Installation of this product must be performed by a trained and
qualified service technician.
APPLICATION
The S8910U Universal Hot Surface Ignition Module is
designed to provide easy field replacement for a wide range of
hot surface ignition modules manufactured by Honeywell,
Robertshaw and White-Rodgers. The S8910U Module
provides operating control of a direct ignition system using a
120 Vac hot surface igniter. The S8910U replaces existing
flame rectification type hot surface ignition modules with the
following characteristics:
• 120 Vac (up to 5A) timed warmup hot surface ignition
elements.
• Single rod (local sense) or dual rod (remote sense) hot
surface ignition.
• One or three ignition trials per call for heat.
• Four-second or seven-second ignition trials.
• Prepurge of 32 seconds or less.
• Up to 96 seconds between trial purge times (three-trial
mode only).
• Natural or LP gas.
The S8910U is not designed to replace:
• Intermittent pilot ignition controls.
• Direct spark ignition controls.
• Proven 120 Vac hot surface ignition controls.
• 24 Vac element hot surface ignition controls.
• 240 Vac input/120 Vac element hot surface ignition
controls.
• 120 Vac timed warmup hot surface ignition controls
— Ignition trial time shorter than four seconds.
— Ignition trial time longer than twelve seconds.
— Edge connectors rather than male quick-connects.
The S8910U package contains the S8910U control, and easyto-use instructions, and the accessories required to adapt the
existing hot surface ignition module. The accessory bag
assembly includes the White-Rodgers adapter, Robertshaw
ground lead, four 1/4 in. female .032 quick-connects, one 3/16
in. female .032 quick-connect, and nine wire labels. The
wiring labels are included to assure proper marking of the
wires attached to the existing module.
A complete list of the specific Honeywell and other modules
that the S8910U is designed to replace is provided in Tables 1
through 3.
NOTE: The S8910U is intended to replace only defective
ignition controls. The service technician should
make sure that the other parts of the appliance
and control system operate safely and reliably
before replacing the ignition control.
EXPLOSION HAZARD. CAN CAUSE INJURY OR
EQUIPMENT DAMAGE.
The S8910U can only be used for direct replacement.
Check Tables 1 through 3 before replacing an existing
hot surface module with the S8910U. If the existing
module is not listed, do not use the S8910U to replace
it. Always refer to the cross-reference table for proper
DIP switch settings.
Electrical Ratings:
Control Voltage: 24 V, 60 Hz.
Maximum Valve Contact Rating: 2 A.
Current Draw: 0.4 A plus valve load.
Hot Surface Igniter Voltage: 120 Vac, 60 Hz.
Contact Rating at 120 Vac: 5 A.
IMPORTANT
The S8910U is designed for 60 Hz applications.
Timings change by 20 percent in 50 Hz applications.
Hot Surface Igniter or Igniter-Sensor:
Norton Model 201 or 271 or equivalent.
NOTE: If an igniter other than a Norton Model 201 or 271
is used, the igniter must meet the following minimum specifications required over the life of the
igniter:
• Igniter must reach 1832 °F (1000 °C) within
the selected warm up time of 7, 17, 34 or
45 seconds with 102 Vac applied.
• Igniter must maintain at least 500M ohm
insulation resistance between the igniter
leadwires and the igniter mounting bracket.
• Igniter must not develop an insulating layer
on its surface (over time) that would prevent
flame sensing.
• Igniter surface area immersed in flame must
not exceed one-fourth of the grounded area
immersed in flame. This would prevent flame
sensing.
S8910U3000
• Igniter current draw at 132 Vac must not
exceed 5A.
Sensor:
Separate sensor required for remote sensing applications.
Wiring:
Use existing appliance wiring. If repair or replacement of lead-
wires is required, follow instructions on appliance label.
Use included quick connect terminals and wiring adaptors
according to instructions.
Prepurge:
32 seconds.
Igniter Warmup:
7 (12), 17 (27), 34 or 45 seconds. Numbers in parenthesis
represent second and third trial for ignition timings.
Purge between Trials for Ignition:
96 seconds (32 second prepurge and 64 seconds interpurge).
Flame Failure Response Time:
1.5 seconds maximum.
Ignition Sequence:
The number of trials for ignition and trial time are determined
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifications. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
The S8910U package contains the S8910U control, and easyto-use instructions, plus the accessories required to adapt the
existing hot surface ignition module. The accessory bag
assembly includes the White-Rodgers adapter, Robertshaw
ground lead, four 1/4 in. female .032 quick-connects, one 3/16
in. female .032 quick-connects, and nine wiring labels. The
wiring labels are included to assure proper marking of the
wires attached to the existing module.
A complete listing of the specific Honeywell and other
modules that the S8910U is designed to replace is provided in
Tables 1 through 3.
NOTE: The S8910U is intended to replace only defective
ignition controls. The service technician should
make sure that the other parts of the appliance
and control system operate safely and reliably
before replacing the ignition control.
Model Available:
S8910U Universal Hot Surface Ignition Module.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
34-00008EFS—012
Table 1. White-Rodgers Control to Honeywell S8910U Cross Reference.
NOTES: This list is for reference only. Honeywell reserves the right to add or delete models at any time, based on new or
updated information.
S8910U
Remove
Between
Trial Purge
(sec)
Model Numbers
S8910U
Specifications
Black
Jumper
Local (L) or
Remote (R)
Sensing
— Local or
Remote
Lockout
Time
(sec)
Ignition
Trial s
PrePurge
(sec)
Igniter
Warmup
(sec)
4 1 32 34 NA
3 96
7 1 NA
3 96
50E47-1 thru 9 Yes R 4 1 0 17 NA
50E47-10 thru 19 Yes R 4 1 0 45 NA
50E47-20 thru 29 Yes R 4 1 30 17 NA
50E47-30 thru 39 Yes R 4 1 30 45 NA
50E47-40 thru 49 Yes R 4 3 30 17 90
50E47-50 thru 59 Yes R 4 3 30 45 90
50E47-60 thru 69 Yes R 4 3 0 17 60
50E47-70 thru 79 Yes R 4 3 0 45 60
50E47-101 thru 109 Yes R 7 1 0 17 NA
50E47-110 thru 119 Yes R 7 1 0 45 NA
50E47-120 thru 129 Yes R 7 1 30 17 NA
50E47-130 thru 139 Yes R 7 1 30 45 NA
50E47-140 thru 149 Yes R 7 3 30 17 90
50E47-150 thru 159 Yes R 7 3 30 45 90
50E47-160 thru 169 Yes R 7 3 0 17 60
50E47-170 thru 179 Yes R 7 3 0 45 60
50E47-201 thru 209 Yes R 4 1 0 17 NA
50E47-210 thru 219 Yes R 4 1 0 45 NA
50E47-220 thru 229 Yes R 4 1 30 17 NA
50E47-230 thru 239 Yes R 4 1 30 45 NA
50E47-240 thru 249 Yes R 4 3 30 17 90
50E47-250 thru 259 Yes R 4 3 30 45 90
50E47-260 thru 269 Yes R 4 3 0 17 60
50E47-270 thru 279 Yes R 4 3 0 45 60
50E47-301 thru 309 Yes R 7 1 0 17 NA
50E47-310 thru 319 Yes R 7 1 0 45 NA
50E47-320 thru 329 Yes R 7 1 30 17 NA
50E47-330 thru 339 Yes R 7 1 30 45 NA
50E47-340 thru 349 Yes R 7 3 30 17 90
50E47-350 thru 359 Yes R 7 3 30 45 90
50E47-360 thru 369 Yes R 7 3 0 17 60
50E47-370 thru 379 Yes R 7 3 0 45 60
50F47-1 thru 9 Yes R 4 1 0 17 NA
50F47-10 thru 19 Yes R 4 1 0 45 NA
50F47-20 thru 29 Yes R 4 1 17 17 NA
50F47-30 thru 39 Yes R 4 1 17 45 NA
50F47-40 thru 49 Yes R 4 3 17 17 77
S8910U3000
334-00008EFS—01
S8910U3000
Table 1. White-Rodgers Control to Honeywell S8910U Cross Reference. (Continued)
NOTES: This list is for reference only. Honeywell reserves the right to add or delete models at any time, based on new or
updated information.
S8910U
Remove
Between
Trial Purge
(sec)
Model Numbers
S8910U
Specifications
Black
Jumper
Local (L) or
Remote (R)
Sensing
— Local or
Remote
Lockout
Time
(sec)
Ignition
Trial s
PrePurge
(sec)
Igniter
Warmup
(sec)
4 1 32 34 NA
3 96
7 1 NA
3 96
50F47-50 thru 59 Yes R 4 3 17 45 77
50F47-60 thru 69 Yes R 4 3 0 17 60
50F47-70 thru 79 Yes R 4 3 0 45 60
50F47-101 thru 109 Yes R 7 1 0 17 NA
50F47-110 thru 119 Yes R 7 1 0 45 NA
50F47-120 thru 129 Yes R 7 1 17 17 NA
50F47-130 thru 139 Yes R 7 1 17 45 NA
50F47-140 thru 149 Yes R 7 3 17 17 77
50F47-150 thru 159 Yes R 7 3 17 45 77
50F47-160 thru 169 Yes R 7 3 0 17 60
50F47-170 thru 179 Yes R 7 3 0 45 60
50F47-201 thru 209 Yes R 4 1 0 17 NA
50F47-210 thru 219 Yes R 4 1 0 45 NA
50F47-220 thru 229 Yes R 4 1 17 17 NA
50F47-230 thru 239 Yes R 4 1 17 45 NA
50F47-240 thru 249 Yes R 4 3 17 17 77
50F47-250 thru 259 Yes R 4 3 17 45 77
50F47-260 thru 269 Yes R 4 3 0 17 60
50F47-270 thru 279 Yes R 4 3 0 45 60
50F47-301 thru 309 Yes R 7 1 0 17 NA
50F47-310 thru 319 Yes R 7 1 0 45 NA
50F47-320 thru 329 Yes R 7 1 17 17 NA
50F47-330 thru 339 Yes R 7 1 17 45 NA
50F47-340 thru 349 Yes R 7 3 17 17 77
50F47-350 thru 359 Yes R 7 3 17 45 77
50F47-360 thru 369 Yes R 7 3 0 17 60
50F47-370 thru 379 Yes R 7 3 0 45 60
34-00008EFS—014
S8910U3000
Table 2. Robertshaw Control to Honeywell S8910U Cross Reference.
S8910U
Remove
Between
Trial Purge
(sec)
Model Numbers
S8910U
Specifications
Black
Jumper
Local (L) or
Remote (R)
Sensing
— Local or
Remote
Lockout
Time
(sec)
Ignition
Trial s
PrePurge
(sec)
Igniter
Warmup
(sec)
4 1 32 34 NA
3 96
7 1 NA
3 96
HS780-17NL-104A No L 4 1 0 17 NA
HS780-17NL-108A No L
a
8
1 0 17 NA
HS780-17NL-304A No L 4 3 0 17 17
HS780-17NL-308A No L
8a
3 0 17 17
HS780-17NR-104A Yes R 4 1 0 17 NA
HS780-17NR-306A Yes R
HS780-17NR-308A Yes R
HS780-34NL-108A No L
6
8
8a
a
a
3 0 17 17
3 0 17 17
1 0 34 NA
HS780-34NL-304A No L 4 3 0 34 34
HS780-34NL-306A No L
HS780-34NL-308A No L
HS780-34NL-312A No L
6a
8a
12b
3 0 34 34
3 0 34 34
3 0 34 34
HS780-34NR-104A Yes R 4 1 0 34 NA
HS780-34NR-306A Yes R
HS780-34NR-308A Yes R
HS780-34NR-312A Yes R
HS780-34PL-308A No L
a
The S8910U and the original control lockout times are different. The S8910U lockout time is within the design tolerance lockout
12
6a
8a
8a
b
3 0 34 34
3 0 34 34
3 0 34 34
3 34 34 34
time of the original control.
b
The lockout time of the S8910U is shorter than the original control. Be sure to observe the appliance operation under a variety of
input conditions to assure reliable operation.
534-00008EFS—01
S8910U3000
Table 3. Honeywell Control to Honeywell S8910U Cross Reference.
S8910U
Remove
Between
Trial Purge
(sec)
Model Numbers
S8910U
Specifications
Black
Jumper
Local (L) or
Remote (R)
Sensing
— Local or
Remote
Lockout
Time
(sec)
Ignition
Trial s
PrePurge
(sec)
Igniter
Warmup
(sec)
4 1 32 34 NA
3 96
7 1 NA
3 96
S89C1004 No L
S89C1012 No L
6
6a
a
1 0 34 NA
1 0 34 NA
S89C1046 No L 4 1 0 34 NA
S89C1087 No L
6a
1 0 34 NA
S89C1103 No L 4 1 0 34 NA
S89D1002 Yes R
a
6
1 0 34 NA
S89G1005 No L 4 3 0 34 30
S89G1013 No L
S89G1021 No L
S89G1047 No L
6a
11
6
b
a
3 0 34 30
3 0 34 30
3 0 34 30
S89H1003 Yes R 4 3 0 34 30
11
6
6a
6a
6
a
b
3 0 34 30
3 0 34 30
1 0 34 NA
1 30 34 NA
a
1 30 34 NA
S89H1011 Yes R
S89H1029 Yes R
S89J1008 No L
S890C1007 No L
S890D1006 Yes R
S890G1003 No L 4 3 30 34 30
11
a
6
b
a
6
3 30 34 30
3 30 34 30
3 30 34 30
S890G1011 No L
S890G1029 No L
S890G1037 No L
S890H1002 Yes R 4 3 30 34 30
11
a
6
b
S890H1010 Yes R
S890H1028 Yes R
a
The S8910U and the original control lockout times are different. The S8910U lockout time is within the design tolerance
3 30 34 30
3 30 34 30
lockout time of the original control.
b
The lockout time of the S8910U is shorter than the original control. Be sure to observe the appliance operation under a
variety of input conditions to assure reliable operation.
34-00008EFS—016
Table 4. DIP switch configuration.
WARNING
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
M35557
Trial count = 1 try
Trial count = 3 tries
Trial for ignition period = 4 seconds
Trial for ignition period = 7 seconds
Igniter warm-up time = 34 seconds
Igniter warm-up time = 45 seconds
S8910U3000
REVIEW THE INSTALLATION
FIRE OR EXPLOSION HAZARD.
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
Follow these warnings exactly:
1. Review the installation as outlined in this section.
2. Plan for frequent maintenance as described in the
Maintenance section.
When hot surface ignition systems are used on central heating
equipment in barns, greenhouses, and commercial properties
and on heating appliances such as commercial cookers,
agricultural equipment, industrial heating equipment and pool
heaters, heavy demands are made on the controls. Special
steps may be required to prevent nuisance shut-downs and
control failure due to frequent cycling, and severe
environmental conditions related to moisture, corrosive
chemicals, dust or excessive heat. These applications require
Honeywell Home and Building Control Engineering review;
contact your Honeywell Sales Representative for assistance.
Review the following conditions that can apply to your specific
installation and take the precautionary steps suggested.
Frequent Cycling
These controls are designed for use on appliances that
typically cycle only three to four times an hour during the
heating season. In year-around applications with greater
cycling rates, the control can wear out more quickly. Perform a
monthly checkout.
Igniter warm-up time = 17 seconds
(27 seconds 2
nd
and 3rd trial)
Igniter warm-up time = 7 seconds
(12 seconds 2
nd
and 3rd trial)
Water or Steam Cleaning
If a module or gas control gets wet, replace it. If the appliance
is likely to be cleaned with water or steam, cover the controls
and wiring to protect from water or steam flow. Mount the
controls high enough above the bottom of the cabinet to avoid
getting wet during normal cleaning procedures. A NEMA 4
enclosure is recommended for the ignition module.
High Humidity or Dripping Water
Dripping water can cause the module to fail. Never install an
appliance where water can drip on the controls.
In addition, high ambient humidity can cause the gas control to
corrode and fail.
If the appliance is in a humid atmosphere, make sure air
circulation around the controls is adequate to prevent
condensation. Also, regularly check out the system. A NEMA 4
enclosure is recommended for the ignition module.
Corrosive Chemicals
Corrosive chemicals can attack the module and gas control,
eventually causing a failure. If chemicals are used for routine
cleaning, avoid contact with the controls. Where chemicals are
suspended in air, as in some industrial or agricultural
applications, A NEMA 4 enclosure is recommended for the
ignition module.
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause controls to
malfunction. Where dust or grease can be a problem, provide
covers for the module and the gas control to limit
contamination. A NEMA 4 enclosure is recommended for the
ignition module.
734-00008EFS—01
S8910U3000
WARNING
CAUTION
Heat
Excessively high temperatures can damage controls. Make
sure the maximum ambient temperature at the control does not
exceed the rating of the control. If the appliance operates at
very high temperatures, use insulation, shielding, and air
circulation, as necessary, to protect the controls. Proper
insulation or shielding should be provided by the appliance
manufacturer; verify proper air circulation is maintained when
the appliance is installed.
INSTALLATION
When Installing this Ignition System...
1. Read these instructions carefully. Failure to follow them
could damage the components or cause a hazardous
condition.
2. Check Tables 1, 2, and 3 to confirm that the S8910U is a
direct replacement for the existing module.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out component and
appliance operation as provided in these instructions.
FIRE OR EXPLOSION HAZARD.
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
1. If the ignition module gets wet, it can malfunction,
leading to accumulation of explosive gas.
— Never install where water can flood, drip or
condense on the module.
— Never use a module that has been wet.
Replace it.
2. Liquefied petroleum (LP) gas is heavier than air
and can not vent upward naturally.
— Do not light pilot or operate electric switches,
lights or appliances until you are sure the
appliance area is free of gas.
3. Do not attempt to disassemble or clean the module.
Improper reassembly and cleaning can cause
unreliable operation.
1. Disconnect the power supply before beginning
wiring to prevent electrical shock or equipment
damage.
2. If a new gas control is to be installed, turn off the
gas supply before starting the installation. Conduct
a Gas Leak Test according to the gas control
manufacturer instructions after the gas control is
installed.
3. If a module must be mounted where it can be
exposed to moisture or water, provide a suitable
waterproof enclosure.
4. Using the wire labels provided, label all wires
before disconnecting. Wiring errors can cause
improper appliance operation and create
dangerous conditions such as bypassing safety
features.
Perform Preinstallation Safety Inspection
A preinstallation safety check of the appliance and venting
system must be done before the replacement module is
installed. If a condition is detected that could result in unsafe
operation, shut off the appliance and advise the owner of the
unsafe condition. Correct any potentially unsafe condition
before proceeding with the installation.
Remove Old Module
Disconnect power supply before doing any work on the unit.
Disconnect and tag the wires from the old module using the
wire labels provided. Remove the old module from its mounting
location.
Mount New Ignition Module
Mount the S8910U Module in the same location as the old
module. Protect the module from exposure to water, moisture,
corrosive chemicals and excessive dust and grease. Assure
that ambient temperature at the module is within the range
listed in the Application section.
Mount the module with the terminals down to protect from
dripping water and dust. The module can also be mounted with
terminals on either side. Do not mount with the terminals pointing up. Refer to Fig. 1 for mounting recommendations.
When it is necessary to drill new mounting holes, use the
S8910U as a template to mark the mounting hole pattern. Drill
new holes as required. Fasten securely with four No. 6-32
machine or No. 8 sheet metal screws.
34-00008EFS—018
WARNING
CAUTION
TERMINALS FACING DOWN
TERMINALS FACING LEFTTERMINALS FACING RIGHT
MOUNT IN ONE OF THESE POSITIONS
DO NOT MOUNT
WITH TERMINALS FACING UP
M2647A
Fig. 1. Module mounting recommendations.
EXPLOSION HAZARD. CAN CAUSE
INJURY OR EQUIPMENT DAMAGE.
Only trained professional gas appliance service
technicians should install and check out the S8910U.
S8910U3000
Wire the Module
1. Check the wiring diagram furnished by the
appliance manufacturer, if available, and compare
with Table 5. Carefully follow any special
instructions affecting the general procedures
outlined in this section.
2. Disconnect the power supply before making wiring
connections to prevent electrical shock or
equipment damage.
IMPORTANT
1. Be sure all wiring complies with applicable electrical
codes and ordinances.
2. Hot surface igniter leadwires should not be allowed to
rest against grounded metal surfaces.
3. A common ground is required for the S8910U and the
main burner. The 24V (GND) terminal internally
grounds one side of the transformer. Any auxiliary
controls or limits must not be in the grounded leg. In
addition, the appliance should be earth-grounded.
4. Make sure the transformer has adequate VA. The
ignition module requires 0.4A at 24 Vac. Add the current draws of all other devices in the control circuit,
including the pilot and main valves in the gas control,
and multiply by 24 to determine the total VA requirement of these components. Add this total to 9.6 VA
(for the ignition module). The result is the minimum
transformer VA rating. Use a Class II transformer
when replacement is required.
5. Check that L1 (hot) and L2 (neutral) are wired to the
proper terminals.
1. Connect the wires to the S8910U Ignition Module as
shown in Table 5. Make sure that adequate system
ground is provided as indicated in the wiring table. See
Fig. 2 through 4. Where a change in quick-connect is
required, cut off the original quick-connect, strip the leadwire and firmly crimp in place the proper quick-connect
supplied.
2. Verify the thermostat anticipator setting as explained in
the preceding IMPORTANT, item 4.
Selectable DIP switches allow the ignition module to be
customized for the appropriate trial count, trial for
ignition period, and igniter warm-up time. Use only the
appropriate DIP switch configuration as given in Table 4
on page 7. Refer to Tables 1, 2, and 3 for appropriate
number of ignition trials, warm-up, prepurge and
between trial prepurge timings.
Improper DIP switch configuration can result in
appliance malfunction.
934-00008EFS—01
S8910U3000
Table 5. Replacement Wiring Terminals.
Replacement ControlOriginal Control
S8910U
Terminal Function
Terminal
Burner Ground Connection GND (BURNER)
Tranformer Secondary
24V (GND)
(unswitched leg)
Main Valve Common VALVE (GND)
Honeywell
S89/S890 Terminal
GND (BURNER)
24V (GND)
VALVE (GND)
a
a
White Rodgers
50E/F47 Terminal
a
MVa (next to TR
Robertshaw
HS780 Terminal
GND
TR (GND CLIP)
TR GND
—
terminal)
Transformer Secondary
24V
(switched leg)
Main Valve Operator VALVE VALVE
e
120 Vac Neutral Leg Power Supply
L2 120V NEUTRAL
L2 120V NEUTRAL—L2
120 Vac Hot Leg Power Supply L1 120V HOT L1 120V HOT
Hot Surface Igniter Element
HSI 120V NEUTRAL
e
Hot Surface Igniter Element HSI 120V HOT HSI 120V
Flame Sensor
a
Remove quick-connect and replace with the included 1/4 in. quick-connect.
b
Use green adapter cable (provided) to connect S8910U GND (BURNER) terminal to chassis ground.
c
Do not use the S8910U VALVE (GND) terminal. VALVE (GND) and 24V (GND) are interconnected in the appliance wiring.
d
Remove quick-connect and replace with the included 3/16 in. quick-connect.
e
Do not use this terminal if model being replaced does not have 120V neutral power supply connection.
f
Use the black wire on the included adapter cable.
g
Use the orange wire on the included adapter cable.
h
On remote sense models, remove jumper quick-connect from S8910U sense terminal, cut jumper wire at circuit board and
SENSEh SEN
24V
a
TH TH
MV
L
d
f
VALVE
L1
HSI 120V—IGN
g
IGN
h
FP
i
IGN
RS
discard. On local sense models, leave black jumper connected.
i
Remove jumper from S8910U sense terminal, cut jumper wire at circuit board and discard.
Prepurge Time = 32 Sec.
Igniter Warm Up Time = See Inst. Sh. 34-00008
Ignition Trial Time - See Selection Tab
Number of Trials - See Selection Tab
Between Trial Time - 96 Sec.
See
LED
States
(GND)
TH-W
5
THERMOSTAT OR
CONTROLLER
NOTE: ALWAYS apply
this control as instructed
in Instruction Sheet
34-00008
SYSTEM SETUP
LED
Golden Valley, MN 55422
Assembled in Mexico
Selection Tab
Trial count
ON
OFF
= 1 try (default)
Trial count
ON
OFF
= 3 tries
Trial for ign. period
ON
OFF
= 4 seconds (default)
Trial for ign. period
ON
OFF
= 7 seconds
132
4
120 VAC
NEUTRAL
VALVE
6
2
HSI
L2
4
LED States
Control Status Color Pattern
Device damaged- Red Steady
replace control
Ignition lockout Red Blink
Normal operation Green Steady
Weak flame signal Green Blink
See Instruction Sheet 34-00008
for additional states
32304204-001 Rev. A
120 VAC
See
HOT
Instructions
for
Single/Dual
Rod
L1
HSI
Applications
ORANGE
BLACK
LIMIT
CONTROLLER
®
CUS
AUTO
IGNITION
SYSTEMS
ANSI Z21.20
SENSE
ADAPTER
3
S8910U3000
FLAME
SENSOR
HOT SURFACE
IGNITER
4
L1
(HOT)
L2
1
M8528E
Fig. 2. Typical hookup when S8910U replaces White-Rodgers 50E/F47.
1134-00008EFS—01
S8910U3000
WARNING
Golden Valley, MN 55422
Assembled in Mexico
Explosion Hazard.
Can cause
serious injury or death.
Disconnect power before servicing. This device can malfunction if it gets wet. Never
try to use a device that has
been wet -- replace it.
Prepurge Time = 32 Sec.
Igniter Warm Up Time = See Inst. Sh. 34-00008
Ignition Trial Time - See Selection Tab
Number of Trials - See Selection Tab
Between Trial Time - 96 Sec.
(GND)
(GND)
(GND)
BURNER
24V
VALVE
TH-W
LED
SYSTEM SETUP
VALVE
L2
HSI
L1
HSI
SENSE
NOTE: ALWAYS apply
this control as instructed
in Instruction Sheet
34-00008
32304204-001 Rev. A
120 VAC
NEUTRAL
120 VAC
HOT
See
Instructions
for
Single/Dual
Rod
Applications
See
LED
States
®
CUS
AUTO
IGNITION
SYSTEMS
ANSI Z21.20
Selection Tab
ON
OFF
132
ON
OFF
ON
OFF
ON
OFF
Trial for ign. period
= 7 seconds
Trial for ign. period
= 4 seconds (default)
Trial count
= 3 tries
4
Trial count
= 1 try (default)
Control Status Color Pattern
Device damaged- Red Steady
replace control
Ignition lockout Red Blink
Normal operation Green Steady
Weak flame signal Green Blink
See Instruction Sheet 34-00008
for additional states
LED States
MV
MV
L1
(HOT)
L2
1
3
2
1
2
3
4
4
5
6
COMBINATION
GAS CONTROL
S8910U HOT SURFACE IGNITER CONTROL
HOT
SURFACE
IGNITER
FLAME
SENSOR
LIMIT
CONTROLLER
THERMOSTAT OR
CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MAKE SURE L1 AND L2 ARE NOT REVERSED.
ALTERNATE LIMIT CONTROLLER LOCATION.
SENSE ROD WILL BE PRESENT IF REMOTE SENSE HS780 MODEL. SEE TABLE 2.
WHEN HS780 IS A REMOTE SENSE MODEL, REMOVE JUMPER QUICK-CONNECT FROM S8910U. CUT WIRE AT CIRCUIT
BOARD AND DISCARD. CONNECT FLAME ROD LEAD WIRE TO SENSE. SEE TABLE 2.
CUT 1/4 IN. QUICK-CONNECT OFF WIRE AND REPLACE WITH 3/16 IN. QUICK-CONNECT (SUPPLIED).
USE GREEN GROUND ADAPTER (SUPPLIED) TO CONNECT S8910U GND (BURNER) TO APPLIANCE CHASSIS.
BURNER
GROUND
M8529E
5
6
4
HS780
TR (GND CLIP)
GND
—
TH
VALVE
L2
L1
IGN
IGN
RS
4
4
TERMINAL CROSS
REFERENCE
S8910U
GND(BURNER)
24V (GND)
VALVE (GND)
24V
VALVE
L2
L1
HSI
HSI
SENSE
6
34-00008EFS—0112
Fig. 3. Typical hookup when S8910U replaces Robertshaw HS780.
S8910U3000
WARNING
TERMINAL CROSS
REFERENCE
S8910U
GND(BURNER)
24V (GND)
VALVE (GND)
24V
VALVE
L2
L1
HSI
HSI
SENSE
COMBINATION
GAS CONTROL
S8910U HOT SURFACE IGNITER CONTROL
Golden Valley, MN 55422
34-00008
Assembled in Mexico
Selection Tab
ON
OFF
ON
OFF
ON
OFF
ON
OFF
132
4
VALVE
Trial count
= 1 try (default)
Trial count
= 3 tries
Trial for ign. period
= 4 seconds (default)
Trial for ign. period
= 7 seconds
120 VAC
NEUTRAL
HSI
L2
LED States
Control Status Color Pattern
Device damaged- Red Steady
replace control
Ignition lockout Red Blink
Normal operation Green Steady
Weak flame signal Green Blink
See Instruction Sheet 34-00008
for additional states
120 VAC
See
HOT
Instructions
for
Single/Dual
Rod
L1
HSI
Applications
CUS
AUTO
IGNITION
SYSTEMS
ANSI Z21.20
32304204-001 Rev. A
SENSE
®
FLAME
SENSOR
S89/S890
GND (BURNER)
24V (GND)
VALVE (GND)
24V
VALVE
L2
WARNING
Explosion Hazard.
Can cause
serious injury or death.
Disconnect power before servicing. This device can malfunction if it gets wet. Never
try to use a device that has
been wet -- replace it.
Prepurge Time = 32 Sec.
Igniter Warm Up Time = See Inst. Sh. 34-00008
Ignition Trial Time - See Selection Tab
Number of Trials - See Selection Tab
Between Trial Time - 96 Sec.
VALVE
(GND)
TH-W
NOTE: ALWAYS apply
See
LED
this control as instructed
States
SYSTEM SETUP
LED
in Instruction Sheet
L1
HSI
HSI
5
4
4
SEN
BURNER
GROUND
MV
MV
LIMIT
CONTROLLER
THERMOSTAT OR
CONTROLLER
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MAKE SURE L1 AND L2 ARE NOT REVERSED.
ALTERNATE LIMIT CONTROLLER LOCATION.
2
SENSE ROD WILL BE PRESENT IF REMOTE SENSE S89/S890 MODEL. SEE TABLE 3.
3
WHEN S89/S890 IS A REMOTE SENSE MODEL, REMOVE JUMPER QUICK-CONNECT FROM S8910U. CUT WIRE AT CIRCUIT
4
BOARD AND DISCARD. CONNECT FLAME ROD LEAD WIRE TO SENSE. SEE TABLE 3.
CUT QUICK-CONNECTS OFF WIRES AND REPLACE WITH 1/4 IN. QUICK-CONNECTS (PROVIDED).
5
2
HOT
SURFACE
IGNITER
L1
(HOT)
L2
1
3
M8530E
Fig. 4. Typical hookup when S8910U replaces Honeywell S89/S890.
STARTUP AND CHECKOUT
Check out the gas control system:
• At initial installation of the appliance.
• As part of regular maintenance procedures.
• At maintenance intervals determined by the application.
• As the first step in troubleshooting.
• Any time work is done on the system.
Determine maintenance frequency individually for each
application; see Maintenance section.
FIRE OR EXPLOSION HAZARD.
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
1. If you smell gas or suspect a gas leak, turn off gas
at the manual service valve and evacuate the
building. Do not try to light any appliance; do not
touch any electrical switch or telephone in the
building until you are sure no spilled gas remains.
2. Perform a gas leak test, as described in Steps 1
and 6 in the Startup and Checkout section, for initial
installation and any time work is done involving the
gas piping.
Step 1: Perform visual inspection.
a. With power off, make sure all wiring connections are
clean and tight.
b. Turn on the power to the appliance and the S8910U.
c. Open the manual shutoff valves in the gas line to the
appliance.
d. Test for a gas leak upstream of the gas control if the
piping has been disturbed.
GAS LEAK TEST: Paint gas control gasket edges and all pipe
connections upstream of the gas control with a rich soap and
water solution. Bubbles indicate gas leaks. Tighten the joints
and screws or replace the component to stop a gas leak.
Recheck with soap and water solution.
1334-00008EFS—01
S8910U3000
WARNING
Step 2: Verify control system ground.
The ignition module must share a common ground with the
main burner. The burner serves as the common grounding
area to assure reliable flame detection. If there is not good
metal-to-metal contact between the burner and ground, run a
lead from the burner to ground.
Step 3: Review normal operating sequence and module
specifications. See Operation and Application sections.
Step 4: Reset the ignition module.
a. Turn the thermostat or controller to the lowest setting.
b. Turn on the system power.
c. Wait one minute.
As you do Steps 5 and 6, watch for points where operation
deviates from normal. Refer to Troubleshooting section to
correct the problem.
Step 5: Check the safety lockout operation.
a. Turn off the gas supply.
b. Set the thermostat or controller above the room
temperature to call for heat.
c. Watch for igniter warmup following prepurge. Igniter
starts to glow several seconds after it is powered.
d. Time the length of time gas control is energized; measure
the time by connecting a voltmeter across the gas valve
terminals.
e. When configuring control for three ignition trials, watch for
the start of the 96-second between trial purge, followed
by a configured igniter warmup period and a second try
for ignition. After a third purge, warmup, and trial for
ignition sequence, the S8910U should lock out. The LED
displays a brief red flash. Refer to Table 6 for a complete
list of LED codes.
f. Open the manual gas control knob and make sure no gas
is flowing to the burner.
g. Set the thermostat below the room temperature and wait
one minute before continuing.
Step 6: Check normal operation.
a. Set the thermostat or the controller above the room
temperature to call for heat.
b. Observe the lightoff sequence and make sure the main
burner lights smoothly without flashback.
c. Make sure the burner operates smoothly without floating,
lifting, or flame rollout to the furnace vestibule or heat
buildup in the vestibule.
d. Test for a gas leak downstream of the gas control if the
piping has been disturbed.
f. Turn the thermostat or controller below the room
temperature. Make sure the main burner and the pilot
flames go out.
FIRE OR EXPLOSION HAZARD.
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
Improper location of the 120 Vac hot surface igniter or
any flame sensing rod can result in appliance
malfunction.
1. Never attempt to relocate the 120 Vac hot surface
igniter or the flame sensing rod from the original
position established by the appliance manufacturer.
2. Be sure the 120 Vac hot surface igniter or the flame
sensing rod is replaced in exactly the original
position after removal for inspection, service or
replacement.
CHECK BURNER FLAME CONDITION
NOISY
LIFTING
FLAME
BURNER
1/4 TO 1/2 IN. (6 TO 13 MM)
WAVING
FLAME
SMALL
BLUE
FLAME
LAZY
YELLOW
FLAME
GOOD
RECTIFYING
FLAME
3/4 TO 1 IN. (19 TO 25 MM)
CHECK FOR:
• HIGH GAS PRESSURE
• EXCESS PRIMARY AIR
OR DRAFT
CHECK FOR:
• POOR DRAFT
• EXCESS DRAFT
• HIGH VELOCITY OR
SECONDARY AIR
INSTALL SHIELD IF NECESSARY
CHECK FOR:
• CLOGGED PORTS OR
ORIFICE FILTER
• WRONG SIZE ORIFICE
CHECK FOR LACK OF
AIR FROM:
• DIRTY PRIMARY
AIR OPENING
• LARGE PORTS
OR ORIFICES
Fig. 5. Check burner flame condition.
OPERATION
M8446B
GAS LEAK TEST: Paint the gas control gasket edges and all
pipe connections downstream of the gas control with a rich
soap and water solution. Bubbles indicate a gas leak. Tighten
the joints and screws or replace the component to stop a gas
leak. Recheck with soap and water solution.
e. Check the burner flame condition. The igniter-sensor or
sensor must be constantly immersed in flame. Check the
burner flame condition as shown in Fig. 5. Do not relocate
the hot surface igniter or flame rod.
34-00008EFS—0114
The S8910U is a direct ignition control used with 120 Vac timed
warmup hot surface igniter. The control provides operating
control and shuts off all gas flow on ignition failure or loss of
main burner flame in central heat furnaces and other heating
appliances.
Module operation is in three phases—prepurge/igniter
warmup, trial for ignition and burner operation. The S8910U
provides one or three trials for ignition, depending on the DIP
switch configuration. Fig. 6 shows the normal operating
sequence.
S8910U3000
Purge/Prepurge
When the S8910U is used in a fan-assisted combustion
system, the combustion air blower starts on a call for heat from
the thermostat. On proof of airflow, the air proving switch
closes and energizes the S8910U. When the S8910U is used
in an atmospheric system, the call for heat energizes the
module.
CALL FOR HEAT (24V
TERMINAL POWERED)
INITIALIZATION CHECKS
SYSTEM WILL
NOT START
FLAME
SIMULATING
FAILURE
PREPURGE (32 SEC)
NO FLAME
SIMULATING
FAILURE
In either case, the S8910U first initiates a 32-second delay to
allow system prepurge.
Igniter Warmup
After prepurge, the S8910U energizes the igniter to start the
igniter warmup. The module energizes the hot surface igniter
for the selected warmup period; the gas control is closed
during this period.
WELDED
RELAYS
DETECTED
DEVICE LOCKED
(REPLACE CONTROL)
INTERPURGE
(64 SEC)
IGNITER WARMS UP (7
(12), 17 (27), 34 OR 45 SEC)
GAS CONTROL OPENS
FOR TIMED TRIAL
FOR IGNITION.
IGNITER OFF;
FLAME SENSING BEGINS.
FLAME
PRESENT
GAS CONTROL STAYS
OPEN (MAIN BURNER
RUNS).
CALL FOR HEAT
IS SATISFIED.
NO
FLAME
FLAME
FAILURE
GAS
CONTROL
CLOSES
ONE
TRIAL
THREE
TRIALS
HOW MANY IGNITION
TRIALS COMPLETED
THIS CALL FOR HEAT?
THREE
LOCKOUT OCCURS.
SYSTEM MUST BE
RESET.
LESS
THAN
THREE
GAS CONTROL CLOSES
(MAIN BURNER OFF).
Fig. 6. S8910U normal operating sequence.
1534-00008EFS—01
M35558
S8910U3000
WARNING
Trial for Ignition
At the end of the warmup period, the gas control opens for the
ignition trial time determined by the DIP switch configuration.
The hot surface igniter stays powered for an ignition activation
period of two seconds if the four second trial time is used or
five seconds if the seven second trial time is used. The igniter
turns off after the ignition activation period. Near the end of the
ignition trial time, the flame rectification sensing circuit
determines if the main burner flame is present. If so, the gas
control remains open and the burner operation phase begins.
Burner Operation
When the main burner is lit, a flame rectification circuit is
completed between the flame sensor (igniter on local sense
systems or flame rod on remote sense systems) and the main
burner (burner ground). The S8910U flame sensing circuit
detects the flame current and holds open the gas control. The
main flame is monitored continuously during the call for heat.
Safety Shutdown
One Trial
If flame is not sensed by the end of the timed trial for ignition,
the gas control closes and the module locks out. It must be
manually reset by removing power or setting the thermostat
below the room temperature for at least 30 seconds.
MAINTENANCE
FIRE OR EXPLOSION HAZARD.
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
Do not attempt to take apart the module or to clean it.
Improper assembly and cleaning can cause unreliable
operation.
Regular preventive maintenance is important in applications
that place a heavy load on system controls such as those used
in the commercial cooking and agricultural and industrial
industries because:
• In many such applications, particularly commercial cooking,
the equipment operates 100,000 to 200,000 cycles per
year. This heavy cycling can wear out the gas control in one
to two years.
• Exposure to water, dirt, chemicals and heat can damage the
gas control and shut down the control system. A NEMA 4
enclosure can reduce exposure to environmental contaminants.
The maintenance program should include regular checkout of
the system as outlined in the Startup and Checkout section,
and checkout of the control system as described in the
appliance manufacturer literature.
If the burner lights and flame is proved but goes out during the
run cycle, the gas control closes and the module locks out. It
must be manually reset by removing power or setting the
thermostat below the room temperature for at least 30
seconds.
Three Trial
If flame is not sensed by the end of the first timed trial for
ignition, the gas control closes and the module initiates a
second 96 seconds between trial purge cycle, followed by
igniter warmup and a second trial for ignition. If flame is not
established, the between trial purge, warmup, trial for ignition
cycle is repeated a third time. If flame is still not established
following the third trial, the gas control closes and the module
locks out. It must be manually reset by removing power or
setting the thermostat below the room temperature for at least
30 seconds.
If the burner goes out during the run cycle, the gas control
closes and the module checks for the number of ignition trials
performed during the current call for heat. If the number is less
than three, the module initiates a between trial purge, warmup
and trial for ignition. After the third trial during a single call for
heat, the module locks out. The module must be manually
reset following the lockout.
Maintenance frequency must be determined individually for
each application. Some considerations are:
• Cycling frequency. Appliances that may cycle 20,000 times
annually should be checked monthly.
• Intermittent use. Appliances that are used seasonally
should be checked before shutdown and again before the
next use.
• Consequence of unexpected shutdown. Where the cost of
an unexpected shutdown would be high, the system should
be checked more often.
• Dusty, wet, or corrosive environment. Because these
environments can cause the gas control to deteriorate more
rapidly, the system should be checked more often.
Any control should be replaced if it does not perform properly
on checkout or troubleshooting. In addition, replace any
module if it is wet or looks like it has ever been wet. Protective
enclosures, as described in the Planning the Installation
section, are recommended regardless of checkout frequency.
TROUBLESHOOTING
IMPORTANT
1. The following service procedures are provided as a
general guide. Follow the appliance manufacturer
service instructions if available.
2. Meter readings between gas control and ignition
module must be taken within the trial for ignition
period. Once the ignition module shuts off, wait for
retry or reset at the thermostat.
3. If any component does not function properly, make
sure it is correctly installed and wired before replacing
it.
34-00008EFS—0116
S8910U3000
4. The ignition module cannot be repaired. If it malfunctions, replace it.
5. Only trained, experienced service technicians should
service hot surface ignition systems.
6. After servicing, verify proper system operation.
Perform the checkout steps in the Startup and Checkout
section as the first step in troubleshooting. Then check the
troubleshooting sequence (Fig. 7) to determine the exact the
cause of the problem.
After troubleshooting, perform the checkout procedure again to
be sure the system is operating normally.
Status LED Used to Troubleshoot
The LED can be used to check the appliance status. A
description of the LED signals follows. Refer to Table 6 on
page 18 for a complete list of LED codes.
IMPORTANT
The LED displays system status for the current call for
heat. When the call for heat is interrupted (thermostat
satisfied or system power switched off), the LED goes
off and the status information is lost.
• A steady green LED indicates the normal operating mode
during a call for heat (24 V terminal is powered). The
system can be in any of the normal operating modes
including prepurge, warmup, ignition trial, between trial
purge, or normal run.
• An intermittant red flash, and two, three, or four yellow
flashes indicate a lockout mode. Refer to Table 6 for a
complete list of LED codes. The most probable cause is the
main burner failing to light or failure to detect the flame. Run
the appliance through a call for heat and if the burner does
not light, check the:
— gas supply
— input voltage
— hot surface igniter
— gas control
— wiring
If the main burner lights, but goes out at the end of ignition trial,
check the:
• Intermittant green flashes indicates the flame rectification
signal is weak. The most probable causes are:
— contaminated or mislocated igniter/sensor or flame rod
— poor flame sense leadwire insulation or connections
— poor gas pressure
If the flame rectification signal is strong when the
appliance lights, but weak while heat is being delivered, check
for overheating of the igniter/sensor, flame rod ceramic or
flame sense leadwires.
• Four yellow flashes indicate an internal error. The most
probable cause is an S8910U logic failure. Start a new call
for heat and if the four-flash signal returns wait 1 to 2 hours
and repeat the last step. If the four-flash signal returns
again, replace the S8910U.
• A steady red LED indicates a device lockout due to a
detected welded gas valve relay. Replace the control.
Ignition System Checks
Step 1: Check igniter wire harness.
Make sure:
a. Ignition cable does not run in contact with any metal
surfaces.
b. Connections to the ignition module and to the igniter or
igniter-sensor are clean and tight.
c. Ignition cable provides good electrical continuity.
Step 2: Check ignition system grounding. Nuisance shutdowns
are often caused by a poor or erratic ground.
a. A common ground is required for the module, igniter,
flame sensor and main burner.
•Check for good metal-to-metal contact between the
igniter bracket and the main burner.
•Check the ground path from the GND (BURNER)
terminal on the module to the main burner. Make sure
connections are clean and tight. If the wire is
damaged or deteriorated, replace it by following the
appliance manufacturer instructions. A temporary
leadwire connection between the GND (BURNER)
terminal and the main burner can help confirm a
ground path problem.
•Check the temperature at the igniter ceramic or flame
sensor insulator. Excessive temperature permits
leakage to ground. Contact the appliance
manufacturer if the temperature exceeds rating of
igniter or sensor.
•If flame sensor or bracket is bent out of position,
restore to the correct position.
•Replace the igniter and sensor or igniter-sensor with
an identical unit if the insulator is cracked.
Step 3: Check the flame sensing circuit.
a. Make sure the burner flame is capable of providing a
good rectification signal. See Fig. 5.
b. Make sure about 3/4 to 1 in. of the flame sensor or igniter-
sensor is continuously immersed in the flame for the best
flame signal. See Fig. 5.
c. Check for excessive (above 1000 °F [538 °C])
temperature at the ceramic insulator on the flame sensor.
Excessive temperature can cause a short to ground.
d. Check for cracked igniter-sensor or sensor ceramic
insulator, which can cause short to ground, and replace
unit if necessary.
•Make sure electrical connections are clean and tight.
Replace damaged wire with moisture-resistant No. 18
wire rated for continuous duty up to 221 °F (105 °C).
e. If the igniter is other than a Norton 201 or 271, make sure
it meets the following specifications:
•Igniter must reach 1832 °F (1000 °C) within the
selected warm up time of 7, 17, 34 or 45 seconds
with 102 Vac applied.
•Igniter must maintain at least 500M ohm insulation
resistance between the igniter leadwires and the
igniter mounting bracket.
•Igniter must not develop an insulating layer on its
surface (over time) that would prevent flame sensing.
•Igniter surface area immersed in flame must not
exceed one-fourth of the grounded area immersed in
flame. This would prevent flame sensing.
•Igniter current draw at 132 Vac must not exceed 5 A.
1734-00008EFS—01
S8910U3000
RedSteadyDevice locked - detected welded gas valve relay. Replace control
RedIntermittent blinkHard lockout - exceeded maximum number of retries
YellowSteadySoft lockout - gas valve failure or 8 consecutive recoverable lockouts:
Yellow1Flame detected out of sequence.
Yellow2Recoverable lockout - Low input voltage detected.
Yellow3Recoverable lockout - AC line frequency out of acceptable range.
Yellow4Recoverable lockout - Internal error.
GreenSteadyNormal sequence and operation.
GreenIntermittent blinkNormal sequence and operation, weak flame detected.
Table 6. LED codes.
ColorFlash CodeStatus
the unit will wait 1 hour before next ignition attempt.
34-00008EFS—0118
CONFIRM THAT 120V HOT LEAD
CONNECTS TO L1, AND 120V NEUTRAL
LEAD CONNECTS TO L2.
M8531B
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
START
TURN THERMOSTAT TO
CALL FOR HEAT
DOES S8910U GET POWER
(24 VAC NOMINAL)?
30 SECOND MINIMUM
PURGE
IGNITER WARMS UP AND
GLOWS RED
REPEAT PROCEDURE UNTIL TROUBLE-FREE OPERATION IS OBTAINED.
SYSTEM RUNS UNTIL CALL
FOR HEAT ENDS
CALL FOR HEAT ENDS,
SYSTEM SHUTS OFF
TROUBLESHOOTING ENDS
••CHECK FOR PROPER TEMPERATURE CONTROLLER OPERATION.
REMOVE VALVE LEAD AT S8910U; IF VALVE CLOSES, RECHECK TEMPERATURE CONTROLLER
AND WIRING; IF NOT, REPLACE GAS CONTROL.
NOTE: IF S8910U GOES INTO LOCKOUT, RESET SYSTEM.
CHECK CONTINUITY OF GROUND WIRE.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS CAN OCCUR OCCASIONALLY
EVEN THOUGH OPERATION IS NORMAL AT THE TIME OF CHECKOUT.
CHECK FOR EXCESSIVE HEAT AT IGNITER OR FLAME ROD CERAMIC BASE
(TEMPERATURE ABOVE 1000F (538C) CAUSES SHORT TO GROUND).
IF CHECKS ARE OKAY, REPLACE S8910U MODULE.
NOTE: SYSTEM FAILURE DURING A RUN CYCLE HAS A LOW PROBABILITY OF
BEING THE S8910U.
•
•
•
MAIN BURNER REMAINS
POWERED AND LIT
MAIN BURNER LIGHTS
CHECK FOR 120 VAC ACROSS HOT
SURFACE IGNITER TERMINALS.
NOTE: IF S8910U GOES INTO LOCKOUT, RESET SYSTEM.
CHECK CONTINUITY OF GROUND WIRE AND GROUND PATH FROM MAIN BURNER TO
GND (BURNER) TERMINAL OF S8910U.
CONFIRM THAT 120 VAC HOT LEAD IS CONNECTED TO L1 AND 120 VAC NEUTRAL LEAD
IS CONNECTED TO L2.
CHECK THAT BURNER FLAME COVERS IGNITER/SENSOR OR SENSOR.
CHECK INSULATION ON IGNITER/SENSOR LEADS.
CHECK IGNITER/SENSOR OR FLAME ROD FOR CONTAMINATION OR DAMAGE. REPLACE,
IF NECESSARY.
CHECK INSULATION ON SENSOR LEADS AND CHECK SENSOR POSITION.
IF CHECKS ARE OK, REPLACE S8910U MODULE.
NOTE: SYSTEM FAILURE AFTER MAIN FLAME LIGHTS HAS A LOW PROBABILITY
OF BEING THE S8910U.
•
•
•
•
•
•
CHECK FOR 24 VAC ACROSS VALVE TERMINALS ON S8910U DURING TRIAL FOR IGNITION
TIMING. IF NO VOLTAGE, REPLACE S8910U.
CHECK ELECTRICAL CONNECTIONS BETWEEN S8910U AND GAS CONTROL.
IF OK, REPLACE GAS CONTROL.
CHECK IGNITER POSITION.
CHECK GAS PRESSURE TO MAIN BURNER.
•
•
•
•
REPLACE S8910U.
CHECK AND CORRECT WIRING FUSE
OR CIRCUIT BREAKER.
CHECK WIRES TO IGNITER.
IF OK, REPLACE IGNITER.
CHECK AIR PROVING SWITCH.
REPLACE S8910U.
•
•
CHECK LINE VOLTAGE POWER.
CHECK LOW VOLTAGE TRANSFORMER.
CHECK LIMIT CONTROLLER.
CHECK AIR PROVING SWITCH (IF USED).
CHECK THERMOSTAT.
CHECK WIRING.
•
•
•
•
•
•
NOTE: BEFORE TROUBLESHOOTING, BECOME FAMILIAR WITH STARTUP
AND CHECKOUT PROCEDURES.
S8910U3000
Fig. 7. S8910U troubleshooting sequence.
1934-00008EFS—01
S8910U3000
Flame Current Measurement
Flame current of the device can be meaured using a standard
micro-ammeter by simply inserting the meter probes into the
holes labeled FLAME CURRENT, as shown in Fig. 8.
— Flame current must be measured with valve lit.
— Set meter to DC μAmp scale.
— Ensure meter leads are positioned correctly [+/-].
S8910U HOT SURFACE IGNITER CONTROL
Golden Valley, MN 55422
NOTE: ALWAYS apply
this control as instructed
in Instruction Sheet
34-00008
SYSTEM SETUP
Assembled in Mexico
Selection Tab
ON
OFF
ON
OFF
ON
OFF
ON
OFF
132
4
VALVE
Trial count
= 1 try (default)
Trial count
= 3 tries
Trial for ign. period
= 4 seconds (default)
Trial for ign. period
= 7 seconds
120 VAC
NEUTRAL
L2
LED States
Control Status Color Pattern
Device damaged- Red Steady
replace control
Ignition lockout Red Blink
Normal operation Green Steady
Weak flame signal Green Blink
See Instruction Sheet 34-00008
for additional states
120 VAC
HOT
HSI
L1
WARNING
Can cause
Explosion Hazard.
serious injury or death.
Disconnect power before servicing. This device can malfunction if it gets wet. Never
try to use a device that has
been wet -- replace it.
Prepurge Time = 32 Sec.
Igniter Warm Up Time = See Inst. Sh. 34-00008
Ignition Trial Time - See Selection Tab
Number of Trials - See Selection Tab
Between Trial Time - 96 Sec.
See
LED
States
VALVE
(GND)
(GND)
TH-W
LED
Recommended Minimum Flame Current:
• Must read steady 1 μAmp DC minimum.
• Flame current should be 2 μAmp or greater for reliable
appliance operation.
®
CUS
AUTO
IGNITION
SYSTEMS
ANSI Z21.20
32304204-001 Rev. A
HSI
See
Instructions
Single/Dual
Rod
Applications
for
SENSE
002.3
DC
µA
Fig. 8. Measuring flame current with micro-ammeter.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
L'installation de ce produit doit être réalisée par un technicien
d'entretien formé et qualifié.
APPLICATION
Le module d'allumage par incandescence universel S8910U
est conçu pour remplacer facilement un vaste éventail de
modules d'allumage par incandescence fabriqués par
Honeywell, Robertshaw et White-Rodgers. Le module
S8910U contrôle le fonctionnement d'un système à allumage
direct faisant appel à un allumeur par incandescence de 120
V c.a. Le modèle S8910U remplace les modules d’allumage à
veilleuse intermittente et redressement de flamme existants
par les caractéristiques suivantes :
• Éléments d'allumage par incandescence à réchauffage
temporisé 120 V c.a. (jusqu'à 5 A).
• Allumage par incandescence à électrode unique (détection
locale) ou à deux électrodes (détection à distance).
• Un ou trois essais d'allumage par appel de chaleur.
• Essais d'allumage de quatre secondes ou sept secondes.
• Prébalayage de 32 secondes ou moins.
• Durées de balayage entre essais jusqu'à 96 secondes
(mode trois essais uniquement).
• Gaz naturel ou GPL.
Le modèle S8910U n'est pas destiné à remplacer les
systèmes suivants :
• Modules d'allumage à veilleuse intermittente.
• Modules d'allumage à étincelles direct.
• Modules d'allumage par incandescence 120 V c.a. avec
vérification.
• Modules d'allumage par incandescence avec élément
24 V c.a.
• Modules d'allumage par incandescence entrée 240 V c.a./
avec élément. 120 V c.a.
• Modules d'allumage par incandescence 120 V c.a. à
réchauffage temporisé de 120 V c.a
— Temps d'essai d'allumage inférieur à quatre secondes.
—
Temps d'essai d'allumage supérieur à douze secondes
— Connecteurs plats au lieu de connecteurs rapides
mâles.
Le système S8910U contient le contrôleur S8910U, un mode
d'emploi simple et les accessoires requis pour assurer la
compatibilité avec le module d'allumage par incandescence
existant. Le sac des accessoires comprend un adaptateur
White-Rodgers, un fil de terre Robertshaw, quatre
connecteurs rapides 0,032 femelles 1/4 po, un connecteur
rapide 0,032 femelle 3/16 po et neuf étiquettes de câblage.
Les étiquettes de câblage sont incluses pour permettre un
marquage adéquat des fils attachés au module existant.
Une liste complète des modules Honeywell et d’autres
marques pouvant être remplacés par le modèle S8910U est
fournie dans les Tableaux 1 à 3.
REMARQUE :Le modèle S8910U est destiné à remplacer
Caractéristiques électriques :
Tension du contrôleur : 24 V, 60 Hz.
Intensité maximale des contacts de vanne : 2 A.
Appel de courant : 0,4 A plus charge de la vanne.
Tension de l'allumeur par incandescence : 120 V c.a., 60 Hz.
Tension nominale des contacts à 120 V c.a.: 5 A.
IMPORTANT
Le modèle S8910U est conçu pour les applications de
60 Hz. Les temporisations varient de 20 % pour les applications de 50 Hz.
Allumeur par incandescence ou allumeur-capteur :
.
Modèle Norton 201 ou 271 ou équivalent.
REMARQUE : Si un allumeur autre que le modèle Norton
les contrôleurs d'allumage défectueux
uniquement. Le technicien d'entretien doit
s'assurer que les autres composants de
l'appareil et du système de contrôle
fonctionnent correctement et de manière
fiable avant de remplacer le contrôleur
d'allumage.
RISQUE D’EXPLOSION. PEUT CAUSER DES
BLESSURES ET DES DOMMAGES MATÉRIELS.
Le modèle S8910U ne peut être utilisé que pour un
remplacement direct. Consulter les Tableaux 1 à 3
avant de remplacer un module par incandescence
existant par le modèle S8910U. Si le module existant
n'est pas répertorié, ne pas utiliser le modèle S8910U
pour le remplacer. Toujours consulter le tableau des
correspondances pour assurer un réglage correct des
commutateurs DIP.
201 ou 271 est utilisé, il doit être conforme
aux caractéristiques minimales suivantes
requises pour toute la durée d'utilisation de
l'allumeur
• L'allumeur doit atteindre 1000 °C (1832 °F)
dans la période de réchauffage sélectionnée
de 7, 17, 34 ou 45 secondes à 102 V c.a.
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.