Honeywell Silent Knight SK-Duct Installation And Maintenance Instructions Manual

WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3432-006
SK-Duct
12 Clintonville Road, Northford, CT 06472-1610
Phone: 203-484-7161 Fax: 203-484-7118
Air Duct Smoke Detector
SPECIFICATIONS
Operating Temperature: –4° to 158°F (–20° to 70°C) 32° to 120°F (0° to 49°C) with module installed in the SK-Duct Storage Temperature: –22° to 158°F (–30° to 70°C) Humidity: 0% to 93% Relative Humidity Non-condensing Air Velocity: 100 to 4000 ft./min. (0.5 to 20.3 m/sec.) Rectangular Footprint Dimensions: 14.38 in L×5 in W×2.5 in D (37 cm L×12.7 cm W×6.36 cm D) Square Footprint Dimensions: 7.75 in L×9 in W×2.5 in D (19.7 cm L×22.9 cm W×6.35 cm D) Weight: 1.8 pounds; 0.82 kg Operating Voltage Range: 15 to 32 VDC Standby Current: 300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled) Max. Alarm Current (LED on): 6.5 mA @ 24 VDC
NOTE: The SK-Duct comes with the sensor head factory installed, part number SK-PHOTOR.
Table of Contents Page
[1] Limitations of Duct Smoke Detectors .........................1
[2] General Description .....................................1
[3] Contents of the Duct Smoke Detector Kit ......................1
[4] Detector Installation .....................................1
[5] Sampling Tube Installation ................................2
[6] Measurement Tests ......................................3
[7] Field Wiring ...........................................3
[8] Verification of Operation ..................................4
[9] Detector Cleaning Procedures ..............................4
[10] Sensor Replacement ....................................5
[11] Optional Accessories ....................................5
Warranty .............................................6
BEFORE INSTALLING
Read System Sensor's Applications Guide: Duct Smoke Detectors (HVAG53), which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available online at www.systemsensor.com. NFPA Standards 72 and 90A should also be refer­enced for detailed information.
[1] LIMITATIONS OF DUCT SMOKE DETECTORS
The National Fire Protection Association has established that DUCT DETEC­TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. The SK-Duct Air Duct Smoke Detectors are listed per UL 268A.
This device will not operate without electrical power. Fire situations may cause an interruption of power. The system safeguards should be discussed with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating and the cover is installed.
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be operated within ALL electrical and environmental specifications listed in this manual and the sensor head installation manual. Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct.
[2] GENERAL DESCRIPTION
Smoke introduced into this air duct system will be distributed throughout the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
Model SK-Duct Air Duct Smoke Detector utilizes photoelectric technology for the detection of smoke. This detection method, when combined with an ef­ficient housing design, samples air passing through the duct and allows detec­tion of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans, blowers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
The SK-Duct incorporates a sensor cover tamper feature that provides a trou­ble signal at the panel immediately if the cover is removed or improperly in­stalled. Proper installation of the sensor cover removes the trouble condition.
If programmed with the system control panel, two LEDs on each duct smoke detector light to provide local visible indication.
The SK-Duct provides a remote alarm output for use with auxiliary devices, such as the RA400Z/RA100Z remote LED annunciator, as well as remote test capability with the RTS451/RTS151 or RTS451KEY/RTS151KEY Remote Test Stations.
[2.1] DETECTOR FEATURE SET
– Utilizes plug-in head, part number SK-PHOTOR – Sampling tubes install from front and rear – Compatible with existing accessories – Able to address detector per code switches on sensor head.
[3] CONTENTS OF THE DUCT SMOKE DETECTOR KIT
1. Sensor/power board assembly and covers sensor head is factory installed
2. Three #10 sheet metal screws for mounting
3. Drilling template
4. One sampling tube end cap
5. One plastic exhaust tube NOTE: A sampling tube must be ordered to complete the installation. It must be the correct length for the width of the duct where it will be installed. See Table 1 on page 3 to determine the inlet tube required for different duct widths.
[4] DETECTOR INSTALLATION [4.1] VERIFY DUCT AIR FLOW DIRECTION AND VELOCITY
Model SK-Duct detectors are designed to be used in air handling systems hav­ing air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12 feet can be accommodated. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If neces­sary, use a velocity meter (anemometer) to check the air velocity in the duct.
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE STANDBY ALARM
RA400Z/RA100Z 0 mA 12 mA Max. RTS451/RTS151 0 mA 12 mA Max.
RTS451KEY/ RTS151KEY
www.silentknight.com
12 mA 12 mA Max.
1 I56-3432-006 04-12
EXHAUST TUBE
FIGURE 1. EXPLODED VIEW OF DUCT SMOKE DETECTOR COMPONENTS:
REMOVE SCREW AND PIVOT
REPLACE SCREW
SAMPLING
TUBE SOLD
SEPERATELY
SENSOR MODULE
SENSOR HEAD
NOTE: SENSOR HEAD IS ONLY INCLUDED ON SPECIFIED MODELS.
WIRING COMPARTMENT
WIRING COMPARTMENT COVER
SENSOR MODULE COVER
H0569-06
[4.2] ] DETERMINE MOUNTING LOCATION AND CONFIGURATION
On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend, obstruction in the duct, or the supply or return air inlet.
Exception: Installation of duct detectors can be on or within a commercial packaged rooftop heating and air-conditioning system, fire/smoke dampers and economizers. They may be mounted in either the supply and/or return air section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted in a side-by-side “rectangular” configuration or a top-over-bottom “square” configuration as shown in Figure 2. If mounting in the square configuration, remove the rear attachment screw, rotate the unit at hinge, and replace the screw into the new attachment hole as shown in Figure 2. Do NOT remove the hinge screw during this process. Final installation approval shall be based upon passing differential pressure and smoke entry tests described in the Mea­surement Tests section.
[4.3] DRILL THE MOUNTING HOLES
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct.
[4.3.1] FOR RECTANGULAR SIDE-BY-SIDE MOUNTING CONFIGURATION:
Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for the rectangular configuration mounting tabs as shown on mounting template. Drill pilot holes at target “A” centers and cut two 1.375-inch diameter holes using a 13⁄8-inch hole saw or punch. Drill .156-inch diameter holes using a 5⁄32­inch drill at target “B” centers.
FIGURE 2:
DETECTOR AS SHOWN BELOW.
TO SECURE DETECTOR
IN PLACE.
[4.3.2] FOR SQUARE TOP-OVER-BOTTOM MOUNTING CONFIGURATION:
Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for the square configuration mounting tabs as shown on mounting template. Drill pilot holes at target “A” centers and cut two 1.375-inch diameter holes using a 13⁄8-inch hole saw or punch. Drill .156-inch diameter holes using a 5⁄32-inch drill at target “C” centers. If desired, drill an additional .156-inch hole at the location of one of the mounting tabs on the lower housing.
[4.4] SECURE THE DUCT DETECTOR TO THE DUCT
Use two (rectangular configuration) or three (square configuration) of the pro­vided sheet metal screws to screw the duct detector to the duct.
CAUTION: Do not overtighten the screws.
[5] SAMPLING TUBE INSTALLATION [5.1] SAMPLING TUBE SELECTION
The sampling tube must be purchased separately. Order the correct length, as specified in Table 1, for width of the duct where it will be installed. The sampling tube length must extend at least 2⁄3 across the duct width for optimal performance.
The sampling tube is always installed with the air inlet holes facing into the air flow. To assist proper installation, the tube’s connector is marked with an arrow. Make sure the sampling tube is mounted so that the arrow points into the airflow as shown in Figure 3. Mounting the detector housing in a vertical orientation is acceptable provided that the air flows directly into the sam­pling tube holes as indicated in Figure 3. The sampling tube and exhaust tube can be mounted in either housing connection as long as the exhaust tube is mounted downstream from the sampling tube.
TABLE 1. SAMPLING TUBES RECOMMENDED FOR DIFFERENT DUCT WIDTHS:
Outside Duct Width Sampling Tube Recommended*
Up to 1 ft. DST1
1 to 2 ft. DST1.5
2 to 4 ft. DST3
4 to 8 ft. DST5
8 to 12 ft. DST10 (2-piece)
*Must extend a minimum of 2⁄3 the duct width.
2 I56-3432-006 04-12
H0550-00
Loading...
+ 4 hidden pages