PDX Series Models:
PDX140S*F(BN,SX,CX)
PDX150S*F(BN,SX,CX)
PDX440S*F(BN,SX)
PDX450S*F(BN,SX)
PDX250T*F(BN,SX,CX)
PDX265T*F(BN,SX,CX)
PDX275T*F(BN,SX,CX)
PDX50S60F(B,S,C)*(N,X)
PDX65S65F(B,S,C)*(N,X)
PDX75S70F(B,S,C)*(N,X)
(*) Denotes Warranty Years
Powered Direct Vent Gas Water Heaters
PDX Series
Table of Contents
PagePDX Service Procedure
Introduction4- - -
How to use this manual5- - -
Tool required for service5- - -
Specifications6- - -
Control Timings9- - -
Sequence of Operation10- - -
Troubleshooting13- - -
Burner Inspection, Cleaning and Replacement15I
Pilot Testing, Cleaning and Replacement17II
Pressure Switch Testing and Replacement 18III
Blower Testing and Replacement20IV
Blower Temperature Switch Testing and Replacement22V
Gas Control & Thermal well Testing & Replacement24VI
Flammable Vapor Sensor Testing & Replacement28VII
Safety Circuit Voltage Trace29VIII
115VAC Circuit Trace30IX
Dip Tube inspection and Replacement31X
Anode Inspection and Replacement32XI
Flue Baffle Inspection and Replacement33XII
Inner Door Removal, Inspection & Replacement34XIII
Glossary of Terms38- - -
Parts List39- - -
Page 2
2
PDX Series
WARNING: If the information in these instructions is
not followed exactly, a fire or explosion may result
causing property damage, personal injury, or death.
FOR YOUR SAFETY
Donotstoreor usegasolineor other flammable,
combustible, or corrosive vaporsand liquids inthe
vicinity ofthisor any other appliance.
WHAT TO DO IF YOU SMELL GAS
Donottry tolightany appliance.
Donottouch any electricalswitch; donot useany
phone in your building.
Immediately call your gassupplier from a neighbor's phone.
Follow thegassupplier's instructions.
If you cannot reach your gassupplier, callthefire
department.
Installationand service mustbe performed by a qualified
installer, serviceagency or thegassupplier.
WARNING
Water heatersare heat producingappliances. Toavoid
damageor injury, donotstore materialsagainstthe
water heater or vent-air intakesystem. Use proper care
to avoid unnecessary contact (especially by children) with
the water heater and vent-air intake components. UNDER
NO CIRCUMSTANCES MUST FLAMMABLE MATERIALS,
SUCH AS GASOLINE OR PAINT THINNER BE USED OR
STORED IN THE VICINITY OF THIS WATER HEATER, VENTAIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH
FUMES COULD REACH THE WATER HEATER OR VENT-AIR
INTAKE SYSTEM.
CAUTION
Ifsweatfittingsaretobe used DO NOTapply heattothe
nipples on top of the water heater. Sweat the tubing to
the adapter before fitting the adapter to the water
connections. It is imperative that heat is not applied to
the nipples containing a plastic liner.
WARNING
Hydrogengas canbe produced in anoperating water
heater that hasnot had water drawnfrom thetank for a
long period oftime (generally two weeksor more).
Hydrogengas is extremely flammable. To preventthe
possibility of injury under these conditions, we
recommend the hot water faucettobeopenfor several
minutes atthe kitchensink before you useany electricalappliance which is connected tothe hot water system. If
hydrogen is present, there willbean unusualsound such
as air escaping through the pipes as hot water begins to
flow. Do not smoke or have open flame near the faucet
at the time it is open.
Incorrect operation of this appliance may
CAUTION
createa hazard tolifeand property and
willnullify the warranty.
DANGER
Donotstoreor usegasolineor other
flammable, combustible, or corrosive
vaporsand liquids inthe vicinity ofthisor
any other appliance.
IMPORTANT
Before proceeding, please inspectthe
water heater and its componentsfor
possible damage. DO NOT installany
water heater with damaged components.
If damage isevidentthen please contactthesupplier wherethe water heater was
purchased or the manufacturer listed on
the rating platefor replacement parts.
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE
NOT CERTAIN OF THE FOLLOWING:
Liquefied petroleum gases/propanegasand naturalgas
haveanodorantadded by thegassupplier thataids in
the detectionofthegas.
Most people recognizethisodor asa “sulfur” or “rottenegg” smell.
Other conditions, such as “odorantfade” can causetheodorantto diminish in intensity, or ”fade”, and notbeas
readily detectable.
If you havea diminished senseofsmell, or are inany way
unsureofthe presenceofgas, immediately contact your
gassupplier from aneighbor'stelephone.
Gas detectorsareavailable. Contact your gassupplier, or
plumbing professional, for more information.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/
4” TEMPERATURE AND PRESSURE RELIEF VALVE WILL
RELEASE THE MANUFACTURER FROM ANY CLAIM THAT
MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND
PRESSURES.
CAUTION
Turn off or disconnect the electrical power supply to the
water heater beforeservicing. Labelall wires prior to
disconnection whenservicing controls. Wiringerrors can
cause improper and dangerousoperation. Verify proper
operation after servicing.
Page 3
3
PDX Series
The new Bradford White PDX1, PDX2 and PDX4 water heaters are designed to provide
reliable performance with enhanced standard features. New design features include reliable
spark to pilot ignition system, enhanced diagnostics, simplified servicing, significantly quieter
operation, additional vent lengths and certified FVIR technology.
Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes
reliable and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease
of troubleshooting by providing simple diagnostic codes to pinpoint an installation or
component performance issue.
New Powerful Blower - will eliminate problems with difficult venting situations.
Quieter and Cooler Blower Operation - blower noise is significantly reduced for both
interior and exterior environments. Cooler operation increases blower life by reducing bearing
wear and noise.
Increased Vent Lengths - increased venting performance is achieved while maintaining
Energy Factor & FHSR performance.
The PDX1, PDX2, and PDX4 water heaters use a combustion system were flue gases are
combined with dilution air to reduce the flue gas temperature in the blower, combustion air and
dilution air are drawn from outside the building. The diluted flue gases are evacuated to the
exterior through non metallic vent materials. The gas control maintains water temperature,
ignition sequence and regulates gas flow. A safety circuit consisting of a pressure switch and
blower temperature switch verifies proper conditions exist for safe and reliable operation. If a
situation outside of normal operating parameters exists, the gas control diagnostic LED will
flash a code to positively identify an operational issue.
This service manual is designed to facilitate problem diagnosis and enhance service efficiency.
To further promote quicker service times the new gas valve can be removed and replaced
without draining the water heater. A special tool is required and will be provided with each gas
valve kit shipped from our Service Parts department.
Please read the service manual completely before attempting service on this new series of
power vent models.
How the Safety System Works
During normal operation, air for combustion is drawn into the water heater though the vent pipe from outside your
building. The air travels into the closed combustion chamber. The air then mixes with in a normal manner with
supplied gas and its efficiently combusted, producing very low NOx emissions.
In the unlikely event trace amounts of flammable vapors are present in the area surrounding the water heater, the
sealed combustion system prevents the flammable vapors from reaching the ignition source. In addition the
flammable vapors sensor will stop the water heater from operating if a significant amount of flammable vapors are
present.
Page4
4
How to Use This Manual
PDX Series
It is intended for this manual to be used by qualified service personal for the primary purpose of
troubleshooting and repair of the Bradford White PDX Series water heaters. Understanding the
sequence of operation section of this manual will contribute greatly to troubleshooting the water
heater.
The Honeywell WV4460E Electronic Gas Control will display error codes in the event of abnormal
operation. Error codes are listed in the troubleshooting chart beginning on page 12 of this service
manual. The troubleshooting chart will also indicate the probable cause for the error code and
direct the service professional to a service procedure to properly diagnose the abnormal operation.
In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent
system to determine the problem.
Contact the Bradford White technical support group immediately if diagnosis can not be made
using the methods described in this service manual.
ToolsRequired forService
Manometer:A liquid “U” tube type or a digital (magna-helic) type can be used. This
device is used to measure gas and/or air pressure and vacuum.
Multi-Meter:A digital type is strongly recommended. This device is used to measure
electrical values. The meter you select must have the capability to
measure volts AC, volts DC, Amps, micro-amps and ohms.
Electronic Probes:In some cases, standard multi-meter probes will damage or simply
not be effective to obtain certain voltage and ohm reading. It will be
necessary to have special electronic “pin” type multi-meter probes.
These probes are available at most electronic wholesale outlets.
Thermometer:Used to measure water temperature. An accurate thermometer is
recommended.
Water Pressure Gage: Used to measure water supply pressure. Also used to determine tank
pressure by adapting to the drain valve of the heater.
Gas Control Service Tool:BWC part number 239-45991-00. A specialized tool designed to remove
the gas control from gas control thermal well. Available from
your Bradford White parts supplier.
Various Hand Tools:Pipe wrench, channel locks, open end wrenchs (3/8",7/16",½"),
Blower Temperature Switch Normally closed, opens @ 155°F (68°C), auto reset @ 128°F (54°C).
Standard Altitude-Normally open, closes at differential pressure of -.80.
Pressure switch
High Altitude-Normally open, closes at differential pressure of -.73.
Blower115VAC,60Hz, 3.1amps.
Page6
6
PDX Series
Specifications
Venting Specifications for:
48 Gallon
65 Gallon
75 Gallon
This water heater is approved for installation with the following PVC, CPVC or ABS
Schedule 40 venting material.
The maximum and minimum vent lengths listed on this label are for the exhaust portion of
the vent. The intake portion of the vent must be equal to or less than the length of the
exhaust.
Vent Tables
3" Diameter (7.6 cm) PVC Vent Connector Lengths
Maximum 75 gal.Maximum 48, 65 gal.
Terminating
Through the Wall
Through the Wall250 (15.2)2 (.6)
Through the Wall345 (13.7)2 (.6)
Through the Wall440 (12.2)2 (.6)
Through the Roof060 (18.3)7 (2.1)
Through the Roof155 (16.8)7 (2.1)
Through the Roof250 (15.2)7 (2.1)
Through the Roof345 (13.7)7 (2.1)
# of
Elbows
Maximum
Length ft (m)
Length ft (m)
155 (16.8)2 (.6)
Minimum
Maximum
Length ft (m)
Minimum
Length ft (m)
45 (13.7)2 (.6)
40 (12.2)2 (.6)
35 (10.7)2 (.6)
30 (9.1)2 (.6)
50 (15.2)7 (2.1)
45 (13.7)7 (2.1)
40 (12.2)7 (2.1)
35 (10.7)7 (2.1)
4" Diameter (10.2 cm) PVC Vent Connector Lengths
Terminating
Through the Wall
# of
Elbows
Maximum
Length ft (m)
Minimum
Length ft (m)
195 (29.0)10 (3.1)
Through the Wall290 (27.4)10 (3.1)
Through the Wall385 (25.9)10 (3.1)
Through the Wall480 (24.4)10 (3.1)
Through the Wall575 (22.9)12 (3.6)
Through the Roof0100 (30.5)15 (4.6)
Through the Roof195 (29.0)15 (4.6)
Through the Roof290 (27.4)15 (4.6)
Through the Roof385 (25.9)15 (4.6)
Through the Roof480 (24.4)15 (4.6)
Maximum 75 gal.Maximum 48, 65 gal.
Maximum
Length ft (m)
Minimum
Length ft (m)
85 (25.9)10 (3.1)
80 (24.4)10 (3.1)
75 (22.9)10 (3.1)
70 (21.3)10 (3.1)
65 (19.8)12 (3.6)
90 (27.4)15(4.6)
85(25.9)15 (4.6)
80 (24.4)15 (4.6)
75(22.9)15 (4.6)
70 (21.3)15 (4.6)
Page 7
7
PDX Series
Part II-Venting Specifications for:
40 Gallon
50 Gallon
Specifications
Vent Tables
The minimum equivalent length for the exhaust portion of the vent is 7 feet. The maximum equivalent vent length for the exhaust is 35 feet
for 2" diameter pipe and 85 feet for 3" diameter pipe. The intake portion of the vent must be equal to or less than the vent length of the
exhaust. The tables below are provided for your quick reference, some installations may require a greater number of elbows. When
calculating equivalent vent length, one 90° elbow is equivalent to 5 feet.
IMPORTANT
VENT CONNECTOR LENGTHS FOR 2" (5.1 cm) DIAMETER VENT PIPE
# of
Terminating
Through the Wall
Elbows
(excl. vent
term.)
130 (9.1)
Through the Wall225 (7.6)
Through the Wall3
Through the Wall415 (4.6)
Through the Roof035 (9.1)
Through the Roof130 (9.1)
Through the Roof225 (7.6)
Through the Roof320 (6.1)
Maximum
straight
Length ft (m)
20 (6.1)
Minimum
straight
Length ft (m)
2 (.6)
2 (.6)
2 (.6)
2 (.6)
7 (2.1)
7 (2.1)
7 (2.1)
7 (2.1)
VENT CONNECTOR LENGTHS FOR 3" (7.6 cm) DIAMETER VENT PIPE
PS Fault Delay (failed open/close)Retry after 2 Minutes
Soft LockoutRetry after 5 Minutes
TCO Limit LockoutIndefinite (cycle power to restart)
Verify ResistiveDelayRetry after 2 Minutes (repeats 5 times)
Simulated Resistive Load LockoutIndefinite (cycle power to restart)
Hardware Error LockoutIndefinite (self clears if fault clears for at least 15 seconds)
Specifications
IgnitionStateTiming
Page9
9
PDX Series
1
Start Up.
Uponpower up, the control runs a safe-start check with a typical start-updelay of 1-5 seconds.
2
Flammable Vapor Check.
To assure no outputs are energized if the “Flammable Vapor Sensor” is out of range, the control will test the
the “Flammable Vapor Sensor” for proper operating range. If the “Flammable Vapor Sensor” is within range the
control resumes normal operation with no perceptible delay. If the “Flammable Vapor Sensor” is out of range, the
control LEDimmediately flashes 7 times with 3 second pause.
1
Thermostat calls for heat.
Prior to energizing blower, gas control checks safety circuit to insure the circuit is open. Normal switch positions
in the safety circuit are as follows:
a) Exhaust pressure switch normally open.
b) Blower temperature switch normally closed.
If the safety circuit is closed, the control waits 4 seconds, gas control LED flashes 2 times with 3 second pause.
Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens.
Sequence of Operation
2
Blower energizes.
3
Blower pre-purge period (15 seconds)
4
Differential pressure switch proves blower/vent system operation.
a) If the pressure switch does not close within 30 seconds, the control LED Flashes 3 times with 3 second pause.
The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature
switch to close. This cycle repeats as long as there is a call for heat.
5
Trial for pilot ignition (90 seconds).
a) The gas control lights the pilot by activating spark igniter andgas flow to pilot burner.
b) If flame is not sensedwithin 90 seconds, igniter andgas flow are deactivated,blower will post purge and
control LED flashes 6 times with 3 secondpause.
6
Mainburner Ignition
After pilot flame is sensed,gas control activates main valve for mainburner ignition. The gas control will ignore
flame andpressure switch signals for 3 seconds allowing for mainburner to stabilize.
10
Page10
PDX Series
Steady state operation.
7
8
Thermostat satisfies.
9
Burner off.
During Steady State Operation the Control Monitors:
Thermostat temperaturesensor- When set point temperature is satisfied, gas valve is shut down and
blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status
code.
Pressureswitch / Blowertemperatureswitch- If either switch opens, pilot valve and main valve is shut
down. The blower continues to run for 30 seconds attempting to close the circuit. The control LED Flashes
3 times with 3 second pause.
FlameSense- Ifflame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts
to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control
re-attempts to light pilot starting at normal heating sequence #2.
Sequence of Operation
10
Blower post purge (15 seconds).
1. Simulated Resistive Device Fault:
a) If the FlammableVaporSensorresistanceisgreaterthan70,000 Ohms - the gas control immediately turns
off all outputs. Control waits and monitors resistance for 30 seconds. If the resistance is greater than 70,000 ohms
after 30 seconds, the gas control proceeds to verify resistive delay for 2minutes and flashes 7 times with a three
second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds
to a lockout mode flashing 7 times with a 3 second pause.
b) If the FlammableVaporSensorresistanceisbelow 3000ohms - The gas control immediately turns off all
outputs and proceeds to flash8 times then once with three second pause. The error selfclears if the resistance
returns to normal range for at least 15 seconds.
2. Temperature Sensor Fault:
a) Temperature sensor detected open circuit - The gas control Immediately turns off all outputs and proceeds to
flash8 times then three times with three second pause. The error selfclears if the fault clears for at least 15
seconds.
b) Temperature sensorsnotreadingthesametemperaturewithin ±5.5 °F - The gas control Immediately turns off
all outputs and proceeds to flash 8 times then three times with three second pause. The error self clears if the fault
clears for at least 15 seconds.
c) Watertemperatureinexcessof TCO (TemperatureCut Off) limit - The gas control immediately turns off pilot &
main valve and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset.
Power needs to be cycled to remove gas control from TCO lockout.
Page 11
11
Sequence of Operation
PDX Series
3. Pressure Switch/Blower Temperature Fault:
a) Pressure switch closed at start of call for heat - The control waits four seconds then, proceeds to flash
2 times with 3 second pause. The control waits 2 minutes and then turns onblower for 30 seconds. The blower
turns off after 30 seconds and the control waits for pressure switch to open. Any time the Pressure switch opens,
the blower turns on (or stays on) and the control proceeds to waitingfor pressure switch to close.
b) Pressure switch or blower temperature switch failed open - The control runs the blower for 30 seconds
waitingfor the pressure switch and/or blower temperature switch to close. If either switch does not close in30
seconds, the blower turns off and the control flashes 3 times with 3 second pause. The control waits two
minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as
there is a call for heat or until the circuit closes.
c) Pressure switch or blower temperature switch opens during burner operation - The control turns off the
pilot and main valve, runs blower for 15 seconds (inter-purge) waitingfor pressure switch and/or blower
temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above. If the
circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count has
gins. If the recycle count has been reached, the control
not reached its limit (4), another trial for ignition
turns off the blower andflashes 6 times then 2 times with 3 second pause. The control waits 5 minutes before
repeating ignition sequence.
be
4. Trial For Ignition Fault:
a) Pressure switch opens during trial - The control turns off igniter and pilot valve. The gas control proceeds
as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for
ignition starting at blower pre-purge.
b) Flame Not Sensed - The control energizes the spark igniter attempting to light the pilot and prove flame. If
flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the
blower through post purge and flashes 6 times then once with 3 second pause. The control waits 5 minutes before
repeating the ignition sequence.
5. Flame Sensing Fault:
a) Flame lost during run - The control turns off pilot and main valves, runs blower for 15 seconds (inter purge).
The control increments the recycle count, if the recycle count has not reached its limit (4), another trial for
ignitionbegins. If the recycle count has been reached, the control turns off the blower andflashes 6 timesthen 3 times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
b) Flame sensed out of sequence - the control only looks for pilot flame when the blower is running. If flame is
present when the pilot valve is not open, the control proceeds to wait for flame loss and flashes 5 times with 3
second pause. This continues until flame is lost, once the flame signal is lost, the control flashes 6 times then 4times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
12
Page12
PDX Series
Troubleshooting
Observegreen LEDindicatoron Electronic gas
control. Error flash codesare displayed with a
three second pause before repeating. Check
and repair the system as noted in the
troubleshooting table below.
4. Refer to venting section of
installation manual
5. Page 20
6 & 7 Page 22
8. Refer to installation
manual.
1. Page 15
2-4. Page 17
5. Refer to installation manual
Replace gas control,
page 26
Page 28
Eight-one flash, three
second pause
Eight-three flash, three
second pause
Eight-four flash, three
second pause
14
Flammable Vapor
Sensor out of
specification.
Thermal well
sensor damaged
or unplugged
Gas valve
electronics fault
detected
Gas valve fault
detected.
* Verify Flammable Vapor Sensor (FVS) resistance is
not below 25 K Ohms.
* Check wiringto FVSandinsureitisnotshorted.
* Replacecontrol ifeverythingabovechecksout OK.
1. Damagetothermal well wire.
2. Thermal well sensorresistanceoutofrange.
1. Control needstobereset.
2. Control iswetorphysicallydamaged.
1. Control needstobereset.
2. Control iswetorphysicallydamaged.
Page 28
Page 24
1. Interrupt power supply
2. Replace gas control,
page 26
1. Interrupt power supply
2. Replace gas control,
page 26
Page14
PDX SERVICE PROCEDURE I
PDX Series
Burner Operation Inspection,
Adjustment, Cleaning and Replacement
Burner Inspection and Air Shutter Adjustment.
At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main burner for proper
operation and to assure no debris is accumulating.
Pilot flame should be stable, some causes for an unstable pilot flame are:
a) Water heater vent is less than the allowable vent length.
b) Gas pressure is out of specification.
c) Pilot flame not fully engulfing spark/flame sensor.
d) Door was not sealed properly after servicing.
Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips.
Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter. Cast iron burner can
have the gas and air mixture properly proportioned by adjusting the air shutter on the mixer face of the main burner
(see cast iron burner adjustment below).
Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning
procedure on page 14).
Cast Iron Burner Air Shutter Adjustment
WARNING
Innerdoor andburner components may be HOT when performing this operation. Take
necessary precaution to prevent personal injury.
Step 1.With main burner in operation, remove outer jacket door remove inner door as described in this manual,
see inner door removal, inspection and replacement section (page 35).
Step 2.To adjust for proper burning, loosen the air shutter nut, rotate the air shutter to close the opening in the
burner, then slowly rotate the air shutter open until flame becomes as blue as possible with a minimum of
yellow tips. Tighten the air shutter nut.
Too much air will cause the flame to lift off the burner ports and create noisy burner operation.
Too little air will result in soot formation.
Step 3.Replace inner door as described in this manual, observe burner operation. Burner should operate as
adjusted in step 2. If not, repeat air shutter adjustment compensating for proper burner operation with inner
door closed.
AirShutter Nut
Air Shutter
Page15
15
PDX Series
Burner Cleaning
Step 1.Position gas control power switch to the “OFF” position and unplug heater from wall
outlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and inner door per service procedure XIII on page 35.
Step 4.Disconnect pilot tube (7/16 wrench) and
feedline (¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sensor wire from gas control.
PDX SERVICE PROCEDURE I
Burner Operation Inspection,
Adjustment, Cleaning and Replacement
Igniter/flame
sense wire
Feedline nut
Step 6.Remove burner assembly from combustion chamber.
Step 7.Thoroughly inspect burner surface area and burner port area and
remove any loose debris.
Step 8.For cast iron burners, inspect for any debris build up inside
burner casting.
Burner
surface area
Burner
port area
Step 9.Unscrew burner from main burner
orifice. On cast iron burners, loosen
air shutter nut and unscrew feedline
from burner.
Pilot tubing nut
Main burner
orifice
16
Step 10.Remove main burner orifice from
feedline (½" wrench on steel
burners, 3/8" wrench on cast iron)
inspect orifice, clean or replace if
necessary.
Step 11.Reassemble burner and reinstall into water heater. Restore gas supply
and check for gas leaks.
Step 12To resume operation follow the instruction located on the lighting
instruction label or the lighting instruction located in the installation
and operating manual.
L.P. Main burner
orifice. Left hand
thread
Page16
PDX Series
Pilot Inspection, Testing and Replacement
Step 1.Position gas control power switch to the “OFF” position and unplug heater from wall
outlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and remove inner door per service proceedure XIII on page 35.
PDX SERVICE PROCEDURE II
Pilot testing, Cleaning and Replacement
Igniter/flame
sense wire
Step 4.Disconnect pilot tube nut (7/16 wrench) and feedline nut
(¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sense wire from gas control.
Step 6.Remove burner assembly from combustion chamber.
Step 7.Remove pilot assembly from feedline (¼" nut driver).
Step 8.Visually inspect igniter/flame sense wire for damage. Replace
pilot if damage is found.
Step 9.With a multi-meter set to the ohms setting, check continuity
through igniter/flame sense wire. Replace pilot if no continuity.
Step 10.Visually inspect igniter/flame sense electrode for deterioration.
Replace pilot as necessary. Electrode should not be in contact
with pilot hood, If so, carefully adjust electrode to a gap
distance of 3/32" (.09) from pilot hood.
Step 11.Visually inspect igniter/flame sense electrode for oxidation
build up. Carefully clean any oxidation using very fine emery
cloth.
Step 12.Visually inspect pilot tubing for kinks or cracks. If damage is
found replace pilot.
Ferrule
Pilot
nut
tubing
Igniter/flame sense
wire
Pilot
orifice
Feedline nut
Pilottubing nut
Pilot
hood
Igniter/flame sense
electrode
Step 13.Inspect pilot tubing and pilot orifice for blockage:
a) Remove ferrule nut from bottom of pilot assembly (7/16" wrench).
b) Remove pilot tube and pilot orifice.
c) Inspect pilot tubing and pilot orifice for blockage. Clean
or replace as necessary.
Step 14.Reassemble pilot and install to feedline. Reinstall burner assembly to water heater. Restore gas supply
and check for gas leaks.
Step 15To resume operation follow the instruction located on the lighting instruction label or the lighting
instruction located in the installation and operating manual.
Page17
17
PDX Series
PDX SERVICE PROCEDURE III
Pressure Switch Testing and
Replacement
Pressure Switch Testing
WARNING
120 volt potential exposure. Use caution
making voltage checks to avoid personal injury.
Step 1.Position power switch on gas control
to the “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 1).
Step 3.Carefully remove pressure switch from blower housing (see photo 2)
Exhaust pressure
switch
Pressure switch
wire leads
With steps 1,2 & 3 complete,
disconnect wire leads from
pressure switch.
1
2
PressureSwitch
3
Slide pressure switch in direction of
arrow while tilting slightly away
from blower housing.
Use a multi-meter set to the
ohms setting. With blower off,
check across pressure
switch terminals.
Are switch contacts open?
(no electrical continuity)
Y
Position gas valve power
switch to the “ON” position
and adjust thermostat
to call for heat,
this will start the blower.
Check with multi-meter, do
pressure switch contacts close
with blower running with the
switch in the vertical
postition?
Y
Switch contacts are OK.
See safety circuit trace
(page 30)
N
N
``
Y
Check tubing and
pressure tap on
switch for blockage.
Is there blockage?
Check tubing and pressure tap
on switch for blockage.
Is there blockage?
Y
Clear blockage
Y
N
Is vent
system
blocked
N
N
Is vent system length
Replace switch
(see page 18)
within vent table
specifications
listed on page 7 or 8
Reconfigure vent
system to be
compliant with
vent tables.
Y
Y
N
See blower testing
(page 21)
Is blower OK?
N
Correct blower
problem.
Page18
18
PDX Series
PDX SERVICE PROCEDURE III
Pressure Switch Testing and
Replacement
Exhaust Pressure Switch
Replacement
120 volt potential exposure. Use caution
WARNING
to avoid personal injury.
Step 1.Position gas control power switch
to “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 3).
Pressure Switch
4
5
Step 3.Carefully remove pressure
switch from blower
housing (see photo 4)
Slide pressure switch in direction of
arrow while tilting slightly away
from blower housing.
Step 4.Disconnect tubing from
67
pressure switch.
(see photo 5)
Step 5.Disconnect yellow wires
from pressure switch
(see photo 6)
Step 6.Reconnect wires from step 5 to new pressure switch.
Step 7.Reconnect tubing to new pressure switch.
Step 8.Carefully position pressure switch into blower housing.
Step 9.Position gas control power switch to “ON” position and verify proper heater operation.
Step 10.Replace control access cover from step 2.
Page19
19
PDX Series
PDX SERVICE PROCEDURE IV
Blower Testing and Replacement
Blower Testing
115 volt potential exposure. Use caution when
making voltage checks to avoid personal injury.
Step 1.Position gas control power switch
to “ON” position and adjust control to call for heat.
Step 2.Remove the three screws (Phillips Screw driver)
from control access cover on blower assembly and
remove cover (see photo 8).
Does blower energize Within 2
minutes?
N
9
Does blower energize after 2
minutes, run for 30 seconds
and shut down?
N
Y
tubing from blower.
Pressuretap
Pressureswitch
See pressure switch
Y
Disconnect
pressure switch
(see photo 13)
10
tubing
testing
Page 18
manometer to
pressure tap of
(see photo 11)
Determine voltage
problem and correct.
8
Connect
blower.
1213
Disconnect vent
system from top of
blower and remove
(see photo 15)
With blower running, and exhaust
adapter removed from top of blower,
is there a negative pressure of -2.30"
N
WARNING
exhaust vent
adapter.
Remove exhaust
to -2.60" W.C.?
N
Is there 115vac across blue
and green wires
(see photo 14)
adapter
Y
Y
Replace blower
11
Blower OK
Disconnect cord set
shown in photo 9. Is
there 115VAC across
terminals shown in photo
12
N
Is there 115 VAC at
wall outlet?
Y
Check power cord
for damage.
N
Replace blower
Y
N
Y
Is there 115VAC across
terminals shown in
photo 13 ?
Incorrect supply
voltage polarity
Determine
power source
problem and
correct.
Repair or replace
power cord
Y
N
Replace
cord set
Reconnect cord set shown
in photo 8, is there
115VAC between blue wire
and green ground wire
(see photo 14)
N
Does cord set
N
have electrical
continuity?
Y
Replace gas
control
Y
Replace blower
Green ground
wire
Shown with pressure
switch removed.
14
Blue wire
Page 20
20
PDX Series
PDX SERVICE PROCEDURE IV
Blower Testing and Replacement
Blower removal
Step 1.Position gas control power switch to the “OFF” position.
Step 2.Unplug blower power cord from wall outlet.
Step 3.Disconnect vent system from exhaust adapter on top of
blower.
Step 4.Remove exhaust adapter from blower (blade screw driver)
and retain for use on new blower
Step 5.Unplug cord sets from blower.
Step 6.Remove vertical air intake bracket.
Step 7.Disconnect vertical air intake from blower.
Step 8.Remove the three blower mounting screws
(¼" nut driver).
Vertical air intake
Step 9.Remove blower with gasket from water heater.
Vertical air intake
Remove exhaust adapter
and retain for use on
new blower.
Blower Mounting
Screws
Blower
Cord Sets
bracket
Blower Installation
Step 10.Clean any debris from jacket head of water heater.
Step 11.Set new blower with gasket in place using locating pins on
blower flange to line up with location holes in jacket head.
Be sure not to damage gasket.
Step 12.Secure blower in place using mounting screws from step 8.
Step 13.Slide vertical air intake tee onto blower.
Step 14.Re-install vertical air intake bracket.
Step 15.Re-install exhaust adapter from step 4.
Step 16.Reconnect vent system to exhaust adapter.
Step 17.Reconnect cord sets from step 5.
Step 18.Plug blower power cord into wall outlet.
Step 19.Position gas control power switch to the “ON” position.
Step 20. Verify proper blower operation.
Locating Pins
on blower flange
Pin location holes in
jacket head
Page 21
21
PDX Series
PDX SERVICE PROCEDURE V
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Testing.
Step 1.Position power switch on gas control
to the “OFF” position.
Step 2.Remove tubing from inlet pressure tap.
Step 3.Remove the three screws (Phillips screw driver) from
control access cover on blower and remove cover (see
photo 15).
Step 4.Locate blower temperature switch (see photo 16)
Opens on rise @ approximately 155°F
Auto resets on fall @ approximately 128°F
Disconnect wire leads to
switch. Using a multi-meter
set to the ohms setting, is
there continuity between the
Switch Setting
Cool switch to
below 125°F
switch terminals?
N
Replace switch
(see page 24)
120 volt potential exposure. Use caution
WARNING
to avoid personal injury.
15
16
Blower temperature
switch location
Air mixing inlet
Y
Reconnect wire leads and
observe heater operation. Do
exhaust gas temperatures rise
to or above 175°F?
N
Do switch contacts
open?
N
Switch OK
Y
Y
Replace switch
(see page 23)
N
Do switch contacts
open?
Y
temperature is too
Exhaust
hot.
Common causes for
Common causes for
high exhaust temperature
high exhaust temperature
1. Vent length is below minimum allowable.
1. Vent length is below minimum allowable.
2. Vent diameter not tospecification.
2. Vent diameter not to specification.
3. Restricted dilution air inlet.
3. Restricted dilution air inlet.
4. Missing or deteriorated flue baffle.
4. Missing or deteriorated flue baffle.
5. Gas pressure is outofspecification.
5. Gas pressure is out of specification.
6. Excessively high ambient temperatures.
6. Excessively high ambient temperatures.
Page 22
22
PDX Series
PDX SERVICE PROCEDURE V
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Replacement.
Step 1.Position gas control power switch to the “OFF” position
and unplug heater from wall outlet.
Step 2.Remove the three screws (Phillips screw driver) from the
control access cover on blower and remove cover.
(see photo 17)
Step 3.Locate blower temperature switch (see photo 18)
Step 4.Disconnect red and yellow wire leads from switch.
Step 5.With an appropriate tool such as side cutters, snip the
retaining lug from the blower housing to allow removal of
temperature switch (see photo 19).
120 volt potential exposure. Use caution
WARNING
to avoid personal injury.
18
Blower temperature
17
switch location
Step 6.Remove switch from blower housing.
Step 7.Install new switch. Be sure switch is properly seated in
mounting area.
Step 8.Reconnect red and yellows wires to new switch. Wires are
interchangeable with either terminal.
Step 9.Position gas control power switch to the “ON” position
and verify proper heater operation.
Step 10.Replace control access cover from step 2.
19
Snip retaining lug
from blower housing
Page 23
23
PDX Series
Gas Control Testing
See pages 27 & 28 for gas control
input & output testing.
PDX SERVICE PROCEDURE VI
Gas Control/Thermal Well Testing and
Replacement
Thermal Well Testing
IfControl has gone into TCO lockout due to excessive
tank temperature (four flash, 3 second pause) reset
control by rotating knob oftemperature control to the
minimum setting for at least 6 seconds before returning
to desired temperature setting.
Observe heater operation. If control
continues to lockout due to excessive
tank temperature, proceed to thermal
well testing to determine cause.
Thermal well testing
Position gas control power switch to
the “OFF” position and disconnect
thermal well harness from gas
control.
Using a multi-meter set to the
Ohms setting, determine the
resistance of thermal well sensor
(see caution photos 20 & 21)
Disconnect thermal
well wire harness
20
21
CAUTION
DO NOT use standard multimeter probes for this test. Doing
so will damage connector. Use special pin type electronic
probes or small diameter wire pins inserted into connector.
Using a multi-meter set to the ohms setting, insert one meter probe (see caution)
into center wire position of thermal well connector, insert the second probe (see
caution) into either of the outside wire positions (see photo 20).
24
Alternate the probe on the outside position to the opposite outside wire position
(see photo 21).
Once the thermal well resistance values are known, the water
temperature must also be known to determine if the resistance
values are correct. See page 25 to obtain water temperature.
Are thermal well resistance values correct?
Y
Replace gas control
(see page 27)
N
Replace thermal well
(see page 27)
Page 24
PDX Series
Stored watermay be HOT when performing the following steps in this procedure.
DetermineWaterTemperatureInsideTank
Note: It is important to understand once the resistance for the thermal well is determined from page 25, water flow
through the heater should not occur. Prior to performing the steps below, turn off the cold water supply to the
water heater. This will prevent cold water flow into the tank affecting the resistance value of thermal well.
Step 1.Position gas control power switch to “OFF” position.
Step 2.Draw approximately 4 gallons of water from drain valve into a container and discard. Draw an
additional gallon and immediately measure water temperature using an accurate thermometer. It may
be necessary to open a hot water faucet to allow heater to drain.
PDX SERVICE PROCEDURE VI
Gas Control/Thermal Well Testing and
Replacement
WARNING
Take necessary precaution to prevent personal injury.
Step 3.Using the chart below, determine correct resistance value for the water temperature from step 2.
Example: If temperature of water is 84°F, then the resistance through the sensor would be
8449 (see shaded area). NOTE: Sensor resistance increases as the temperature
falls.
Gas Control & Thermal Well Removal From Water Heater
PDX SERVICEPROCEDUREVI
Gas Control & Thermal Well Testing
and Replacement
GasControl
Step 1.Position gas valve power switch to the “OFF”
position and Unplug Heater from power supply.
Thermal
Well
Step 2.Drain heater to a point below the gas
control level.
Step 3.Turn off gas supply to water heater and
disconnect gas piping from gas control.
Step 4.Disconnect wire harnesses and burner assembly
from gas control.
Step 5.Remove gas control & thermal well by rotating flats of Thermal Well counter clockwise (1-5/16"wrench).
GasControlRemoval FromThermalWell
Follow thesteps below allows removal gas control from thermal well withoutremoving thermal well from tank.
Step 1.Position gas control power switch to the “OFF” position and unplug water heater from power supply.
Step 2.Turn off gas supply to water heater and disconnect gas piping from gas control.
Step 3.Disconnect wire harnesses & burner assembly from gas control.
Step 4.Using gas control service tool (239-45991-00) available from your BWC parts supplier, Insert tool into
back of gas control (see photos below)
View from back of
control for clarity
Insert tool from
back of control
Service tool shown
inserted in to back
of control
Step 5.Pivot tool towards heater as far as possible (see photo below). Lift straight up on gas control. The
control should move about 1/8". Hold control in position and remove tool. Lift straight up on control to
remove completely from Thermal Well.
With service tool inserted,pivot tool back towards water
heater as far as possible. Lift straight up on control, control
will move 1/8".Remove tool andcontinue tolift straight up
on control to remove from Thermal Well.
Page 26
26
PDX Series
Gas Control Assembly to Thermal Well
Step 1.Install threaded end of thermal well into tank. Be sure
thermal well flange is positioned as shown in photo 22
for proper control alignment.
Step 2.Route wire leads back into relief opening.
(see photo 23)
Step 3.Align slots located on thermal well flange with tabs
located on back of gas control (see photo 22 & 23)
PDX SERVICE PROCEDURE VI
Gas Control & Thermal Well Testing
and Replacement
22
Thermal well flange
slots
Step 4.Carefully push control back onto thermal well flange
as far as possible towards water heater. Slide control
down to lock into position.
Step 5.Install burner and connect pilot tubing and feedline nut
to gas control.
Igniter/sensor
connection
Step 6.Reconnect wire harnesses to gas control
Step 7.Reconnect gas piping to gas control.
Ground Wire
connection
Step 8.To resume operation, follow the
5 pin
blowerharnessconnection
3 pinthermalwellconnection
Route wires
through relief
opening
23
GascontrolTabs
per the illustration.
Restore gas supply and check for gas
leaks.
instruction located on the lighting
instruction label or the lighting instruction
located in the installation and operation
manual.
Flammable Vapor
Sensor
Page 27
27
PDX Series
Flammable VaporDeviceTesting
Step 1.Position power switch on gas control to the
“OFF” position.
Step 2.Disconnect flammable vapor sensor from
gas control.
Step 3.Using a multi-meter set to the ohms setting
check resistance of flammable vapor sensor.
(see caution below)
Resistance must be within 3,000 ohms and
48,000 ohms. If outside of this range replace
flammable vapor sensor.
PDX SERVICE PROCEDURE VII
Flammable Vapors Sensor Testing
Flammable Vapor
Sensor
Multi-metersetto
ohms setting
Electronic
“pintype”
Meter Probes
DO NOT use standard multimeter probes for this test. Doing
CAUTION
so will damage connector. Use special electronic “pin type”
probes or small diameterwire pins inserted into connector.
Flammable VaporSensor
28
Page 28
PDX Series
PDX SERVICE PROCEDURE VIII
Safety Circuit Voltage Trace
Safety Circuit Voltage
Trace
NOTE: This procedure assumes a cool tank.
Step 2.Remove three screws (Phillips Screw driver) from control
access cover on blower and remove cover (see photo 24).
Position gas control switch to the “ON”
position and adjust thermostat dial to call
for heat, Is there 10 to 13 VAC between red
wire leading to blower temperature switch
and green ground wire?
Blower must be running during this
voltage check.
(see photo 25)
Y
Is there 10 to 13 VAC between yellow wire
leading from pressure switch and green
ground wire?
(see photo 25)
Y
Is LED on gas valve flashing the
N
N
“heartbeat” code (alternating
Verify 120VAC to gas
control (see page 30)
bright/dim)
120 volt potential exposure. Use caution
making voltage checks to avoid personal injury.
Y
N
WARNING
No voltage from gas control,
call for technical support.
Is there continuity
through blower
temperature switch?
(see page 21)
N
24
Y
Check for loose or
broken wire connection
at switch terminals
Do you hear or can you see
the igniter sparking?
Y
Safety circuit
voltage is OK.
If burner does not light,
observe LED flash code on
gas valve and refer to
troubleshooting section on
page 13
Determine cause of blower
Correct igniter/
sensor problem.
N
Check igniter/sensor
(see page 17)
is igniter/sensor OK?
25
temperature switch activation
and correct.
Faulty cord set or
Y
gas control.
Green ground wire
Red wire leading to
blower temp. switch
Yellow wire
leading from
pressure switch
Page 29
29
PDX Series
PDX SERVICE PROCEDURE IX
120 VAC Trace
120 VAC Circuit Trace
120 volt potential exposure. Use caution
WARNING
making voltage checks to avoid personal injury.
Step 1.Verify 120VAC and proper polarity at wall outlet.
Step 2.With unit plugged in and control power switch in the “ON” position verify LED status.
LED status
None, Control LED not
on or flashing.
Disconnect cord set as
shown in photo 26
Using a volt meter set to
volts AC, is there 120VAC
across terminals shown
in photo 27 ?
Y
Is there 120VAC across
terminals shown in
photo 28 ?
N
Incorrect supply
voltage polarity
N
Y
LED status
Short flash, once every
four seconds.
Waiting for
call for heat.
26
Reconnect cord set
shown in photo 26.
Disconnect wire harness
from gas control
(see photo 29).
LED status
“Heartbeat”, alternates
bright/dim.
Thermostat calling
for heat
Check for damage to AC
supply power cord.
N
Replace Blower
27
Y
Wire harness
LED status
Various flashing error
codes.
Verify error code as
listed on page 12
28
Repair damage
29
30
Locate black & white wires at connector, It
may be necessary to pull back wire sheath
to identify wire colors.
(see photo 30)
Is there 120VAC across
black & white wires as
shown in photo 30?
N
Call for technical
support.
Y
Replace gas
control.
30
Wire sheath pulled back to
identify wire colors
Check for 120VAC between black & white wires.
-NOTE-
Electronic meter probes required. Use care not to
damage connector during this check.
Page30
PDX Series
DipTubeInspectionand Replacement
Water Heater components and stored watermay be HOT when performing the following
steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1.Position on/off switch of gas control valve to “OFF” position and unplug water heater from wall outlet.
Step 2.Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an
open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water
heater and allow heater to drain to a point below the inlet connection nipple.
Step 3.Disconnect inlet nipple from plumbing system.
Step 4With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater.
Use caution not to damage pipe threads.
PDX SERVICE PROCEDURE X
Dip Tube
Inspection and replacement
WARNING
Step 5.Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.
Hydro-jet slots should be open and free of any blockage.
Any damage such as cracks, restriction due to deformation or unintentional holes are not field
repairable and the inlet nipple/dip tube must be replaced.
Step 6.Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water
heater. Connect nipple to plumbing system, resume water supply and refill with water.
Step 7.To resume operation follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
Page31
31
PDX Series
AnodeInspectionand Replacement
Water Heater components and stored watermay be HOT when performing the following
steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1.Position on/off switch of gas control valve to the “OFF” position and unplug water heater from wall
outlet.
Step 2.Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an
open drain. Open a nearby hot water faucet to vent water heater for draining. Open drain valve of
water heater and allow water heater to drain to a point below the outlet connection nipple.
Step 3.Disconnect outlet nipple from plumbing system.
Step 4With an appropriate tool such as a pipe wrench, remove outlet nipple/anode from the water heater. Use
caution not to damage pipe threads.
PDX SERVICE PROCEDURE XI
Anode
Inspection and replacement
WARNING
Step 5.Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is
normal. If depletion is ½ of the original anode diameter (approximately ¾” diameter), replacement is
recommended. If any of the steel core of the anode is exposed, replacement is recommended.
Step 6.Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into water
heater. Connect nipple to plumbing system, resume water supply and refill with water.
Step 7.To resume operation, follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
32
Page32
PDX Series
PDX SERVICE PROCEDURE XII
Flue Baffle
Inspection and replacement
Removeblower togainaccess to
Disconnect vent system
from exhaust adapter.
flue baffle
Step 1.Position gas control power switch to the “OFF” position and
unplug blower from wall outlet.
Step 2.Disconnect vent system from exhaust adapter on top of blower.
Step 3.Disconnect intake air piping.
Step 4.Unplug cord sets from blower. (see photo 31).
Step 5.Remove the three blower mounting screws
(¼" nut driver) (see photo 31).
Step 6.Remove blower with gasket from water heater.
Step 7.Remove flue baffle from Heater (see photo 33).
Step 8.Inspect baffle for deterioration, missing restrictors.
Clean any scale or debris build up. Replace with new baffle as
necessary.
Step 9.Reinstall baffle into flue tube. Be sure baffle
hanger tabs are inserted into notch location at the
top of the flue tube (see photos 34 & 35).
Step 10.Check Burner to insure no scale has accumulated during this
operation. See burner cleaning procedure on page 15.
31
Blower
Cord Sets
32
Remove support
bracket
Blower Mounting
Screws
Step 11.Reinstall blower on water heater. Connect vent
system and cords set to blower. Plug water heater
into wall outlet.
Step 12.To resume operation follow the lighting instruction
located on the lighting instruction label or the lighting instruction
located in the installation and operation
manual.
33
Flue Baffle
3435
Flue tube
notch
Baffle shown
installed in flue
tube notch.
Page33
33
PDX SERVICE PROCEDURE XIII
PDX Series
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
Inner Door Removal Procedure.
Step 1. Slide switch of the Electronic Gas Control to the “OFF” position and unplug from wall.
Step 2. Remove outer jacket burner access door.
Step 3. Disconnect wire connections from Electronic Gas Control.
Step 4. Right side Inner Door Removal.
a) Remove wire tie from feedline.
b) Remove (2) 1/4" hex drive screws from right side inner door.
c) Remove (2) 1/4" hex drive screws from flange section of inner door.
d) Remove right side inner door and set aside. Be careful not to damage gasket material on inner door.
¼" Hex Drive Screws shown on
Right Side Inner Door.
¼" Hex Drive Screwsat
Flange section of Inner Door
Step 4. Fully inspect inner door gaskets for the following:
>Tears>Other imperfection that will inhibit proper seal
>Missing Material>Gasket adhesion to inner door
>Cracks>Material left on combustion chamber (around opening)
>Dirt or debris
If the gasket is not effected by any of the above, gasket replacement is not required. If replacement is
required,
proceed to Inner Door Gasket Replacement Procedure.
Inner Door Gasket Replacement
Procedure.
WARNING
If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury ordeath.
Step 5.After inspection of inner door as noted in step 4, completely remove gasket and adhesive residue from right
and left side inner doors as needed.
Step 6.Use RTV sealant (recommended bead size is 1/8") to secure the inner door gasket to the inner door sections
(right & left). Refer to illustration below for proper application. Note the overlap configuration in the flange
area of the inner door. Set the flange section first, this will help to achieve the proper over lap position.
34
Page34
PDX Series
PDX SERVICE PROCEDURE XIII
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
Installation of Inner Door With
Gasket.
Step 7.Clean any residual gasket residue or other debris
from combustion chamber surface before installing
the inner door/gasket assembly.
Step 8.Place the left side inner door into position first.
Firmly position the radiused channel of the inner
door around the feedline. Using the 1/4”
hex drive
screws from step 3d, secure left side inner door in
place. DO NOT OVER TIGHTEN SCREWS.
Step 9Position thermocouple, pilot tube and Piezo wire
against left side inner door flange gasket. DO
NOT ROUTE THROUGH RADIUSED
CHANNEL WITH FEEDLINE.
WARNING
Stripped fastener connections may allow
for seal breach of innerdoor. A seal
breach may result in a fire or explosion
causing property damage, personal
injury ordeath. Do not over tighten
screws in steps 8, 10 and 11.
If a fastener connection is stripped,
contact the manufacturer listed on the
water heaterrating plate.
Igniter wire and pilot tube
shown in proper position.
Radiused Channelfor
Feedline
Page35
35
PDX SERVICE PROCEDURE XIII
PDX Series
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
Installationof inner door with gasket (continued from page 36).
Step 10.Firmly place right side inner door flange against the left side inner door flange and secure with two ¼” drive
screws from step 3c. DO NOT OVER TIGHTEN SCREWS.
Step 11.Align right side inner door to combustion chamber and verify the fastener holes of the combustion
chamber are aligned with the right side inner door slotted opening. Verify seal integrity around
combustion opening. Secure right side inner door using 1/4” hex drive screws from step 3b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and
sealed against the
combustion chamber
Verify threaded hole
alignment with slotted
openings in inner door.
Step 12.Replace outer jacket burner access door.
Step 13.To resume operation follow the instructions located on the lighting instruction label or the lighting instructions
located in the installation and operation manual.
36
Page36
PDX Series
Frozenintake or exhaust vent terminal
If an intake or exhaust vent terminal is blocked with ice or snow due to severe conditions, the pressure switch and control
will not allow the burner to operate. This will result in a three flash error code. Once the blockage is removed (through
melting or other means) the controls will let the burner operate. The position of the vent terminals in relation to each other
and terminals from other appliances can have an effect on the potential for blockage due to ice or snow. See the
installation instructions for recommended positioning of the terminals.
Testing under severe conditions has shown that the optional concentric vent terminal is resistant to ice blockage. Contact
Bradford White or the supplier of the water heater for information about ordering the optional concentric vent terminal.
Bradford White has also developed an air intake relief device that can be installed in the air intake near the water heater
temporarily enabling the water heater to operate with a frozen intake terminal. Contact Bradford White or the supplier of
the water heater for information about the air intake relief device.
Page37
37
PDX Series
BTUBritish Thermal Units
GPMGallons per Minute
HzHertz
KW/hKillo-watts per hour
LEDLight Emitting Diode
NPTNational Pipe Thread
OhmsOhms of resistance
PSIPounds per Square Inch
RPMRevolutions per Minute
TCOTemperature Cut Off
VACVolts Alternating Current
W.C.Inches of Water Column
°CDegrees Centigrade
°FDegrees Fahrenheit
Glossary of Terms
NOTES
38
Page38
PDX Series
Parts List
1. Blower Assembly
2. BlowerTemp. Switch
3. PressureSwitch
4. BlowerGasket
5. TeeandVentPipe Assy.
6. Vent Adapter withTerm.
7. IntakeTerminal
8. VentTerminal Elbow
9. Exhaust Adapter
10. CondensateHose Kit
11. Flue Reducer
12. HeatTrap Insert (outlet)
13. HeatTrap Insert (inlet)
14. HotWater Outlet Anode
15. ColdWater InletDiptube
16. Flue Baffle
17. BlowerHarness
18. T&PRelief Valve
19. ¾ NPT PLUg
20. DirectVentBoot
Escutcheon
21. Air IntakeBoot
22. Air IntakeBoot Gasket
23. OuterDoor
24. RightSide InnerDoor
25. Left Side Inner Door
26. Screw-#10-12 x ¾ HWH
27. Screw-#8-18 x ¾ HWH
28. BrassDrainValve
29. Flammable Vapor Sensor
30. SensorHarness
31. FlammableVaporSensorClip
32. Thermal Well
33. GasControl Kit
34. GasControl Servicetool
35. GasControl
6. Gas
3
37. GasBN burner (Nat.)
38. MainBurner Orifice (Nat.)
39. GasPilot Assembly (Nat.)
40. GasPilot Orifice (Nat.)
Burner Assy (Nat.)
41. Gas Feedline (Nat.)
42. GasBurner Assy (L.P.)
43. Cast IronBurner (L.P.)
44. GasPilot Assy (L.P.)
45. GasPilot Orifice (L.P.)
46. AirShutter (L.P.)
47. LP Gas Feedline (L.P.)
48. AirShutter Nut (L.P.)
49. MainBurner Orifice (L.P.)
50. InnerDoorGasket
51. HeatTrap Insert kit
52. MixingValve
Page39
39
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.