Honeywell SiXGB Installation Instructions Manual

> 2.0m (6.5')
Optimal Satisfactory No
> 1m
(3.3')
<
7.6m (25')
> 1m
(3.3')
> 5 cm
(2”) Diameter
RF6GB-W allMount
Wall Mo unt ( TopView )
Do NOT mo unt o n co lumns, po sts o r po le s.
Glass
Ceiling Mount (Side View)
RF6GB-Ce ilingMount
Ceiling
Glass
Floo r
3.5 mm x 25 mm (#6 x 1")
[2]
3.5 mm x 25 mm (#6 x 1")
[1]
A
L
I
G
N
t
o
D
I
M
P
L
E
SiXTM
Series
The SiXGB is a wireless glassbreak detector intended for use with Honeywell controls that support SiX™ Series devices.
SiXGB
Mounting Guidelines
The SiXGB can be mounted on the wall or on the ceiling:
within 7.6 m (25 feet) of the protected glass
within clear view of the protected glass
at least 2 m (6.5 feet) from the floor
at least 1 m (3.3 feet) from forced
air ducts
at least 1 m (3.3 feet) from sirens or bells greater than 5 cm (2 inches) in diameter
between the protected glass and any heavy window coverings
when heavy window coverings are present, the detector can be mounted on the window frame
Avoid mounting the detector on the same wall as the protected glass, on free-standing posts or pillars, or in rooms with noisy equipment (air compressors, bells, power tools, etc.), if this equipment is operated when the detector is armed.
To remove the mounting bracket:
Turn the top of the detector 15 degrees counter­clockwise and separate the mounting bracket.
NOTE: Before mounting the device permanently, conduct Go/No Go tests (see controller’s instructions) to verify adequate signal strength and adjust the device location and orientation as necessary.
The rear tamper plate MUST be mounted to a stud, solid wood, or with a robust wall anchor.
PULL
TO
CONNECT
Serial Number Loop Number
Zone Description 1 Zone Description 2
Device Type Response Type
Alarm Report Chime Supervision
Panic Home
The Green LED
is ON for
3 seconds
1
2
4
Trigger the
device again
3
The Green LED
flashes. Wait up to
about 20 seconds
30
0
45
20
10
PULL
TO
CONNECT
Programming Mode > Zones > Add New > Serial Number
/
5
Press SAVE
6
Enroll
This device can be enrolled and programmed either before or after installation.
1. Set the Lyric Controller in Programming Mode and go to Zone Programming. Select Add New, then Serial Number. Follow the controller’s instructions to begin enrollment.
2. Remove the battery tab to activate the device and begin the enrollment process.
3. The Green [G1]1 LED flashes during enrollment (up to about 20 seconds*)
*NOTE: Enrollment time varies depending on the signal strength between the device and the controller.
The device sends its unique MAC ID
(Serial Number) and Services information to the controller.
The controller registers the device and
displays the transmitter data on screen.
4. The Green [G1] LED is ON for 3 seconds and the controller beeps to confirm enrollment.
5. Trigger the detector as shown to complete enrollment.
6. Press SAVE.
If the sensor is not successfully enrolled during the enrollment period, the LED turns off and the device powers down. Activate the tamper, power down and up again, or use the FG-701 Glassbreak Simulator to restart the enrollment process.
The device can also be manually enrolled. See the Controller’s Programming Guide for details.
1
Refer to the SiXGB LEDs section.
Program the SiXGB
Consult the Controller’s instructions for programming the device in the system.
Adjust the detector sensitivity setting in the controller programming mode. Refer to the table on the right for sensitivity options.
After enrolling, update the SiXGB firmware (via the Controller) to ensure the latest version is used. See the Controller’s instructions.
NOTE: Once enrolled in a system, the detector cannot be used with another controller until it is removed from the current controller. See the Controller’s instructions for details.
Sensitivity Setting Approximate Range
High* 4.6-7.6m / 15-25 ft.
Medium 3-4.6m / 10-15 ft.
Low 1.5-3m / 5-10 ft.
Lowest 0-1.5m / 0-5 ft.
*Factory default. Change the sensitivity setting at the Controller.
2
Loading...
+ 2 hidden pages