PC3F2699IUF00 Hydronic 
Circulating 3 Speed Pump
APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is 
designed for applications in closed-loop hydronic heating and 
cooling systems, as well as in solar-powered systems. The 
pump is non-submersible and for use in dry, frost-free, wellventilated installations.
SPECIFICATION DATA
SPECIFICATIONS
Rate of flow: up to 34 gpm (128.7 lpm)
Pressure head: up to 31 ft (9 m)
Voltage: 
115VAC +/-10% 60hz
Amperage: See “Speed switching” on page 2.
Max. Pressure:
145 psi (at room temperature); 
50 psi (at 200°F [93°C])
Temperature Range:
Ambient temperature: 32°F to 104°F (0°C to 40°C) 
Media temperature: 14°F to 230°F (-10°F to 110°C) [to 200°F 
(93°C) with optional check valve installed]
Storage Temperature: -40°F to 100°F (-40° to 66°C)
Standards:
Insulation Class F 
Temperature Class FT 95
Fig. 1. Pump dimensions in in. (mm).
L1 L2 L3 L4 L5
6.5 (165.5) 6.1 (155) 6.5 (165.5) 7.75 (197) 3.2 (80.2)
Shipping weight: 9.5 lbs (4.32 Kg)
68-3084-02

PC3F2699IUF00 HYDRONIC CIRCULATING 3 SPEED PUMP
M32833A
0
5
10
15
20
25
30
0 5 10 15 20 25 30 35
1
 PC3F2699IUF00
WITHOUT CHECK VALVE
WITH CHECK VALVE
3
1
2
H
(FEET)
US GPM
Materials
Component Material
Pump body Cast iron
Impeller Polyamide
Shaft Ceramic
Bearing Ceramic
Bearing plate Stainless steel
Can Stainless steel
Control: 3-step switch with manual speed selection
Motor protection
The motor includes an internal thermal overload protection. 
External motor protection is not required.
Speed switching
Three speed, with manual selector.
Speed Volts Amps Watts
1
21.52 175
115
31.78205
Flange Connections
Universal flange 
Bolt hole spacing 3-5/32 in. (80.2 mm) 
Bolt holes 1/2 in. (12.7 mm)
1.09 125
Media
Clean water or water with up to 20% glycol. Up to 50% glycol 
may be used, but flow characteristics will differ from these 
specifications.
Fig. 2. Flow curve characteristics.
Optional and Replacement Parts
Check valves: PCV125 
Flange gasket: PCG100
Table 1. Cross Reference for Pump Replacement
Bell & 
Honeywell Grundfos Taco
Model Pump
Length
PC3F2699IUF00 6.5”
Speed Single 
Speed
High UP26-96F
UP26-96F-FC 
UP26-116F
UP26-116F-FC
Medium UP26-64F
UP26-99FC
3-Speed Single 
UPS26-99 High 
UPS26-99-FC High
UPS26-99 Low 
UPS26-99-FC Low
3-Speed Single 
Speed
0011F 
0011F-IFC 
0013F 
0013F-IFC
0014F 
0014F-IFC
Gossett Armstrong Wilo
Speed
NRF-36 Med 
NRF-45 Med 
H-41
E7 
Astro 50 
Astro 50-3
Star 30F 
Star 32F
Star 17 FX S21 Med
S21 High
Low NRF-33 Star S21 Low
The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if 
information is found to be incorrect. 
If the cross-referenced model uses a flow check valve, then use a flow check with the Honeywell model as well. 
Each Honeywell circulator replaces both regular and rotated flange models.