Honeywell R8182D, R8182E, R8182F, R8182H, R8182J User Manual

R8182D,E,F,H,J Combination
Protectorelay™ Primary Control and
APPLICATION
The R8182 combines a Protectorelay™ primary control and immersion type Aquastat® controller in one unit for use in oil-fired, hydronic heating systems.
The Protectorelay™ primary control provides control of a line voltage, intermittent ignition oil burner when used with a C554A Cadmium Sulfide Flame Detector and a 24V thermostat.
The R8182 models provide switching as follows:
Model Switching
R8182D High limit, spst;
R8182E High limit, spst R8182F High limit, spst
R8182H (with remote bulb) High limit, spst
R8182J (with remote bulb) High limit, spst
The auxiliary ZC and ZR terminals on the R8182D,E,H,J provide zone control through an R845A Switching Relay.
All models are capable of zone control using zone valves. Each additional zone requires a separate 24V thermostat and a V8043 or V8044 Zone Valve.
The R8182D,E,F models mount directly on the boiler. The R8182H,J models mount directly on a 4 by 4 inch junction box and have a 5 foot (1.5 meter) armored capillary for remote sensor location.
To order an immersion well, use form 68-0040
Fittings for Temperature Controllers
and descriptions.
Refer to Fig. 1 through 3 for installation dimensions.
Refer to Fig. 4 through 8 for internal views of the R8182D,E,F,G,J.
Low limit/circulator, spdt
Circulator, spst
Low limit/circulator, spdt
, for part numbers
Wells and
Aquastat
®
Controller
INSTALLATION INSTRUCTIONS
KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)
2-7/16
(62)
1-5/16
(33)
7-1/8
(181)
3-9/16
(91)
3/16
(5)
1 VERTICAL MOUNT SHOWN.
Fig. 1. R8182D,E,F installation dimensions in inches
HORIZONTIAL MOUNT ONLY
5-1/4 (133)
(millimeters).
VERTICAL MOUNT ONLY
1
3-1/4 (83)
M4517
Copyright © 1995 Honeywell Inc. • All Rights Reserved
X-XX UL
69-0600-1
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
SAFETY SWITCH RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY (1K)
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
VOLTAGE BARRIER
TRANSFORMER FOR CAD CELL CIRCUIT
M4525
1/2 (13)
7-1/8 (181)
7/8 (22)
3-7/16
(87)
3-3/8 (86)
KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)
GROUNDING SCREW
1
HIGH LIMIT SETTING
Fig. 4. Internal view of R8182D.
SAFETY SWITCH
1 SIDE MOUNTED HINGE SHOWN.
5-1/4 (133)
Fig. 2. R8182H,J installation dimensions in inches
(millimeters).
3-7/16 (87)
M4518
GROUNDING SCREW
RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT
AQUASTAT SWITCH
CIRCULATOR RELAY (1K)
R8182D,E,F
CONTROL MOUNT
INSULATION LENGTH 1-1/2 OR 3 IN. (38 OR 76 MM)
R8182H,J
SETSCREW
FITS BOILER TAPPED HOLE
1/2 OR 3/4 NPT
INSERTION LENGTH 3-3/8 IN. (86 MM)
FITS BOILER TAPPED HOLE
1/2 OR 3/4 NPT
INSULATION LENGTH 1-1/2 IN. (38 MM)
Fig. 3. Immersion well dimensions in inches
(millimeters).
INSERTION LENGTH 3-3/8 IN. (86 MM)
69-0600—1
M4530
BURNER MOTOR AND IGNITION RELAY (2K)
VOLTAGE BARRIER
HIGH LIMIT SETTING
TRANSFORMER FOR CAD CELL CIRCUIT
M4532
Fig. 5. Internal view of R8182E.
GROUNDING SCREW
SAFETY SWITCH RESET BUTTON
HIGH LIMIT SETTING
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
TRANSFORMER FOR CAD CELL CIRCUIT
VOLTAGE BARRIER
M4515
Fig. 6. Internal view of R8182F.
2
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
SAFETY SWITCH RESET BUTTON
HIGH LIMIT SETTING
CAD CELL LEADS (YELLOW)
TRANSFORMER FOR CAD CELL CIRCUIT
Fig. 7. Internal view of R8182H.
CAD CELL LEADS (YELLOW)
Fig. 8. Internal view of R8182J.
INSTALLATION
When Installing this Product…
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
Check the ratings given in these instructions and
on the product to be sure the product is suitable for your application.
Be sure the installer is a trained, experienced
service technician.
After completing installation, use these
instructions to check product operation.
VOLTAGE BARRIER
SAFETY SWITCH RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT
AQUASTAT SWITCH
2K RELAY
1K RELAY
VOLTAGE BARRIER
TRANSFORMER FOR CAD CELL CIRCUIT
HIGH LIMIT SETTING
TRANSFORMER FOR THERMOSTAT CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY (1K)
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
M4524
M4531
CAUTION
1. Disconnect the power supply before beginning installation to prevent electrical shock or equipment damage.
2. Be sure that the combustion chamber is clear of oil or oil vapor before starting burner.
3. Be sure that the ambient temperature at the element does not exceed 250°F (121°C).
IMPORTANT
Be sure that the sensing bulb fits snugly inside the immersion well and that the sensing bulb rests against the bottom of the immersion well. Refer to Fig. 3.
Mounting the R8182
Disconnect power supply.Drain all water from boiler.Most boilers are equipped with a tapping that
allows horizontal mounting of immersion well where average temperature boiler water circulates freely. If no tapping is provided, prepare one.
Install immersion well or compression fitting
(ordered separately) by threading immersion well into tapped hole.
For R8182D,E,F models:
a. Loosen immersion well clamp screw on side
of R8182 case. b. Insert bulb into immersion well until it bottoms. c. If necessary, bend capillary tube to hold
bulb against bottom of immersion well.
NOTE: Do not make sharp bends in the tubing.
A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case.
d. Fit controller case onto immersion well so
that immersion well clamp slides over flange
of immersion well. e. Securely tighten immersion well clamp screw.
For R8182H,J models:
a. Loosen the screw holding the hinged
backplate to the controller case and swing
the backplate away from the controller case. b. Screw the backplate to a 4 by 4 inch
junction box. c. Insert bulb into immersion well until it bottoms. d. If necessary, bend capillary tube to hold
bulb against bottom of immersion well.
NOTE: Do not make sharp bends in the tubing.
A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case.
e. Tighten immersion well screw over brass
collar. f. After wiring, swing the control against the
backplate and refasten the screw.
Refill the boiler and check for water leakage.
3
69-0600—1