Honeywell Q674A-G, Q674A-E User Manual

TRADELINE
Thermostats/Q674A-E,G Subbases
®
T874A-F Multistage
Installation Instructions for the Trained Service Technician.
Application
The T874A-F Thermostats provide 24 to 30 Vac control
for heating and/or cooling systems as listed in Table 1.
TABLE 1—THERMOSTAT HEATING AND/OR
T874 A B C D E F
Heating Stages 1 122—2 Cooling Stages 1 2122—
The Q674A-E,G Subbases provide wiring terminals, system and fan switching, and mounting bases for T874 Thermostats as listed in Table 2.
TABLE 2—SUBBASE SWITCHING POSITIONS.
Q674 Switch Positions
Model System Fan
A Heat-Auto-Cool Auto-On B Heat-Off-Cool Auto-On C Off-Auto Auto-On D None None
E Off-Heat-Auto-Cool Auto-On
COOLING STAGES.
Operation
On a 2-heat thermostat, the two stages of heat make sequentially as the temperature drops. Make refers to the mercury switch initiating a call for heat or cool.
There are about 2° F [1° C] between stages so that the second stage makes only when the first stage cannot handle the load. This is the interstage differential.
Recycling Notice
M3375
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mer­cury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condi­tion.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service tech­nician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires close as possible to the subbase.
3. Do not overtighten thermostat captive mount­ing screws because damage to subbase threads can result.
4. Do not short across coil terminals on heating relay or gas control. This can burn out the thermostat heat anticipator.
IMPORTANT: Thermostats are calibrated at the factory
by using subbases mounted at true level. Inaccurate subbase leveling will cause thermostat control de­viation.
LOCATION
Locate the subbase about 5 ft [1.5m] above the floor in
an area with good air circulation at average temperature.
Do not mount the subbase where the thermostat may be
affected by:
— drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun, appliances or fireplace. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
MOUNTING THE SUBBASE
The thermostat subbase can be mounted on a vertical
outlet box, horizontal outlet box or directly on the wall.
1. If you must mount the subbase on a vertical outlet box, order Honeywell 193121A Adapter Assembly (Fig. 1). The assembly includes an adapter ring, two screws and a cover plate to cover marks on the wall. Install the ring and cover plate on the vertical outlet box.
J.H. • Rev. 5-94 • • ©Honeywell Inc. 1994 • Form Number 60-1165—6
1 60-1165—6
M3375
Fig. 1—Installation of subbase on outlet box.
For a wall installation, hold subbase in position and mark holes for anchors. See Fig. 2. Obtain wall anchors locally. Take care that the wires do not fall back into the wall opening. Set aside subbase. Drill two 3/16 in. [4.8 mm] holes and gently tap anchors into the holes until flush with the wall.
Fig. 2—Installation of subbase on wall.
3. Secure the cover plate (if used) and subbase with the
screws provided. Do not fully tighten the subbase screws.
4. Level the subbase using a spirit level, as shown in Fig. 3, and firmly tighten subbase mounting screws. The subbase mounting holes provide for minor out-of-level adjustments.
IMPORTANT: An incorrectly leveled subbase will cause
the temperature control to deviate from setpoint.
Fig. 3—Subbase components and leveling procedure.
WIRING THE SUBBASE
All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring in­structions when available. To wire subbase, proceed as follows:
1. Connect the system wires to the subbase as shown in Figs. 8 through 16. A letter code is located near each terminal for identification. The terminal barrier permits straight or conventional wraparound wiring connections. See Fig. 4.
2. Pull electrical wires through the cover plate (if used) and subbase cable opening (Fig. 3). See Wiring the Subbase section before pulling any wires.
IMPORTANT: Use 18 gauge, color-coded thermostat
cable for proper wiring.
60-1165—6
Fig. 4—Wiring connections.
2. Your Q674 Subbase can require one or more jumpers that may or may not be factory supplied. Refer to the wiring diagrams for specific terminals to be jumpered. See Table 3 for proper application.
CAUTION
Never install more than one wire per terminal unless factory supplied jumper with spade termi­nal is used. See Fig. 7.
2
TABLE 3—JUMPER APPLICATIONS.
If your subbase has: Application Use Fig.
RC, RH terminals single transformer 5
system
adjacent terminals special system 6
operation or LED nonadjacent indication 7 terminals
3. Firmly tighten each terminal screw.
4. Fit wires as close as possible to the subbase. Push
excess wire back into the hole.
5. Plug hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
Fig. 5—Jumper RC and RH for single trans­former system. Strip wire 3/4 in. [19 mm].
Fig. 6—Jumper adjacent terminals for special system hookup. Strip wire 3/4 in. [19 mm].
Fig. 7—For nonadjacent terminals, use jumper supplied with subbase.
NOTE: Only the T874D Thermostat is shown with the
subbases. This thermostat/subbase provides 2-stage heat­ing and 2-stage cooling connections. If using another model, see Fig. 16 and Table 4.
TABLE 4—THERMOSTAT BULB
CONFIGURATOIN.
Model No. Heating Bulbs Cooling Bulbs
T874A H1 C1 T874B H1 C1,C2 T874C H1, H2 C1 T874D H1, H2 C1, C2 T874E C1, C2 T874F H1, H2
3 60-1165—6
Fig. 8—T874A-D/Q674A in standard heating/cooling system.
Fig. 9—T874C,D/Q674B in standard heating/cooling system with separate transformers for heating and cooling.
FALL
H1 ANTICIPATOR
FALL
RISE
RISE
60-1165—6
THERMOSTAT
H1
H2
H2 ANTICIPATOR
C1
C1 ANTICIPATOR
C2 ANTICIPATOR
C2
SUBBASE SYSTEM COMPONENTS
1
4
6
8
9
10
11
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RH, RC FOR SINGLE TRANSFORMER.
FAN SWITCH
AUTO
ON
SYSTEM SWITCH
HEAT
OFF
COOL
4
3
2
3
OPTIONAL LED ON SOME MODELS.
RH
HEAT RELAY 1
W1
HEAT RELAY 2
W2
HEAT CHANGEOVER VALVE
B
X1
O
COOL CHANGEOVER VALVE
G
FAN RELAY
Y2
COMPRESSOR CONTACTOR 2
Y1
COMPRESSOR CONTACTOR 1
RC
L1 (HOT)
L2
1
L2
L1 (HOT)
1
M933C
Loading...
+ 8 hidden pages