke sensing utilizing
optical sense technology. The SD355T includes a 135° F fixed thermal sensor. The SD355R is a low profile, intelligent, photoelectric sensor that is remote test capable.
BEAM355 - An addressable long range projected beam smoke detector designed to provide open area protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
DNR(W) - Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing. This requires the SD355R photoelectric smoke detector. Accomodates the installation of the CRF­300 relay module. The DNRW is a watertight housing.

1.4.7 Manual Pull Station

The BG-12LX is a dual-action pull station that, when activated, provides an addressable identification and its location to the control panel. An addressable monitor module is mount ed inside the pull station to facilitate servicing and replacement.

1.4.8 Wireless Gateway

W-GATE: The Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the MS-9200UDLS. It is powered by the SLC loop or by a regulated, external 24VDC UL listed power supply. Available wireless devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor module. For details about wireless devices, system setup, and operation, see the SWIFT™ Smart Wireless In tegrated Fire Technology Instruction Manual.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission (FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may be legally used outside the USA.
1. Addressable Heat Detectors are not compatible with the MS-9200(E).
12 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
SLC Capacity Introduction

1.4.9 300 Series Addressable Devices

Fire•Lite’s 300 Series of addressable devices are fully compatible with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS(C/E), MS-9600UDLS/E, and MS-9050UD FACPs. The devices must be configured for CLIP (Classic Loop Interface Protocol) Mode operation. The address of 300 series devices cannot be set above 99. Compatible devices include:
• SD300 Photo • M300 Monitor Module
• SD300T Photo w/Thermal • M301 Mini Monitor Module
• CP300 Ionization • M302 2-wire Monitor Module
• BG-10LX Pull Station • C304 Control/Relay Module

1.5 SLC Capacity

The protocol selected for an SLC loop determines the maximum number of devices that can be handled by the loop. See Section 1.3, “Polling Protocols”, on page 10. Within those limits, the individual control panel may have additional restrictions. See the specific installation manual for this information.

1.6 SLC Performance

SLC performance depends on the type of circuit (Style 4, Style 6, or Style 7) and the components on the circuit.
NOTE: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults that may occur within other areas of the SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists the trouble conditions that result when a fault exists on an SLC.
Type of Fault Style 4 Style 6 Style 7
Single Open Trouble Alarm, Trouble Alarm, Trouble Single Ground Alarm, Trouble (ground) Alarm, Trouble (ground) Alarm, Trouble (ground) Short Trouble Trouble Alarm, Trouble Short and open Trouble Trouble Trouble Short and ground Trouble Trouble Alarm, Trouble Open and ground Trouble Alarm, Trouble Alarm, Trouble Communications loss Trouble Trouble Trouble
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

1.7 Surge Suppression

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to “Surge Suppression” on page 71.
Table 1.2 SLC Performance

1.8 LED Operation

The table below lists the LED operation on the various devices on an SLC.
Device Standby Activated
Monitor Module Control Module Detector
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 13
Blinks RED Blinks GREEN Blinks RED
Steady RED Steady GREEN Steady RED
Table 1.3 LED Operation

Section 2: Wiring Requirements

2.1 Wire Sizing

The SLC requires use of a specific wire type, depending on the mode of operation, to ensure proper
2
circuit functioning. Wire size should be no smaller than 18 AWG (0.75 mm
2
AWG (3.25 mm
) wire. The wire size depends on the length of the SLC circuit. It is recommended
) and no larger than 12
that all SLC wiring be twisted-pair to minimize the effects of electrical interference.

2.1.1 CLIP (Classic Loop Interface Protocol) Mode

All addressable FACPs can operate in CLIP (Classic Loop Interface Protocol) mode. It is recommended that all SLC wiring be twisted-pair and shielded when operating in CLIP mode to reduce the effects of electrical interference. Use the table below to determine the specific wiring requirements for the SLC.
Wire Requirements Distance in Feet (meters) Wire Size Wire Type
2
) Belden 9583, Genesis 4410,
Signal 98230, WPW D999
2
) Belden 9581, Genesis 4408,
Signal 98430, WPW D995
2
) Belden 9575, Genesis 4406, &
4606, Signal 98630, WPW D991
2
) Belden 9574, Genesis 4402 &
4602, Signal 98300, WPW D975
Twisted-pair, shielded
10,000 feet (3,048 m) 12 AWG (3.1 mm
8,000 feet (2,438 m) 14 AWG (2.0 mm
4,875 feet (1,486 m) 16 AWG (1.3 mm
3,225 feet (983 m) 18 AWG (0.75 mm
MS-9200 = 1,000 feet (305 m)
Untwisted, unshielded wire, inside conduit or not in conduit

2.1.2 LiteSpeed Mode

Wire Requirements Distance in Feet (meters) Wire Size Wire Type
Twisted-pair, unshielded
MS-9600, MS-9600LS(C) & MS-9600UDLS = 3,000 feet (914 m)
MS-9200UD & MS-9200UDLS = 3,000 feet (914
m) MS-9050UD = 3,000 feet (914 m)
12 to 18 AWG
Table 2.1 SLC Wiring Requirements in CLIP Mode
The MS-9200UDLS, MS-9600LS, and MS-9600UDLS SLC can be programmed to operate in LiteSpeed mode for a quicker device response time. While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Use the following table to determine the specific wiring requirements for the SLC.
2
10,000 feet (3,048 m) 12 AWG (3.1 mm
8,000 feet (2,438 m) 14 AWG (2.0 mm
4,875 feet (1,486 m) 16 AWG (1.3 mm
3,225 feet (983 m) 18 AWG (0.75 mm
) Belden 5020UL & 6020UL,
Genesis WG-4315 & WG-4515
2
) Belden 5120UL & 6120UL,
Genesis WG-4313 & WG-4513
2
) Belden 5220UL & 6220UL,
Genesis WG-4311 & WG-4511
2
) Belden 5320UL & 6320UL,
Genesis WG-4306 & WG-4506
Table 2.2 SLC Wiring Requirements in LiteSpeed Mode
14 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Measuring Resistance & Length Wiring Requirements
SLC-meas1.wmf
SLC Out
Branch
Short Point
Figure 2.1 Measuring DC Resistance of a Two-Wire SLC
Branch A Branch B
Branch C
SLC-meas2.wmf
SLC Terminal Block
Figure 2.2 Measuring the Total Wire Length - Two-Wire SLC

2.2 Measuring Resistance & Length

2.2.1 Two-Wire SLC - Style 4 (Class B)

Loop Resistance
T-tapping of the SLC wiring is permitted for 2-wire Style 4 configurations. The total DC resistance from the control panel to each branch end cannot exceed 40 ohms. Measure DC resistance as detailed and shown below:
1. With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.
Total Wire Length
The total wire length of all combined branches of one SLC cannot exceed the limits set forth in each system’s instruction manual. Determine the total length in each SLC by summing the wire lengths of all branches of one SLC.
In the following figure, the total length of the SLC is determined by adding the lengths of Branch A plus Branch B plus Branch C.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 15
Wiring Requirements Measuring Resistance & Length
SLC-meas3.wmf
SLC Out
SLC Return
Short Point
Figure 2.3 Measuring DC Resistance of a Four-Wire SLC
B+ B– A– A+
SLC-meas4.wmf
SLC channel B (output loop)
SLC channel A
(return loop)
SLC Terminal Block
Figure 2.4 Measuring the Wire Length – Four-Wire SLC

2.2.2 Four-Wire SLC Style 6 & 7 (Class A)

Loop Resistance
The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as detailed and shown below.
1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the two leads of SLC channel A (Return).
3. Measure the resistance across the SLC channel B (Out) leads.
Total Wire Length
The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s instruction manual. The figure below identifies the output and return loops from SLC terminal on the control panel:
16 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Shield Wire Termination Wiring Requirements
!
Cabinet
SLC-shieldterm.wmf
Shield Drain Wire
Shield Foil
Conduit
MS-9600 MS-9600LS MS-9600UDLS MS-9200UD MS-9200UDLS MS-9050UD
MS-9200
Figure 2.5 Shield Termination

2.3 Shield Wire Termination

The drawing below shows the method of proper termination of the shield. Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire
through the conduit, into the control box. The shield drain wire must be connected to the “shield” terminal on the SLC terminal block.
NOTE: Use of good wiring practice consistent with local electrical codes is expected.
CAUTION: DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE SYSTEM CABINET OR BE CONNECTED TO EARTH GROUND AT ANY POINT.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 17
Wiring Requirements Control Panel Terminal Blocks
TB6
SHIELD SLC SLC
TB4
SLC-9200tb.wmf
SLC Return
SLC Out
Connections for wire shield
Unregulated Power
Nonresettable Power
Resettable Power
Figure 2.6 MS-9200 Terminal Blocks
TB8
SHIELDSLC SLC SLC SLC
TB3
SLC Return
SLC Out
Connections for wire shield
Nonresettable Power
Resettable Power
SLC-9600tb.wmf
Figure 2.7 MS-9600 Series Terminal Blocks

2.4 Control Panel Terminal Blocks

The terminal blocks on the control panel circuit board that concern the SLC circuit are described below. For more information on this subject refer to the control panel’s Instruction Manual.

2.4.1 MS-9200

TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable. TB6 provides connections for the SLC wiring. 198 addresses are available per loop (99 detectors and 99 modules).

2.4.2 MS-9600, MS-9600LS, & MS-9600UDLS

TB3 provides two types of 24 VDC power; Nonresettable and Resettable. TB8 provides connections for the SLC wiring. 198 addresses are available per loop (99 detectors and 99 modules) while operating in CLIP mode.
318 addresses are available per loop (159 detectors and 159 modules) while operati ng in LiteSp eed mode.
18 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Control Panel Terminal Blocks Wiring Requirements
TB10
SLC
TB1
SLC Out
Connections for wire shield
Resettable Power­jumper selectable by JP6
Nonresettable Power- jumper selectable by JP4
SLC-9200udtb.wmf
SLC Return
Figure 2.8 MS-9200UDLS (Rev 3) Terminal Blocks
TB10
SLC
TB1
SLC Out
Connections for wire shield
Resettable Power
Nonresettable Power
SLC-9200udtb.wmf
SLC Return
Figure 2.9 MS-9200UD & MS-9200UDLS (Rev 1 & 2) Terminal Blocks

2.4.3 MS-9200UDLS (Software Version 3.0)

TB1 provides two types of 24 VDC power; Nonresettable and Resettable, jumper selectable by JP4 and JP6.
TB10 provides connections for the SLC wiring. 198 addresses are available per loop (99 detectors and 99 modules).

2.4.4 MS-9200UD & MS-9200UDLS (Versions 1 and 2)

TB1 provides two types of 24 VDC power; Nonresettable and Resettable. TB10 provides connections for the SLC wiring. 198 addresses are available per loop (99 detectors and 99 modules).
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 19
Wiring Requirements Control Panel Terminal Blocks
SLC Out
Connections for wire shield
SLC-9050udtb.wmf
SLC Return
Figure 2.10 MS-9050UD Terminal Block

2.4.5 MS-9050UD

24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8. TB2 provides connections for the SLC wiring. 50 addresses are available (any combination of detectors and modules).
20 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014

Section 3: SLC Circuits without Isolators

SLC-style4.wmf
Two-wire Addressable Detector
Addressable Module
T-tapped Circuits
Control Panel SLC
B+ B–
Figure 3.1 Basic NFPA Style 4 SLC

3.1 Overview

This chapter concerns itself with the two styles of circuits that do not require isolation devices:
NFPA Style 4
NFPA Style 6

3.2 NFPA Style 4 SLC

NFPA Style 4 requirements can be met by using the diagram below.
T-tapping of the SLC wiring is allowed for Style 4 configuration.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 21
SLC Circuits without Isolators NFPA Style 6 SLC
Control Panel SLC
Two-wire Addressable Detector
Addressable Module
SLC-style6.cdrwmf
SLC Return
SLC Out
B+ B– A– A+
Figure 3.2 Basic NFPA Style 6 SLC

3.3 NFPA Style 6 SLC

NFPA Style 6 requirements can be met by using the diagram below.
T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
22 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014

Section 4: SLC Circuits with Isolators

!

4.1 Fault Isolator Devices

There are three isolator devices used to protect critical elements of the SLC from faults on other SLC branches or segments.
Fault Isolator Module I300
Six Fault Isolator Module ISO-6
Isolator Detector Base B224BI
A Fault Isolator Module on both sides of a device, or the combination of Isolator Base and Isolator Module is required to comply with NFPA Style 7 requirements.
CAUTION: MAXIMUM ADDRESSABLE DEVICES
If relay or sounder bases are not used, a maximum of 25 addressable devices can be
connected between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum number of addressable devices that can be connected between Isolators is reduced to seven. Isolator modules will not function properly when these limits are exceeded.
When more than 100 Isolator Modules are connected to an SLC loop, the address capacity
of the loop is reduced by two (2) addresses for every isolator device in excess of 100.

4.1.1 Isolating an SLC Branch

The module continuously monitors the circuit connected to terminals 3(–) and 4(+). Upon power­up, an integral relay is latched on. The module periodically pulses the coil of this relay. A short cir­cuit on the SLC resets the relay. The module detects the short and disconnects the faulted SLC branch or segment by opening the positive side of the SLC (terminal 4). This isolates the faulty branch from the remainder of the loop preventing a communication problem with all other address­able devices on the remaining branches (labeled “Continuation of the SLC” in the figure below). During a fault condition, the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch. Once the fault is removed, the module automati­cally reapplies power to the SLC branch or segment.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 23
SLC Circuits with Isolators Fault Isolator Devices
(-) (+) (-) (+)
SLC
Isolated branch
of the SLC
SLC-isowire2.wmf
Continuation of the SLC
OUT
OUT
IN
IN
Figure 4.1 Wiring an I300 Module
ISOLATOR 1
ISOLATOR 2
ISOLATOR 3 ISOLATOR 4
ISOLATOR 5
ISOLATOR 6
iso-6wire.wmf
SLC in from FACP or previous device
Figure 4.2 Wiring an ISO-6 Module
SLC out to
next device
status indicators
+
-
+
-

4.1.2 Wiring an Isolator Module

The figure below shows typical wiring of an I300Isolator Module:
The figure below shows typical wiring of an ISO-6 Isolator Module:
24 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
NFPA Style 4 SLC Using Isolator Modules SLC Circuits with Isolators
Figure 4.3 NFPA Style 4 SLC Using an I300 Isolator Module
Two-wire Addressable Detector
Addressable Pull Station
SLC-style4iso.wmf
Control Panel SLC
B– B+
Isolated Branch
Isolator Module
Isolator Module
Isolator Module
Isolated Branch
Isolated Branch

4.2 NFPA Style 4 SLC Using Isolator Modules

A variation of a Style 4 operation using an I300 isolator module to protect each branch of the SLC is shown below. Refer to Figure 4.1 for I300 wiring and to Section 4.1 for limitations.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 25
SLC Circuits with Isolators NFPA Style 4 SLC Using Isolator Modules
Figure 4.4 NFPA Style 4 SLC Using an ISO-6 Isolator Module
Two-wire Addressable Detector
Addressable Pull Station
Control Panel SLC
ISO-6
ISOLATOR 1
Out ­Out + In ­In +
SLC-style4ISO-6.wmf
ISOLATOR 2ISOLATOR 3ISOLATOR 4ISOLATOR 5ISOLATOR 6
Isolated Branch
Isolated Branch
Isolated Branch
A variation of a Style 4 operation using an ISO-6 isolator module to protect each branch of the SLC is shown below. Each terminal on the ISO-6 acts as a single I300 module. Refer to Figure 4.2 for ISO-6 wiring and to Section 4.1 for limitations. Note that the ISO-6 cannot accept two wires at one pin. Wire Style 4 SLC loops as shown in the figure below.
26 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
NFPA Style 6 SLC Using Isolator Modules SLC Circuits with Isolators
Figure 4.5 NFPA Style 6 SLC Using Isolator Modules
SLC Out SLC Return
SLC-style6iso.wmf
Control Panel
Two-wire Addressable Detector
Section B
Section C
Section A
Isolator Module
Isolator Module
Isolator Module
Additional isolator module required when first device in the
section is more than 20 feet from the control panel.
Isolator Module
Isolator Module
Isolator Module
Addressable
Pull Station

4.3 NFPA Style 6 SLC Using Isolator Modules

A variation of Style 6 operation using isolator modules to protect a section of the SLC. By flanking each group of devices with an I300 fault isolator module each group is protected from faults that may occur in the other groups. For example, a fault in Section B will not effect Sections A & C. The isolator modules on either side of Section B will open the loop. Section A will still operate from power on the SLC Out side and Section C will operate from the SLC Return side.
A combination of isolator modules and isolator bases may be used.
T-tapping is NOT allowed within the Style 6 configuration.
Isolator modules shall be within 20 feet (6.1 meters) of device and must be enclosed in metal conduit.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 27
Loading...
+ 61 hidden pages