Honeywell R4184D, R8184G, R8184M, R8184N, R8184P Installation Manual

Page 1
R4184D; R8184G,M,N,P
Protectorelay
®
Oil Primary Controls
INSTALLATION INSTRUCTIONS
The intermittent ignition R4184D and R8184G,M,N,P Oil Primary Controls operate the oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat from the thermostat.
The R8184M also provides automatic, nonrecycling control of cooling systems and low voltage thermostat.
The R8184P provides 15-second valve on delay and selectable 0-, 2-, 4-, 6-minute blower off delay for hydronic and warm air systems. Select models have 30-minute blower off delay timing.
All models use the C554A Cadmium Sulfide (cad cell) Flame Detector to monitor the burner flame and shut down the system on ignition failure or on flame failure during the run cycle. A manual reset button is provided to reset the safety switch after lockout. Clock thermostats (not available on R8184P) that power the clock through the primary control transformer lose time during lockout unless backup batteries are installed.
All models (except the R8184G1310 and R8184G1328) are Underwriters Laboratories Inc. component recognized and meet flammability test requirements for a final enclosure.
NOTE: R8184P is intended for use on oil burning
appliances that do not require a safety rated prepurge and postpurge function as defined in UL 296. The valve on delay and blower off delay in this control are only intended to help establish draft and reduce oil after drip-related problems.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow instructions can damage the product or cause a hazardous condition.
2. Check ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Make sure the installer is a trained, experienced service technician.
4. After completing the installation, use these instruc­tions to check out the product operation.
CAUTION
1. Disconnect the power supply before beginning installation to prevent electrical shock or equipment damage.
2. Be sure the combustion chamber is free of oil or oil vapor before starting the system.
Location
Mount on a 4 x 4 junction box, directly on the main
burner housing or inside the appliance cabinet. See Fig. 1.
Be sure that operating temperatures are between
-40°F and +130°F (-40°C and +54°C). Select R8184G,P models have a maximum temperature of 150°F (66°C), but must be mounted parallel to the ground to achieve 150°F (66°C). See Fig. 2.
RED RESET BUTTON
2
CAD CELL LEADS
LINE VOLTAGE LEADS
STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.
1
T-T TERMINALS ON R8184G; T1-T2 TERMINALS ON R8184N.
2
3
ATTACH WITH NO. 8 MOUNTING SCREWS (OBTAINED LOCALLY).
Fig. 1. Wire and mount 130°F (54°C) maximum ambient
temperature oil primary control.
MOUNTING SCREW HOLE
HOLE OR KNOCKOUT FOR CAD CELL LEADS
LOW VOLTAGE TERMINAL STRIP
2
4 x 4 JUNCTION BOX
1
M1643C
® U.S. Registered Trademark Copyright © 1996 Honeywell Inc. • All Rights Reserved
X-XX UL
69-0618-3
Page 2
R4184D; R8184G,M,N,P Protectorelay ® OIL PRIMARY CONTROLS
VENTILATION
3
SLOTS
RED RESET BUTTON
2
CAD CELL LEADS
LINE VOLTAGE LEADS
STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.
1
ATTACH WITH NO. 8 MOUNTING SCREWS (OBTAINED LOCALLY).
2
3
VENTILATION SLOTS ONLY AVAILABLE ON SELECT MODELS.
Fig. 2. Wire and mount 150°F (66°C) maximum ambient
Line Voltage Wiring Connections
Wiring must comply with all local codes and ordinances.
IMPORTANT
temperature oil primary control.
Be sure all line voltage connections are in a wiring
enclosure such as a junction box or the appliance wiring compartment.
Make the line voltage connections as shown in Fig. 3
through 9.
Splice the leads with solderless connectors.
Do not exceed the load ratings listed in Table 1.
Thread the line voltage cad cell leads through the
hole on the bottom of the low voltage terminal strip. See Fig. 1 or 2.
MOUNTING SCREW HOLE
HOLE OR KNOCKOUT FOR CAD CELL LEADS
LOW VOLTAGE TERMINAL STRIP
4 x 4 JUNCTION BOX
1
M1642C
Table 1. Load relay contact ratings.
120 Vac 240 Vac
Model AFL ALR AFL ALR
R4184D; R8184G,M,N (45-second models)
R8184P (15-, 30-, 45-second models)
R8184G (15- and 30-second models)
7.4A 44.4A 3.7A 22.2A
7.4A 44.4A NA NA
10.0A 60.6A 5.0A 30.0A
Alarm Contact Rating: 25 VA at 24V, 50/60 Hz.
Mounting
If necessary, use the control as a template to mark
and drill new mounting holes.
Mount the control using no. 8 screws (obtained
locally).
Low Voltage Wiring Connections
After mounting, make low voltage connections to screw terminals as follows:
• R4184D—connect the cad cell leads to the F-F terminals. See Fig. 3.
• R8184G—connect the cad cell leads to the F-F terminals and thermostat leads to the T-T terminals. See Fig. 4 and 5.
• R8184M—connect the cad cell leads to the F-F terminals and connect remaining low voltage wiring as shown in Fig. 6.
NOTE: The Y and G terminals are
to the internal circuitry of the R8184M. The Y and G terminals are provided to simplify the connections of the cooling equipment.
• R8184N—connect the cad cell leads to the F1-F terminals and thermostat leads to the T1-T2 terminals. See Fig. 7.
• R8184P hydronic hookup. Connect the cad cell leads to the F-F terminals. See Fig. 8.
• R8184P warm air hookup. Connect the card cell leads to the F-F terminals and the thermostat leads to the R-W terminals. See Fig. 9.
not
connected
2
69-0618—3
R4184D PROTECTORELAY CONTROL
1K
R1
CAD CELL
R2
F
F
SAFETY SWITCH
BILATERAL SWITCH
CAPACITOR
®
SAFETY SWITCH HEATER
TRIAC
1K1
1K2
Fig. 3. Typical hookup for R4184D.
2
JUNCTION BOX
BLACK
ORANGE
WHITE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
THERMOSTAT
LIMIT
BURNER MOTOR
OIL VALVE (OPTIONAL)
IGNITION
(HOT)
1
L1
L2
M715A
Page 3
R4184D; R8184G,M,N,P Protectorelay ® OIL PRIMARY CONTROLS
R8184G PROTECTORELAY® CONTROL
T
T
R1
CAD CELL
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CAD CELL
R2
F
F
R8184G PROTECTORELAY® CONTROL
T
T
R1
F
F
2
1K
2
1K
R2
SAFETY SWITCH
BILATERAL SWITCH
CAPACITOR
SAFETY SWITCH
BILATERAL SWITCH
CAPACITOR
JUNCTION BOXTHERMOSTAT
BLACK
SAFETY SWITCH HEATER
TRIAC
1K1
2
TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER.
1K2
ORANGE
WHITE
BURNER MOTOR
OIL VALVE (OPTIONAL)
IGNITION
Fig. 4. Typical hookup for R8184G.
JUNCTION BOXTHERMOSTAT
BLACK
SAFETY SWITCH HEATER
TRIAC
1K1
SAFETY SWITCH
1K2
ORANGE
WHITE
RED
RED
OIL VALVE (OPTIONAL)
TO REMOTE ALARM CIRCUIT
BURNER MOTOR
IGNITION
LIMIT
LIMIT
LINE VOLTAGE THERMOSTAT
(HOT)
LINE VOLTAGE THERMOSTAT
(HOT)
2
L1
1
L2
M716A
2
L1
1
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT
2
IN SERIES WITH LIMIT CONTROLLER.
Fig. 5. Typical hookup for R8184G with dry contacts for remote alarm.
3
M5172A
69-0618—3
Page 4
R4184D; R8184G,M,N,P Protectorelay ® OIL PRIMARY CONTROLS
CAD CELL
R8184M PROTECTORELAY CONTROL
F
CAD CELL
R8184N PROTECTORELAY CONTROL
T1
T2
R1
F1
F2
2
1K
R2
R1
®
SAFETY SWITCH HEATER
R2
BILATERAL SWITCH
CAPACITOR
SAFETY SWITCH
BILATERAL SWITCH
CAPACITOR
COOLING CONTACTOR
K1
SS
FAN RELAY
WCRYFG
1K1
TRIAC
(T)(T)
R4
1
BROWN BLUE
RED
Fig. 6. Typical hookup for R8184M.
®
SAFETY SWITCH HEATER
TRIAC
1K1
THERMOSTAT
RWY
BLACK
1K2
1K2
BLACK
ORANGE
WHITE
G
JUNCTION BOX
WHITE
ORANGE
BLACK
USED FOR 4 AMP THERMOSTAT ONLY.
1
JUNCTION BOXTHERMOSTAT
LIMIT
BURNER MOTOR
OIL VALVE (OPTIONAL)
IGNITION
BURNER
OIL VALVE
IGNITION
LIMIT
LINE VOLTAGE THERMOSTAT
(HOT)
L1
L2
(HOT)
M1560A
2
L2
L1
1
69-0618—3
.4064T HEATER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TO USE R8184N WITH LINE VOLTAGE CONTROLLER, JUMPER T1-T2 TERMINALS AND CONNECT
2
LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER.
Fig. 7. Typical hookup for R8184N.
4
M717A
Page 5
R4184D; R8184G,M,N,P Protectorelay ® OIL PRIMARY CONTROLS
(HOT)
1
L2
(LINE)
LIMIT
3
BLACK
CAD CELL
RED
VIOLET
WHITE
ORANGE
2
4
R8184P PROTECTORELAY® HYDRONIC CONTROL
F
RC
F
Y
R
G
W
C
M10022
L1
(HOT)
AQUASTAT®
1
CONTROLLER
3
OIL
AIR FLOW
VALVE
SWITCH
L2
(LINE)
BURNER
MOTOR
IGNITION
TRANSFORMER
VENTER
MOTOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2 IGNITION TRANSFORMER CAN BE CONNECTED TO VALVE OR
BURNER MOTOR.
3 OMIT ON SYSTEMS WITHOUT POWER VENTING.
4 JUMPER R-W.
Fig. 8. Typical hydronic hookup for R8184P.
L1
LIMIT
3
AIR FLOW
OIL
BURNER
MOTOR
IGNITION
TRANSFORMER
VENTER
MOTOR
SWITCH
2
3
VALVE
BLACK
RED
VIOLET
WHITE
ORANGE
NOTE: USE COPPER CONDUCTORS ONLY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2 IGNITION TRANSFORMER CAN BE CONNECTED TO VALVE OR BURNER MOTOR.
3 OMIT ON SYSTEMS WITHOUT POWER VENTING.
CAD CELL
R8184P PROTECTORELAY® WARM AIR CONTROL
RC
F
F
Y
R
G
W
C
TRANSFORMER
CONTACTOR
FAN RELAY
THERMOSTAT
COOLING
COOLING
M10021
Fig 9. Typical warm air hookup for R8184P.
5
69-0618—3
Page 6
R4184D; R8184G,M,N,P Protectorelay ® OIL PRIMARY CONTROLS
CHECKOUT
Start System
WARNING
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH
Be sure the combustion chamber is free of oil or oil vapor before starting the system.
Push in and release the red reset button.Open the hand valve in the oil supply line.Make sure the system is powered. Check the circuit
breaker or fuse and close the system switch, if provided.
NOTE: If the safety switch has just locked out, the
safety switch may need a minute to cool down before it can be reset.
Set thermostat to call for heat.Burner should light and operate until a call for heat
ends.
Check Safety Features
Simulate flame failure:
Follow the starting procedure to turn on the burner.Close the hand valve in the oil supply line.Safety switch should lock out in safety switch timing
indicated on the label (15, 30 or 45 seconds). Alarm switch contacts close to initiate alarm on models with remote dry contacts. Ignition and motor should stop and oil valve should close.
Push red reset button to reset safety switch.
Simulate ignition failure:
Follow the starting procedure to turn on the burner,
but do not open the oil supply hand valve.
Safety switch should lock out in safety switch timing
indicated on the label. Alarm switch contacts close to initiate alarm on models with remote dry contacts. Ignition and motor should stop and oil valve should close.
Push the red reset button to reset the safety switch.
Simulate power failure:
Follow the starting procedure to turn on the burner.With the burner running, turn off the power to the
system by tripping the circuit breaker or removing the fuse.
Burner should stop.Restore power. Burner should start.
If system does not operate as described, go to the TROUBLESHOOTING AND MAINTENANCE section.
TROUBLESHOOTING AND MAINTENANCE
IMPORTANT
1. Only a trained, experienced service technician should perform the troubleshooting procedure.
2. This control contains no field-replaceable parts. Do not attempt to take it apart. Replace the entire control if operation is not as described.
Preliminary Steps
Check the wiring connections and power supply.
Make sure power is on to the controls, burner motor and ignition transformer.
Make sure the limit control is closed.
Check Oil Primary Relay
NOTE: You will need an insulated jumper wire with both
ends stripped.
Disconnect cad cell leads from F-F or F1-F
terminals.
Reset the safety switch and set the thermostat to
call for heat. Burner should start.
Within the safety switch timing, use insulated wire to
jumper F-F or F1-F2 terminals. Burner should continue to run.
After the safety switch timing, remove the jumper.
Burner should shut down in the safety switch timing.
If the operation is not as described, replace the oil
primary control.
Check Cad Cell
Disconnect the power at the system switch, circuit
breaker, or fuse.
Disconnect cad cell leads from F-F or F1-F
terminals.
Clean the cell face with a soft cloth.Make sure the cell is seated securely in the socket.
Be careful not to disturb the socket position.
Reconnect the cad cell leads to F-F or F1-F
terminals.
Reset the safety switch, turn on the power and set
the thermostat to call for heat.
If burner does not operate or if safety switch trips,
replace the cad cell. Order Honeywell part no. 130367 Cad Cell.
2
2
2
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, Minnesota 55422
69-0618—3
J.S. Rev. 8-96
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9
6
Loading...