S8701 and S8702 Direct Spark Ignition Controls are
designed for use in commercial cooking and other gas
heating applications which require direct ignition and flame
safety control of gas burners. S8701/S8702 controls are
used to ignite the main burner(s), sense the flame and
control the gas valve in these applications, see Table 1.
Table 1. S8701/S8702 Models.
ModelFlame SenseTrials for IgnitionSpark/SensePrepurge
S8701Dremote 11No
S8702Dremote12No
S8702Fremote3
S8702Kremote12Yes
S8702Mremote3
a
S8702 F and M models include an auto-reset from lockout after 1 hour.
Planning the Installation
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury,
or death.
Follow these warnings exactly:
1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in
the Maintenance section.
Review the following conditions that can apply to your
specific installation and take the precautionary steps
suggested.
Frequent Cycling
This control is designed for use on commercial cooking
appliances that typically cycle 400 times a day, year round.
Perform a monthly checkout.
Water or Steam Cleaning
If a control gets wet, replace it. If the appliance is likely to
be cleaned with water or steam, protect (cover) the control
and wiring from water or steam flow. Mount the control
high enough above the floor so it does not get wet during
normal cleaning procedures.
The S8701 is a single spark, single flame sense, direct
ignition control that is compatible with dual rod systems.
The S8702 is a dual spark, dual flame sense, direct
ignition control capable of igniting and sensing flame on
two separate gas burners that are fed by a single gas
valve. The S8702 is compatible with dual rod systems
only.
a
a
High Humidity or Dripping Water
Dripping water can cause the control to fail. Never install
an appliance where water can drip on the control. In
addition, high ambient humidity can cause the control to
corrode and fail. If the appliance is in a humid atmosphere,
make sure air circulation around the control is adequate to
prevent condensation. Also, regularly check out the
system.
IMPORTANT
Always install a splash cover to protect the
control from water damage.
Corrosive Chemicals
Corrosive chemicals can attack the control, eventually
causing a failure. If chemicals are used for routine
cleaning, avoid contact with the control. Where chemicals
are suspended in air, as in some industrial or agricultural
applications, protect the control with an enclosure.
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause the
control to malfunction. Where dust or grease can be a
problem, provide covers for the control to limit contamination.
Excessively high temperatures can damage the control.
Make sure the maximum ambient temperature at the
control does not exceed the rating of the control, see Table
2. If the appliance operates at very high temperatures, use
insulation, shielding, and air circulation, as necessary, to
protect the control. Proper insulation or shielding should be
provided by the appliance manufacturer; verify proper air
circulation is maintained when the appliance is installed.
Table 2. S8701/S8702 Ambient Temperature Ratings.
OperationAmbient Temperature
50 Hz-40°F to 160°F
60 Hz-40°F to 175°F
Table 3. System Requirements.
Model
S8701/
S8702
a
Valve used must be designed for DSI application.
b
Separate spark igniter and flame sensor mounted on a
common bracket.
No.
Spark
Igniter
Flame
Sensor
Q347AQ354A
b
Q366
Valve Required
Honeywell VR8205
gas valves or
equivalent
a
INSTALLA TION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure it is suitable for your
application.
3. The installer must be a trained, experienced service
technician.
4. After installation is complete, check out system
operation.
IMPORTANT
If this is a replacement application, follow the
appliance manufacturer’s instructions, if available. The manufacturer usually provides wiring
diagrams, start-up and checkout instructions and
the service procedures for their system. If the
manufacturer’s instructions are not available, this
information may be used as a general guide.
Mounting The S8701/S8702 Control
Select a location within 6 ft (1.8m) of the burner that will
permit a direct cable route to the spark igniter terminal.
Ready access to the terminals is necessary for wiring and
servicing. The S8701/S8702 control may be mounted in
any position. Use No. 6-32 machine screws or No. 8
sheetmetal screws 1 inch long for fastening. Fasten
securely. Do not exceed the ambient temperature rating
given in Table 2.
13/16 (21)
2
(50)
1-1/8
(29)
2-13/16 (72)
3-15/16 (100)
3-3/8 (86)
5/17 (7)
3-3/8
(86)
5-3/16
(130)
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
If a new gas control is to be installed, turn off gas
supply before starting installation.
Be sure to conduct a gas leak test after the control
is installed.
CA UTION
Electric Shock Hazard.
Can cause personal injury or equipment
damage.
Disconnect power supply before wiring.
69-1174
7/8 (23)
3/16 (4)
M16233
Fig. 1. S8701/S8702 Dimensions.
Mounting Auxiliary Controls
Mount the spark igniter, flame sensor, temperature control,
transformer, gas control and any other auxiliary controls
according to the manufacturer’s instructions.
NOTE: The S8701 and S8702 installations require a 24V
transformer rated to handle both the S8701/
S8702 current and the gas valve current. Table 4
shows the transformer rating necessary for
various loads.
2
S8701/S8702 DIRECT SPARK IGNITION CONTROLS
Table 4. Transformer Ratings for S8701/S8702 and
Dual Valve Combination Gas Controls.
Minimum VA
Rating (24V
transformer)
Total Valve
Current
(in amperes)
S8701/S8702
(in amperes)
20up to 0.60.15
300.6 to 1.00.15
401.0 to 1.40.15
551.4 to 2.00.15
Wiring
General Precautions
1. Check the wiring diagram furnished by the
heating appliance manufacturer, if available, for
circuits different from the ones shown. Carefully
follow any special instructions affecting the general
procedures outlined below.
2. All wiring must comply with applicable electrical
codes and ordinances.
3. Disconnect the power supply before wiring to
prevent electrical shock or equipment damage.
4. If installing a separate Q345A flame sensor, the
sensor leadwire should be kept as short as possible
and should not be allowed to rest against grounded
metal surfaces.
5. A common ground is required for the S8701/S8702,
the spark igniter and the main burner. The 24V
(GND) terminal does not internally ground the
transformer. The 24 V (GND) terminal must be
grounded to the equipment chassis separately. Any
auxiliary controls or limits must not be in the
grounded leg.
6. Ignition cable should not touch any metal surface or
current carrying wires. It must not be more than 6 ft
(1.8m) long.
7. Do not short valve terminals as this may damage the
temperature controller, the transformer or the
S8701/S8702.
Table 5. Recommended Ignition Cable.
Temperature
RMS
Cable Type
Voltage Rating
UL Style 325710,000482250
Rating
°F°C
Wiring the S8701/S8702 Control
1. Connect system components to the S8701/S8702
terminals as shown in the wiring diagrams, Figs. 2
and 3. Refer to the appliance manufacturer’s
instructions for wiring any other auxiliary controls.
2. Adjust temperature control heat anticipator to match
system current draw. The current draw equals the
total current required for the S8701 or S8702
(0.15A) plus the gas valve and all other 24 V control
loads (vent dampers, prepurge relays, etc.). Gas
valve must be designed for the DSI application.
NOTE: Use only recommended ignition cable (see
Table 5) to connect the S8701/S8702 with the
spark igniter. Cable must not run in continuous
contact with a metal surface or spark voltage
will be greatly reduced; use ceramic standoff
brackets if necessary. Cable length must not
exceed 6 ft (1.8m).
2
S8701D CONTROL MODULE
GND
VALVE (GND)
24 Vac (GND)
24 Vac
BURNER
TEMPERATURE
CONTOLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
3
MAXIMUM IGNITER-SENSOR CABLE LENGTH: 6 FT. (1.8 M) OR LESS.
TRANSFORMER
FLAME
SENSE
ALARM
VALVE
(GND)
SPARK
3
LIMIT CONTROLLER
Q347
SPARK
IGNITER
IGNITER AND
BURNER GROUND
L1
(HOT)
L2
ALARM, IF USED
ANY COMBINATION
GAS CONTROL
2.0A MAX.
Q354 FLAME
SENSOR
BURNER
Fig. 2. S8701 Wiring Diagram.
1
M16232A
3
69-1174
S8701/S8702 DIRECT SPARK IGNITION CONTROLS
TRANSFORMER
ALARM
VALVE
(GND)
3
Q354 FLAME
SENSOR
LIMIT CONTROLLER
ALARM, IF USED
ANY COMBINATION
GAS CONTROL
2.0A MAX.
Q347
SPARK
IGNITER
BURNER
IGNITER AND
BURNER GROUND
L1
(HOT)
L2
1
Q354 FLAME
SENSOR
M16267A
2
S8702D CONTROL MODULE
SENSE 2
SENSE 1
GND
VALVE (GND)
24 Vac (GND)
24 Vac
BURNER
SPARK 2
SPARK 1
TEMPERATURE
CONTOLLER
3
Q347 SPARK
IGNITER
BURNER
IGNITER AND
1
2
3
BURNER GROUND
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM IGNITER-SENSOR CABLE LENGTH: 6 FT. (1.8 M) OR LESS.
Fig. 3. S8702 Wiring Diagram.
Grounding the S8701/S8702 Spark Igniter and
Main Burner
For the system to operate properly, spark igniter, flame
sensor bracket, the burner (GND) terminal on the 24V
(GND) terminal, and the S8701/S8702 control must share
a common ground with the main burner. Use thermoplastic
insulated wire with a minimum rating of 105°C (221°F) for
the ground wire; asbestos insulation is not acceptable. If
necessary, use a shield to protect the wire from radiant
heat generated by the burner.
IMPORTANT
Use moisture resistant 18 AWG wire rated for
continuous duty up to 105
tions must be clean and tight.
Connect the ground wire as follows:
1. Fit one end of the ground wire with a female 1/4 in.
quick-connect terminal and connect it to the male
quick connect GND (Burner) terminal on the S8701/
S8702 control.
2. Strip the other end of the GND (Burner) wire and
fasten it under the igniter bracket mounting screw. If
necessary, use a shield to protect the wire from
radiant heat. The burner serves as the common
grounding area.
°
C (221°F). Connec-
3. Fit one end of another ground wire with a female 1/4
in. quick connect terminal and connect it to the male
quick connect 24V (GND) terminal on the S8701/
S8702 control.
4. Strip the other end of the 24V (GND) wire and fasten
it to the burner ground.
5. If used with a separate flame sensor, make sure the
bracket is connected to the burner ground.
NOTE: It is not necessary that the burner is earth
grounded.
ST ARTUP AND CHECKOUT
The following start-up and checkout procedures are basic
to all S8701 and S8702 control modules. If this is a
replacement application, refer to the specific instructions
provided by the heating appliance manufacturer (if
available). Also, since the auxiliary controls used on any
DSI system may differ, refer to the manufacturer’s
instructions for start-up and checkout procedures for other
system components.
NOTE: If one of the system components fail, the S8701/
S8702 will either not operate or it will go into
safety lockout (depending on the type of failure).
If the system does not perform as outlined in
Start System and Check Trial for Ignition steps
below, refer to the SERVICE section to determine the cause.
Gas Leak Test
If the gas control has been replaced as a part of the S8701
or S8702 installation, perform the following test for gas
leaks.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
To avoid possible explosion or fire, perform Gas
Leak Test.
With the main burner in operation, paint the pipe joints and
valve gasket with a rich soap and water solution. Bubbles
indicate a gas leak. To stop leak, tighten joints and screws or
replace the gasket. Never use a flame to check for gas leaks.
START SYSTEM
1. Turn on the power and the gas supply.
Set the temperature control to request heat and
watch for a spark at the igniter (S8701D, S8702D
models have no delay on start-up. S8702K and M
models have a predetermined delay on start-up for
prepurge.). Time the length of the spark operation; it
must be within the Trial for Ignition (TFI) timing
period (see Table 6).
2. Check that the system starts as follows: Spark turns
on, gas valve opens at once, and burner ignites after
gas reaches main burner. Once burner flame is
established, spark igniter cuts off. For S8702
models; flame must be established on both burners
for spark igniters to turn off.
69-1174
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.