Honeywell PVL4022AS, PVL4024NS, PVL6438NS, PVL0000AS, PUL6438S User Manual

...
Spyder® Lon Programmable, VAV/Unitary Controllers
INSTALLATION INSTRUCTIONS

PRODUCT DESCRIPTION

The PUL1012S, PUL4024S, PUL6438S, PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS controllers are part of the Excel 10 product line family. The eight controllers are Free Topology Transceiver (FTT) L
ONMARK
equipment. These controllers provide many options and advanced system features that allow state-of-the-art commercial building control. Each controller is programmable and configurable through software.
These controllers are for use in VAV (Variable Air Volume) and Unitary HVAC control applications. Each controller contains a host micro controller to run the main HVAC application and a second micro controller for LONWORKS® network communications. Each controller has flexible, universal inputs for external sensors, digital inputs, and a combination of analog and digital Triac outputs. The eight models are described in Table 1. The photo to the left is the model PVL6436AS, which includes the actuator.
Table 1. Controller configurations.
Universal
Controller
Model
PUL1012S Unitary
PUL4024S Unitary
PUL6438S Unitary 6 4 3 8 NO NO
PVL0000AS VAV 0 0 0 0 YES YES
PVL4022AS VAV
PVL4024NS VAV
PVL6436AS VAV 6 4 3 6 YES YES
PVL6438NS VAV 6 4 3 8 YES NO
a
One Universal Input (UI-1*) is user selectable as a fast digital pulse meter.
Each controller communicates via the 78 kbps Echelon® L L
ONMARK® compliant.
Controllers are field-mountable to either a panel or a DIN rail.
Programmable
Typ e
Inputs
(UI)
a
1
a
4
a
4
a
4
Digital Inputs
(DI)
01 2 NONO
02 4 NONO
0 2 2 YES YES
0 2 4 YES NO
ONWORKS® Network, using the FTT-10A LONWORKS® interface, and is
Analog
Outputs
(AO)
®
-compliant devices designed to control HVAC
Velocity
Digital
Outputs
(DO)
Pressure
Sensor
(Microbridge)
Series 60
Floating
Actuator
62-0287—03
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
WARNING

SPECIFICATIONS

General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz Power Consumption:
100 VA for controller and all connected loads (including the
actuator on models PVL0000AS, PVL4022AS, and PVL6436AS)
Controller Only Load: 20 VA maximum; models PUL1012S,
PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS.
Controller and Actuator Load: 21 VA maximum; models
PVL0000AS, PVL4022AS, and PVL6436AS
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum
VAV Operating & Storage Temperature Ambient Rating
(models PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS):
Minimum 32 F (0 C); Maximum 122 F (50 C)
Unitary Operating & Storage Temperature Ambient Rating
(models PUL1012S, PUL4024S, and PUL6438S):
Minimum -40 F (-40 C); Maximum 150 F (65.5 C)
Relative Humidity: 5% to 95% non-condensing LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions

BEFORE INSTALLATION

The controller is available in eight models (see Table 1).
Review the power, input, and output specifications on page 2 before installing the controller. — Hardware driven by Triac outputs must have a minimum
current draw, when energized, of 25 mA and a maximum current draw of 500 mA.
— Hardware driven by the analog current outputs must have
a maximum resistance of 550 Ohms, resulting in a maximum voltage of 11 volts when driven at 20 mA. If resistance exceeds 550 Ohms, voltages up to 18 Vdc are possible at the analog output terminal.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or making wiring connections to prevent electrical shock or equipment damage.

INSTALLATION

For PVL0000AS, PVL4022AS, and PVL6436AS models, the actuator is mounted first and then the controller is mounted. For the other models, go to “Mount Controller” on page 4 to begin the installation.

Mount Actuator onto Damper Shaft (PVL0000AS, PVL4022AS, and PVL6436AS)

PVL0000AS, PVL4022AS, and PVL6436AS controllers include the direct-coupled actuator with Declutch mechanism, which is shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 90 second timing at 60 Hz. The actuator is suitable for mounting onto a 3/8 to 1/2 in. (10 to 13 mm) square or round VAV box damper shaft. The minimum VAV box damper shaft length is 1-9/16 in. (40 mm).
The two mechanical end-limit set screws control the amount of rotation from 12° to 95°. These set screws must be securely fastened in place. To ensure tight closing of the damper, the shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTE: The actuator is shipped with the mechanical end-limit
set screws set to 95 degrees of rotation. Adjust the two set screws closer together to reduce the rotation travel. Each “hash mark” indicator on the bracket represents approximately 6.5° of rotation per side.
NOTE: The Declutch button, when pressed, allows you to
rotate the universal shaft adapter (see Fig. 1).
IMPORTANT
Determine the damper rotation and opening angle prior to installation. See Fig. 2 and Fig. 3 on page 3 for examples.
UNIVERSAL SHAFT
CLAMPING BOLTS (2)
UNIVERSAL
SHAFT ADAPTER
MECHANICAL
END LIMIT SET
SCREWS (2)
DECLUTCH
BUTTON
The controller must be mounted in a position that allows clearance for wiring, servicing, removal, connection of the LonWorks® Bus Jack, and access to the Neuron® Service Pin.
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. See Fig. 4–Fig. 7 on page 4 for mounting dimensions.
62-0287—03 2
M23568
Fig. 1. Series 60 Floating Actuator.
IMPORTANT
Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing.
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
M23569
DAMPER SHAFT ROTATES CLOCKWISE TO OPEN
DAMPER
AIR FLOW
AIR FLOW
CW TO OPEN, CCW TO CLOSE
CCW TO OPEN, CW TO CLOSE
M2067B
TYPE A DAMPER
TYPE B DAMPER
Fig. 2. Damper with 90 degree CW rotation to open.
Before Mounting Actuator onto Damper Shaft (PVL0000AS, PVL4022AS, and PVL6436AS)
Tools required: — Phillips #2 screwdriver - end-limit set screw adjustment — 8 mm wrench - centering clamp
Before mounting the actuator onto the VAV box damper shaft, determine the following:
1. Determine the damper shaft diameter. It must be between 3/8 in. to 1/2 in. (10 to 13 mm).
2. Determine the length of the damper shaft. If the length of the VAV box damper shaft is less than 1-9/16 in. (40 mm), the actuator cannot be used.
3. Determine the direction the damper shaft rotates to open the damper (CW or CCW) (see Fig. 3). Typically, there is an etched line on the end of the damper shaft that indicates the position of the damper. In Fig. 2, the indicator shows the damper open in a CW direction.
4. Determine the damper full opening angle (45, 60, or 90 degrees). In Fig. 2, the damper is open to its full open position of 90 degrees.
Fig. 3. Determining the rotation direction (CW or CCW)
for damper opening.
Mounting Actuator onto Damper Shaft (PVL0000AS, PVL4022AS, and PVL6436AS )
The unit is shipped with the actuator set to rotate open in the clockwise (CW) direction to a full 95 degrees. The extra 5 degrees ensures a full opening range for a 90 degree damper. The installation procedure varies depending on the damper opening direction and angle:
1. If the damper rotates clockwise (CW) to open, and the angle of the damper open-to-closed is 90 degrees: a. Manually open the damper fully (rotate clockwise). b. Using the Declutch button, rotate the universal shaft
adapter fully clockwise. c. Mount the actuator to the VAV damper box and shaft. d. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).
When the actuator closes, the damper rotates CCW
90 degrees to fully close.
2. If the damper rotates clockwise (CW) to open, and the angle of the damper open-to-closed is 45 or 60 degrees: a. Manually open the damper fully (rotate clockwise). b. The actuator is shipped with the mechanical
end-limits set at 95 degrees. Adjust the two mechanical end-limit set screws to provide the desired amount of rotation. Adjust the two set screws closer together to reduce the rotation travel.
c. Tighten the two mechanical end-limit screws
(Phillips #2 screwdriver; (26.5–31 lb-in. [3.0–3.5 Nm] torque).
d. Using the Declutch button, rotate the universal shaft
adapter fully clockwise. e. Mount the actuator to the VAV damper box and shaft. f. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). g. When the actuator closes, the damper rotates CCW
either 45 or 60 degrees to fully close.
3.
If the damper rotates counterclockwise (CCW) to open, and the angle of the damper open-to-closed is 90 degrees: a. Manually open the damper fully (rotate counter-
clockwise). b. Using the Declutch button, rotate the universal shaft
adapter fully counterclockwise. c. Mount the actuator to the damper box and shaft. d. Tighten the two bolts on the centering clamp (8 mm
wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). When
the actuator closes, the damper rotates CW
90 degrees to fully close.
4. If the damper rotates counterclockwise (CCW) to open, and the angle of the damper open-to-closed is 45 or 60 degrees: a. Manually open the damper fully (rotate counter-
clockwise).
b. The actuator is shipped with the mechanical
end-limits set at 95 degrees. Adjust the two mechanical end-limit set screws to provide the desired amount of rotation. Adjust the two set screws closer together to reduce the rotation travel.
c. Tighten the two mechanical end-limit screws
(Phillips #2 screwdriver; (26.5–31 lb-in. [3.0–3.5 Nm] torque).
d. Using the Declutch button, rotate the universal shaft
adapter fully counter-clockwise. e. Mount the actuator to the VAV damper box and shaft. f. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). g. When the actuator closes, the damper rotates CW
either 45 or 60 degrees to fully close.
3 62-0287—03
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
123456
78
109 234567
11 111111
123456780
9
2222222223
3
123456780
9
333
33
33
34
5-3/4 (146)
10-5/16 (262)
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
PANEL MOUNTING HOLE
(4X) 3/16 IN. (4.5)
M28647
5-3/64
(128)
8-5/16 (211)
6-29/64 (164)
1-55/64
(47)
6-17/64
(159)
7/16
(11)
DEPTH IS 2-1/ 4 (57 )
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
5-3/4 (146)
6-27/32 (174)
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
PANEL MOUNTING HOLE
(4X) 29/64 IN. (12)
M23589B
5-3/64
(128)
6-29/64 (164)
5-29/64
(139)
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
6-27/32 (174)
5-3/64
(128)
6-29/64 (164)
5-29/64
(139)
PVL6438NS
PUL6438S
DEPTH IS 2-1/ 4 (57 )

Mount Controller

NOTE: The controller may be wired before mounting to a
panel or DIN rail.
Terminal blocks are used to make all wiring connections to the controller. Attach all wiring to the appropriate terminal blocks (see “Wiring” on page 5).
See Fig. 4 to Fig. 7 for panel mounting dimensions. See Fig. 8 on page 5 for DIN rail mounting.
4-13/16 (122)
4-1/8 (105)
1 1 1 1 1 1 1 2 2 2 2 2 3 4 5 6 7 8 9 0 1 2 3 4
6-1/4 (159)
5-7/8 (149)
1 1 1 2 3 4 5 6 7 8 9 0 1 2
3/16 (4.5) PANEL MOUNTING HOLE (4X)
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
DEPTH IS 2-1/4 (57)
6-1/4 (159)
5-7/8 (149)
4-13/16 (122)
4-1/8 (105)
1 1 1 1 1 1 1 2 2 2 2 2 3 4 5 6 7 8 9 0 1 2 3 4
1 1 1 2 3 4 5 6 7 8 9 0 1 2
M28649
Fig. 5. Panel mounting — controller dimensions in inches
(mm) for PUL1012S, PUL4024S, and PVL4024NS only
(PUL4024S and PVL4024NS shown).
8-9/32
(211) 4-1/8 (105)
1 1 1 1 1 1 1 1 1 1 2
9 0 1 2 3 4 5 6 7 8 9 0
1-15/16
(49)
27/32
(21)
Fig. 4. Panel mounting — controller and actuator
dimensions in inches (mm) for PVL6436AS only.
6-1/4 (159)
5-7/8 (149)
1 2 3 4 5 6 7 8
3/16 (4.5) PANEL
MOUNTING HOLE (4X)
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
Fig. 6. Panel mounting — controller and actuator
dimensions in inches (mm) for PVL0000AS and
PVL4022AS only (PVL4022AS shown).
6-9/32
(159)
DEPTH IS 2-1/ 4 (57 )
M28648
62-0287—03 4
Fig. 7. Panel mounting — controller dimensions in inches (mm) for PUL6438S and PVL6438NS only.
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
WARNING
DIN RAIL
TOP TABS
BOTTOM FLEX CONNECTORS
M16815
Panel Mounting
The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover.
NOTE: The controller is designed so that the cover does not
need to be removed from the base plate for either mounting or wiring.
The controller mounts using four screws inserted through the corners of the base plate. Fasten securely with four No. 6 or No. 8 machine or sheet metal screws.
The controller can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation.
DIN Rail Mounting (PUL1012S, PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS)
To mount the PUL1012S, PUL4024S, PUL6438S, PVL4024NS, or PVL6438NS controller on a DIN rail [standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)], refer to Fig. 8 and perform the following steps:
1. Holding the controller with its top tilted in towards the DIN rail, hook the two top tabs on the back of the con­troller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connec­tors of the controller onto the DIN rail.
NOTES:
Use 1/4 inch (6 mm) outside diameter, with a
0.040 in. (1 mm) wall thickness, plenum-rated 1219 FR (94V-2) tubing.
Always use a fresh cut on the end of the tubing
that connects to the air flow pickups and the restrictor ports on the controller.
Connect the high pressure or upstream tube to the plastic restrictor port labeled ( downstream tube to the restrictor port labeled (
+), and the low pressure or
-). See labeling
in Fig. 9. When twin tubing is used from the pickup, split the pickup tubing a short length to accommodate the connections.
NOTES:
If controllers are mounted in unusually dusty or
dirty environments, an inline, 5-micron disposable air filter (use 5-micron filters compatible with pneumatic controls) is recommended for the high pressure line (marked as
+) connected to the air
flow pickup.
The tubing from the air flow pickup to the control-
ler should not exceed three feet (0.914 m). Any length greater than this will degrade the flow sensing accuracy.
Use caution when removing tubing from a con-
nector. Always pull straight away from the con­nector or use diagonal cutters to cut the edge of the tubing attached to the connector. Never remove by pulling at an angle.
Fig. 8. Controller DIN rail mounting (models PUL1012S,
PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS).
IMPORTANT
To remove the controller from the DIN rail, perform the following:
1. Push straight up from the bottom to release the top tabs.
2. Rotate the top of the controller out towards you and pull the controller down and away from the DIN rail to release the bottom flex connectors.

Piping (PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS)

Air flow Pickup
For PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS, connect the air flow pickup to the two restrictor ports on the controller (see Fig. 9).
AIR FLOW PICKUP
RESTRICTOR
PORT
M23556A
ΔP
1 2 3 4 5 6
2 2 1 2 3 4 5 6
7 8
CONNECTOR TUBING
RESTRICTOR PORT
2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
1 1 1 1 1 1 1 1 1 2 1 1 0 9 2 3 4 5 6 7 8 0 9
3 3 3
3 3
3 3
3 4
7 8 0 9
Fig. 9. Air flow pickup connections (PVL0000AS,
PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS).

Wiring

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Controller wiring is terminated to the screw terminal blocks located on the top and the bottom of the device.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or making wiring connections, to prevent electrical shock or equipment damage.
5 62-0287—03
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
A
NOTES:
For multiple controllers operating from a single
transformer, the same side of the transformer sec­ondary must be connected to the same power input terminal in each controller. Controller config­urations will not necessarily be limited to three devices, but the total power draw, including accessories, cannot exceed 100 VA when pow­ered by the same transformer (U.S. only). For power and wiring recommendations, see “Wiring” on page 5 The earth ground terminal (terminal 3) must be connected to a verified earth ground for each controller in the group (see Fig. 12 on page 7).
All loads on the controller must be powered by the
same transformer that powers the controller itself. A controller can use separate transformers for controller power and output power.
Keep the earth ground connection (terminal 3)
wire run as short as possible.
Do not connect the universal input COM
terminals, analog output COM terminals or the digital input/output COM terminals to earth ground. Refer to Fig. 10–Fig. 12 for wiring examples.
The 24 Vac power from an energy limited Class II power source must be provided to the controller. To conform to Class II restrictions (U.S. only), the transformer must not be larger than 100 VA.
Maintain at least a 3 in. (7.6 cm) separation
between Triac outputs and L
ONWORKS® wiring
throughout the installation.
CONNECT POWER TO TERMINALS 1 AND 2
COM
24 VAC
TRANSFORMER
ΔP
1 2 3 4 5 6
OUTPUT DEVICE POWER
2
2 2 1 2 3 4 5 6
7 8
EARTH GROUND (TERMINAL 3)
2 2 2 2
2 2 3 3
7 8 0 9
1 1 1 1 1 1 1 1 1 2 1 1 0 9 2 3 4 5 6 7 8 0 9
3 3 3
3 3
1 2 3 4 5 6
3 3
Fig. 10. Power wiring details for one controller
per transformer.
ΔP
2
2 2 2 2
2 2 1 2 3 4 5 6
2 2 3 3
7 8 0 9
3 3 3
3 3
1 2 3 4 5 6
3 4
7 8 0 9
M23557
3 3
3 4
7 8 0 9
Fig. 10 depicts a single controller using one transformer.
IMPORTANT
Power must be off prior to connecting to or removing connections from the 24 Vac power (24 Vac/24 Vac COM), earth ground (EGND), and 20 Vdc power (20 Vdc) terminals..
IMPORTANT
Use the heaviest gauge wire available, up to 14 AWG (2.0 sq mm), with a minimum of 18 AWG (1.0 sq mm), for all power and earth ground wiring.
Screw-type terminal blocks are designed to accept up to one 14 AWG (2.0 sq mm) conductor or up to two 18 AWG (1.0 sq mm) conductors. More than two wires that are 18 AWG (2.0 sq mm) can be con­nected with a wire nut. Include a pigtail with this wire group and attach the pigtail to the terminal block.
IMPORTANT
If the controller is used on Heating and Cooling Equipment (UL 1995, U.S. only) and the
transformer primary power is more than 150 volts, connect terminal 2, (the 24 Vac common [24 VAC COM] terminal) to earth ground (see Fig. 11). For these applications, only one controller can be powered by each transformer.
NOTES:
Unswitched 24 Vac power wiring can be run in the
same conduit as the L
ONWORKS® cable.
CONNECT POWER TO TERMINALS 1 AND 2
7 8
1 2 3 4 5 6
TRANSFORMER
COM
24 VAC
LINE VOLTAGE GREATER THAN 150 VAC
IF THE CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE
1
PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM SIDE OF TRANSFORMER SECONDARY.
1
EARTH GROUND
OUTPUT DEVICE POWER
EARTH GROUND (TERMINAL 3)
1 1 1 1 1 1 1 1 1 2 1 1 0 9 2 3 4 5 6 7 8 0 9
M23558A
Fig. 11. Transformer power wiring details for one
controller used in UL 1995 equipment (U.S. only).
More than one controller can be powered by a single transformer. Fig. 12 shows power wiring details for multiple controllers.
NOTE: Controller configurations are not necessarily limited
to three devices, but the total power draw, including accessories, cannot exceed 100 VA when powered by the same transformer (U.S. only). For power wiring recommendations, see “Wiring” on page 5.
62-0287—03 6
Wiring Method
WARNING
M23559A
120/240
VAC
TRANSFORMER
OUTPUT DEVICE POWER
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
COM
24 VAC
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
EARTH GROUND (TERMINAL 3)
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
EARTH GROUND (TERMINAL 3)
EARTH GROUND (TERMINAL 3)
CONNECT POWER TO TERMINALS 1 AND 2
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
Fig. 12. Power wiring details for two or more controllers per transformer.
1.
STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
TWIST WIRES
2.
TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
1/2
(13)
NOTE: When attaching two or more wires to the same termi-
nal, other than 14 AWG (2.0 sq mm), be sure to twist them together. Deviation from this rule can result in improper electrical contact (see Fig. 13).
Each terminal can accommodate the following gauges of wire: — Single wire: from 22 AWG to 14 AWG solid or stranded — Multiple wires: up to two 18 AWG stranded, with 1/4 watt
wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in
the required terminal location and tighten the screw.
3. If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them (see Fig. 13).
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw.
5. Pull on each wire in all terminals to check for good mechanical connection.
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)
BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M17207
Fig. 13. Attaching two or more wires at terminal blocks.

Controller Replacement (PVL0000AS, PVL4022AS, and PVL6436AS)

For PVL0000AS, PVL4022AS, and PVL6436AS controllers, which are hard-wired to an actuator, perform the following actions to replace the complete assembly (controller and actuator):
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
pressure sensor.
7 62-0287—03
3. Remove the terminal blocks.
4. Remove the old controller and actuator assembly from
its mounting.
• Loosen the two bolts on the actuator clamp to release the actuator from the shaft.
• Remove the controller’s mounting screws.
• Gently pull the controller and actuator assembly straight out, until the assembly is clear of the actuator shaft.
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
5. Mount the new controller and actuator assembly (see “Installation” on page 2).
6. Reconnect the two air flow pickup tubes to the pressure sensor (see “Piping (PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS)” on page 5).
7. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.
9. Perform checkout.

Controller Replacement (PVL4024NS and PVL6438NS)

Perform the following to replace the PV4024NS and PVL6438NS controllers:
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
pressure sensor.
3. Remove the terminal blocks.
4. Remove the old controller from its mounting.
IMPORTANT
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 8 on page 5).
5. Mount the new controller.
• see “Installation” on page 2
6. Reconnect the two air flow pickup tubes to the pressure sensor (see “Piping (PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS)” on page 5).
7. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.
9. Perform checkout.

Controller Replacement (PUL1012S, PUL4024S, and PUL6438S)

Perform the following to replace the PUL1012S, PUL4024S, and PUL6438S controllers:
1. Remove all power from the controller.
2. Remove the terminal blocks.
3. Remove the old controller from its mounting.
IMPORTANT
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 8 on page 5).
4. Mount the new controller (see “Installation” on page 2).
5. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
6. Restore power to the controller.
7. Perform checkout.
LON®, LONTALK®, LONWORKS®, and NEURON® are registered trademarks of Echelon® Corporation.
ONMARK® and the LonMark Logo are trademarks of the LonMark Association.
L
N
IAGARA FRAMEWORK® and the Niagara framework logo are registered trademarks of Tridium, Inc.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2009 Honeywell International Inc. 62-0287—03 K.K. 02-09
Loading...