Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of
an automatic fire alarm system (as described above) and a life
safety communication system that may include an autonomous
control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods—can broadcast a mass notification message. Such a
system, however, does not assure protection against property
damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises following
the recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no charge
to all installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-type
sensing chambers tend to detect fast-flaming fires better than
smoldering fires. Because fires develop in different ways and
are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide
adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches
(especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority over
a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly disseminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear
a fire alarm signal, do not respond to or comprehend the
meaning of the signal. Audible devices, such as horns and
bells, can have different tonal patterns and frequencies. It is
the property owner's responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm
signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line
failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt, or high air
velocity require more frequent maintenance. A maintenance
agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be performed by authorized professional life safety system installers
only. Adequate written records of all inspections should be kept.
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH™, NIS™, NOTI•FIRE•NET™, eVance™, and SWIFT™ are all trademarks; and Acclimate® Plus, FAAST®, FlashScan®, NION®, NOTIFIER®,
ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark
and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a
specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
Section 1: General Information................................................................................................7
1.1: UL 864 Compliance.......................................................................................................................................7
1.1.1: Products Subject to AHJ Approval......................................................................................................7
1.1.2: Programming Features Subject to AHJ Approval ...............................................................................7
1.2: About This Manual ........................................................................................................................................8
1.2.1: Cautions, Warning, and Notes.............................................................................................................8
1.2.3: Supplemental Information ...................................................................................................................9
1.2.4: Shortcuts to Operating Functions ......................................................................................................10
1.3: Introduction to the Control Panel ................................................................................................................10
1.5: How to Enter a Password.............................................................................................................................11
2.2: How to Enter Programming.........................................................................................................................14
2.4: The Network Program .................................................................................................................................47
2.5: The Utility Program.....................................................................................................................................48
2.7: Setting the Baud Rate of Serial Ports ..........................................................................................................50
2.7.1: Printer Serial Port ..............................................................................................................................50
2.7.2: CRT Serial Port .................................................................................................................................51
3.2: How to Enter Status Change........................................................................................................................52
3.3: Disable or Enable a Point ............................................................................................................................53
3.6: Clearing the History Buffer .........................................................................................................................55
3.7: Setting the System Time and Date...............................................................................................................55
3.8: Walk Test .....................................................................................................................................................56
3.8.1: Basic Walk Test.................................................................................................................................57
3.8.2: Advanced Walk Test .........................................................................................................................58
3.8.3: Walk Test Activation Indications......................................................................................................58
3.8.4: Viewing Walk Test Results ...............................................................................................................59
A.5: Auxiliary Control Functions .......................................................................................................................91
B.1: Presignal and Positive Alarm Sequence (PAS) ...........................................................................................92
B.1.1: What is Presignal and PAS?..............................................................................................................92
B.1.2: Selecting Presignal and PAS Outputs ...............................................................................................93
B.2: Time Control Zones.....................................................................................................................................93
B.3: Coding Functions for NACS .......................................................................................................................93
C.2: Features .......................................................................................................................................................95
C.2.1: Drift Compensation and Smoothing .................................................................................................95
C.2.2: Maintenance Warnings – Three Levels ............................................................................................96
D.2: Input and Outputs......................................................................................................................................106
E.2: System Testing and Detector Initialization................................................................................................110
E.3: How to Replace a Detector.................................................................................................
.......................110
E.4: How to Manually Initialize a Detector ......................................................................................................111
F.1: What are Type Codes? ...............................................................................................................................112
F.2: How to Select a Type Code........................................................................................................................112
F.3: In this Appendix .........................................................................................................................................112
F.4: Type Codes for Input Devices....................................................................................................................112
F.4.2: Type Codes for Intelligent Detectors ..............................................................................................112
F.4.3: Type Codes for Monitor Modules ...................................................................................................114
F.5: Type Codes for Output Devices .................................................................................................................115
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
A complete listing identifying which products have or have not received UL 864 9th Edition
certification is located in the installation manual of this fire alarm system. Those products which
have not received UL 864 9th Edition certification may only be used in retrofit applications.
Operation of the NFS2-640/E with products not tested for UL 864 9th Edition has not been
evaluated and may not comply with NFPA 72 and /or UL 864. These applications will require the
approval of the local Authority Having Jurisdiction (AHJ).
1.1.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below
must be approved by the local AHJ.
Table 1.1 Programming Settings
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values
or not used at all as indicated below.
Program Feature or OptionPermitted in UL 864? (Y/N)Possible SettingsSettings Permitted in UL 864
IP downloads over a local area network
(LAN) or the internet (WAN - WIde Area
Network)
The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-NOT) provides the current
document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable)Document Number
Device Compatibility Document15378
Fire Alarm Control Panel (FACP) and Main Power Supply InstallationDocument Number
NFS2-640/E Installation, Operations, and Programming Manuals52741, 52742, 52743
SLC Wiring Manual51253
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming UtilityDocument Number
Ver iFir e
Veri•Fire Medium Systems Help File
Cabinets & ChassisDocument Number
CAB-3/CAB-4 Series Cabinet Installation Document15330
RM-1 Series Remote Microphone Installation Document51138
RA100Z Remote LED Annunciator Installation DocumentI56-0508
Table 1.3 Related Documentation (2 of 2)
1.2.4 Shortcuts to Operating Functions
To the left of each program function, you’ll find a keypad shortcut, which contains
a series of keypad entries required to access the program function. All shortcuts
start with the control panel in normal operation.
For example, the keypad shortcut to the left shows how to enter the Read Status
function with the control panel in normal operation.
1.3 Introduction to the Control Panel
The NFS2-640 is an intelligent, field-programmable Fire Alarm Control Panel. Field-programming
the control panel lets you customize the fire alarm system by selecting and setting program options
for intelligent/addressable detectors and modules, and Notification Appliance Circuits (NACs).
This manual provides information for programming using the NFS2-640 keypad connected to the
control panel. VeriFire™ Tools must be used for programming if no keypad is used, or if a network
control annunciator is used as the keypad in either a network or standalone application. Refer to
VeriFire™ Tools for information on programming without the NF2S-640 keypad, and the NF2S-640 Installation Manual and NCA-2 Manual for installation information.
For details on control panel operation, refer to the NFS2-640 Operations Manual.
The NF2S-640 provides two methods for field-programming the control panel:
• Local programming – program directly from the control panel keypad to reduce installation
time.
• PC programming – input long data entry programming information on a PC; transfer
programming data between a PC and the control panel using VeriFire™ Tools programming
utility.
• Security – use passwords to control access to the control panel and protect memory.
• 80-Character (2x40) Liquid Crystal Display – view programming and device information on
the control panel.
1.5 How to Enter a Password
The control panel provides two types of selectable passwords:
•Program Change
•Status Change
Listed below are uses and the factory-setting for each password type:
Table 1.4 Programming Passwords
Password
type
Program
Change
(high level)
Status Change
(low level)
Use to
Enter Program Change option to program
essential control panel functions, including basic
system functions and utility options.
Enter Status Change option to program minor
functions.
REGION=0 TBL.REMIND=2 ALA.SCROLL=N
LOCAL CONTROL=0
FLASHSCAN L1DET L1MOD L2DET L2MOD
NYNY
Program Change is the programming level that lets you change the essential control panel
functions, such as point programming, changing passwords, changing system functions. Included
are four options: Basic Program, Network, FlashScan Poll, and Utility Program.
The structure of the Program Change option is shown below:
Section 2: Programming
This section contains instructions and sample screens for using the Programming selections:
Figure 2.1 Program Change Selections
• Basic Program The Basic Program lets you program essential functions, such as clearing
the program, Autoprogramming the system, programming points, and setting system
functions. Refer to “Basic Program” on page 14.
• Network Program The Network Program allows programming of network channel
thresholds, network node number, and wiring style.“The Network Program” on page 47.
• Utility Program The Utility Program screen provides selections for selecting a Trouble
Reminder per NFPA, a Region setting, and enabling or disabling local control of the
ACKNOWLEDGE/SCROLLDISPLAY, SIGNALSILENCE, SYSTEMRESET and DRILL keys. Refer to
“The Utility Program” on page 48.
• FlashScan Poll The FlashScan Poll screen provides the option for selecting between CLIP
1.At the “SYSTEM NORMAL” screen, press the
“Entry” screen, as shown below:
2.At the “Entry” screen, press the 1 key. The control panel displays the “Enter Password” screen
as shown below:
3.Enter your Program Change password (See “How to Enter a Password” on page 11). The
control panel displays the “Program Change Selection” screen, as shown below:
4.Select a Program Change selection: 1, 2, 3 or 4.
2.3 Basic Program
From the “Program Change Selection” screen, press the 1 key to display the “Basic Program”
screen which provides nine (9) options as shown below:
ENTER key. The control panel displays the
Press the number of any one of the nine (9) options as detailed below
Option 0=CLR - Clears all existing user programming. For details, refer to How to Clear Memory
(0=
CLR) on page 15. Note: The user is prompted to double-check that this is what is really wanted.
Option 1=AUTO - Add or remove addressable devices to the control panel program. For details,
refer to How to Autoprogram the Control Panel (1=
AUTO) on page page 15.
Option 2=POINT - Modify or delete a point. For details, refer to “How to Modify or Delete a
Point (2=
POINT)” on page page 19.
Option 3=PASSWD - Change the Program Change or the Alter Status password. For details, refer
to “How to Change a Password (3=
PASSWORD)” on page page 25.
Option 4=MESSAGE - Edit the 40-character message that displays on the first line. For details,
refer to “How to Create a System Message (4=
MESSAGE)” on page page 26.
Option 5=ZONES - Edit the 20-character custom zone label for zones 01-99. For details, refer to
“How to Create a Custom Zone Label (5=
ZONE)” on page page 27.
Option 6=SPL FUNCT - Program Releasing Zones and Special Zones. For details, refer to “How
to Program Special Zones (6=
SPLFUNCT)” on page page 27.
Option 7=SYSTEM - Program Global System Functions. For details, refer to “How to Change
Global System Functions (7=
SYSTEM)” on page page 31.
Option 8=CHECK PRG - Check the program for errors. For details, refer to “How to Check the
Program for Errors (8=check prg)” on page 47.
PRESS ENTER TO CLEAR ENTIRE PROGRAM
OR ESCAPE TO ABORT
Program Change
Password
2.3.1 Clear Memory (0=CLR)
The Clear option removes all programming information from control panel
memory. If installing the control panel for the first time, use option 0 to clear
control panel memory. To do so, follow these steps:
1.From the “Basic Program” screen, press the 0 (zero) key to display the Clear Program screen.
The control panel prompts for verification as shown below:
2.Press the
ENTER key to clear control panel memory or press the ESC key to exit the screen
without clearing.
2.3.2 Autoprogram the Control Panel (1=AUTO)
Purpose
The Autoprogram option identifies all addressable devices connected to the control panel. Devices
include addressable detectors and modules connected to SLC 1 or SLC 2, and NACs. You can use
the Autoprogram option to create a new program and add or remove devices. A summary of the
Autoprogram functions, when to use the functions, and where to find information on using the
functions is found below:
Add one or more
SLC-connected detectors
and modules to an
existing program
Remove one or more
SLC-connected detectors
and modules from an
existing program
A new control panel or a control panel with no
existing program in memory.
A program exists in memory and you want to
add a detector or module to the existing
program—without modifying information for
existing detectors and modules.
A program exists in memory and you want to
remove an installed detector or module from
the existing program—without modifying
information for existing detectors and
modules.
“Create a New Program for the
Control Panel” on page 15
“Add a Device to the Program”
on page 16
“Remove a Device from the
Program” on page 17
View system defaultsA program exists in memory and you want to
view system settings assigned during
Autoprogram, such as custom labels,
passwords, and so on.
Page 19 “Change Autoprogram
Default Value” to see the system
defaults
Create a New Program for the Control Panel
This section covers how to use the Autoprogram option to create a new
program for the control panel. The control panel will identify all addressable
detectors and modules connected to the SLC.
To create a new program for the control panel, follow these steps:
1.Use the Clear option to clear program information from memory. For instructions on clearing
memory, refer to “How to Clear Memory (0=
NOTE: Once Step 1 is completed, Step 2 will cause the panel to assess whether a loop is
comprised of all FlashScan devices or not. If they are all FlashScan, autoprogramming will
change the loop setting to FlashScan if it was not already at that setting. If the devices are not all
FlashScan, autoprogramming will not make a change to the default setting of CLIP. (See
“FlashScan Poll” on page 49 for FlashScan settings.)
CLR)” on page page 15.
2.From the “Basic Program” screen, press the 1 key to start Autoprogram. While the control
panel scans the system to identify all SLC devices and NACs, it displays the following screen:
When the autoprogram is finished identifying SLC devices and NACs, it displays a summary
screen that gives a count of all the devices it has located. Refer to the following screen for an
example of this display.
SB represents detectors with B200 series sounder bases. Refer to VeriFire Tools for B200 sounder
base programming.
3.Press
ENTER. All devices are automatically accepted during initial autoprogramming. The
following screen displays briefly, followed by the
SYSTEMNORMAL screen.
To edit the autoprogramming default values for a point, refer to “How to Modify or Delete a Point
(2=
POINT)” on page page 19.
To edit the autoprogram default values assigned to all modules and detectors during
autoprogramming, refer to “Change Autoprogram Default Values” on page 18.
Add a Device to the Program
You can also use the Autoprogram option to add addressable devices to the control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not
change program information for installed and programmed devices. However, it will assess
whether a loop contains all FlashScan devices and change the loop setting to FlashScan if
necessary.
The following steps describe how to add a new detector at SLC address 1D147 with 10 detectors in
the existing program:
1.Physically install the addressable detector to SLC 1 at address 147 (for instructions, refer to the
NF2S-640 Installation Manual and the installation document that comes with the detector).
2.From the “Basic Program” screen, press the 1 key to start Autoprogram. The Autoprogram
Prompt screen appears in the LCD display as the control panel identifies addressable devices.
When finished identifying addressable devices, the control panel displays information for the
new detector at SLC address 1D147 on the LCD display as shown below:
3.Press the ENTER key to add detector 147 to the program with the default program information.
If you want to change the default information, use the programming keys to do so, then press
the
ENTER key to add detector 147 to the program.
The Autoprogram Summary screen appears. You can verify addition of the detector to the
program by noting the new count of detectors as shown below:
4.Press the
ENTER key, then press the esc key to save the program in memory and return to the
“Basic Program” screen).
Remove a Device from the Program
You can also use the Autoprogram option to remove addressable detectors and modules from the
control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not
change program information for installed and programmed devices.
The following steps describe how to delete a detector at SLC address 1D133 with 11 detectors
connected to SLC 1 in the existing program:
1.Disconnect and remove the detector from SLC 1 at address 1D133.
2.From the “Basic Program” screen, press the 1 key to start Autoprogram. The Autoprogram
Prompt screen displays while the control panel identifies addressable devices.
3.When finished identifying addressable devices, the control panel displays a screen, indicating a
missing detector at SLC address 1D133 as shown below:
4.Press the
ENTER key to delete detector 1D133 from the program.
The Autoprogram Summary screen appears. You can verify removal of the detector from the
program by noting the new count of detectors as shown below:
5.Press the
ENTER key, then press the ESC key to save the program in memory and return to the
NOTE: The FCM-1-REL has an inherent two second
delay, which must be factored into the DELAY TIME
and SOK (soak time) entries.
Change Autoprogram Default Values
To assign system default values from the basic program screen, Press 0 (clear), then press 1
(autoprogram). Refer to the chart below for default values and how to modify them.
Table 2.1 Autoprogram Defaults (1 of 2)
FunctionDefault ValuesTo Alter, refer to
Software
Zones
01-99
F0PRG PRESIGNAL FUNCT PRESIGNAL DELAY
Releasing
Zones
R0-R9
Default custom label “Zone xx” where xx is the
number of the zone
Note: Zone 00 is reserved for a general alarm.
DELAY=180 PAS=NOF00
PRG RELEASE FUNCT RELEASE CONTROL
DELAY=00 ABORT=ULI CROSS=N SOK=0000
“How to Create a Custom Zone Label (5=
“F0 (Presignal/PAS) The Presignal screen provides fields for
changing the delay time or PAS. For details on Presignal
selections, refer to “Presignal and PAS Time” on page 92. From
the Special Function Change screen, press the F key, then
press the 0 key to display the Presignal Function screen.” on
page 29
“R0-R9 (Releasing Functions) The Releasing Function screen
provides fields for changing releasing functions: Delay Timer,
Abort Switch, Cross Zone, and Soak Timer. For details on
releasing applications, refer to “NFPA Releasing Applications”
on page 61.” on page 29 and “How to Program a Releasing
Zone” on page 61.
ZONE)” on page 27
F5 and F6 PRG TIME FUNCTIONTIME CONTROL
ON=**:** OFF=**:** DAYS=********
F7PRG HOLIDAY FUNCTION **/** **/** **/**
**/** **/** **/** **/** **/** **/**
F8PRG CODING FUNCTION CODE TYPE
MARCH TIMEF08
F9PRE-ALARM FUNCTALERT
F09
System
Parameters
Passwords Default programming passwords are:
SYSTEM
NORMAL
message
SIL INH=0000 AUTO=0077
0 VERIFY=30 USA TIME
TERM=N AC_DLY=Y LocT BLINK=01 ST=4 ACS=N
Program Change=00000
Status Change=11111
(YOUR CUSTOM SYSTEM MESSAGE HERE)
SYSTEM NORMAL 10:23A 041508 Tue
A message, along with the current day, time, and
date, that displays on the second line of the LCD
display during normal operation.
“F5-F6 (Time Control Functions) The Time Control screen
provides fields for changing the start time, stop time, or days of
the week. For details on time selections, refer to “Time Control
Zones” on page 93. From the Special Function Change screen,
select F5 or F6 to display the Time Control screen:” on page 30
“F7 (Holiday) The Holiday screen provides fields for specifying
up to nine holiday dates. For details on holiday selections, refer
to “Time Control Zones” on page 93. From the Special Function
Change screen, press F7 to display the Holiday screen:” on
page 30
“F8 (Coding Function) The Coding Function screen provides
fields for specifying one of the following coding functions: March
Time, Two-stage, California, Temporal, Two-Stage Canada (3
minutes), Two-Stage Canada (5 minutes), Two-Stage Canada
Manual, System Sensor Strobe, Gentex Strobe, and Wheelock
Strobe. For details on selecting coding functions, refer to
“Coding Functions for NACS” on page 93. From the Special
Function Change screen, press F8 to display the Coding
Function screen:” on page 30
“F9 (Pre-Alarm) The Pre-Alarm screen provides fields for
programming the Alert or Action Pre-Alarm functions. For
details on Pre-Alarm selections, refer to “Pre-Alarm” on
page 99. From the Special Function Change screen, press F9
to display the Pre-Alarm screen:” on page 31
“How to Change Global System Functions (7=
page 31
“How to Change a Password (3=
Note: The second line, “SYSTEM NORMAL”, is a standard
system message that you cannot change
DCC Mode Default setting is N, no DCC participation.“The Utility Program” on page 48
(YOUR CUSTOM SYSTEM MESSAGE HERE)
SYSTEM NORMAL 10:23A 041508 Tue
The first line of the LCD display contains 40 blank
characters for a custom message.
Default setting is zero (0), IP Access not enabled.“The Utility Program” on page 48
“How to Create a System Message (4=
page 26
MESSAGE)” on page
2.3.3 Modify or Delete a Point (2=POINT)
After programming all SLC-connected devices into the system, you can
modify or delete points. From the “Basic Program” screen, press the 2 key to
display the Point Programming screen:
To modify a point for a detector, module, or NAC: press the 1 key to display
the “Modify Point” screen.
NOTE: When programming points, take the following into design consideration:
Each general zone must be dedicated to a single event type (i.e. Fire, MN, Security, etc.)
Map inputs only to general zones designed for the input’s event type. For example, map mass
notification devices to general zones designed for mass notification.
Outputs can be mapped to multiple general zones that are dedicated to different event types. For
instance, a single output can be mapped to an MN general zone and a Fire general zone.
To delete a point for a detector, module, or NAC: press the 2 key to display the “Delete Point”
screen.
20-character user-editable custom label (in
this example, autoprogramming has used
the first 19 and left a space at the end.)
SLC Loop number
Alarm sensitivity level
Pre-alarm sensitivity level
Cooperative multi-detector
mode indicator
Alarm verification setting
The Modify Point and Delete Point screens let you edit or delete points for a detector, a monitor or
control module, or NAC. To select a point, follow these steps:
To selectDo the followingRefer to
an addressable
detector
an addressable monitor
module
an addressable control
module
a NACPress
Press
Type the SLC number (1 or 2) and
detector (D) and address (001-159)
Press
Press
Type the SLC number (1 or 2) and module
(M) and address (001-159)
Press
Press
Type the SLC number (1 or 2) and module
(M) and address (001-159)
Press
Type the NAC address (01-04)
Press
The next four sections describe how to program the points selected.
Modify an Addressable Detector Point
This section contains a sample detector programming screen, detector default selection, and
instructions for modifying a detector point. Autoprogram default values for a detector are shown:
“Modify an Addressable Detector
Point” on page 20.
“Modify an Addressable Monitor
Module Point” on page 22.
“Modify an Addressable Control
Module Point” on page 23.
20 character custom label. Change by placing the cursor into the first space of the field using the arrow
Press the
Type Code selections. See F.4.2 on page 112 for lists and descriptions.
keys, then typing the descriptor. DETECTOR ADDR 1D101 is the
autoprogram default custom label for the detector at address 101 on SLC 1.
NEXT or PREVIOUS Selection keys to scroll through valid detector
Basic ProgramProgramming
Zone 01 (Heat detectors)
Zone 02 (Ion detectors)
Zone 03 (Photo detectors, Beam detectors)
Zone 04 (Laser detectors)
Zone 05 (Multisensor)
A8 (Photo)
A6 (Ion)
A6 (Laser)
A5 (Multisensor)
P8 (Photo)
P6 (Ion)
P6 (Laser)
P5 (Multisensor)
Table 2.2 Detector Program Values
FieldDescriptionSet as Follows
Extended
Label
12 character custom label
extension.
CBE ListFive zones can be listed - one
zone, Z03, is shown in the
example. Up to 4 more could
be added to this detector.
Alarm
Sensitivity
The alarm sensitivity level,
with 9 the least sensitive
alarm level and 1 the most
sensitive alarm level.
Pre-alarm
level
Shows the Pre-Alarm level
setting—a number between 0
and 9—as follows:
0 – no Pre-Alarm
1 – self optimizing
2 – most sensitive Pre-Alarm
level
9 – least sensitive Pre-Alarm
level
See “Custom Label” above.
Note that spaces must be input by the user, including any space necessary
between the custom and extended label fields. An 80-column printout will
run the two fields together.
Zones can be changed or added to the CBE list by placing the cursor in the
zone field using arrow keys, then typing.
Defaults:
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in
the field using the arrow keys, then either pressing the
NEXT or PREVIOUS
keys to make the selection, or typing the value.
Defaults:
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in
the field using the arrow keys, then either pressing the
NEXT or PREVIOUS
keys to make the selection, or typing the value.
Defaults:
Cooperative
Multidetector
mode
Alarm
verification
Indicates the cooperative
multi-detector mode (A in the
example).
Indicates the alarm
verification setting (V in the
example).
Select by placing the cursor in the field using the arrow keys, then either
pressing the
NEXT or PREVIOUS keys to make the selection, or typing the
value.
* = OFF (Default)
A combines the detector's alarm decision with the next address above
B combines the detector's alarm decision with the next address below
C combines the detector's alarm decision with the next address above and
the next address below
Indicates Alarm Verification (V=on, *=off). Select by placing the cursor in the
field using the arrow keys, then pressing the
NEXT or PREVIOUS keys to make
the selection. Refer to “Interpreting a Detector Status Display or
Maintenance Report” on page 104 for more information on the alarm
verification feature.
Note: Do not use this setting when an alarm activation requires activation of
two or more automatic detection devices.
PROGRAM MONITOR WESTERN ENTRANCE AND
HALLWAY 09 __ __ __ __ 2M101
20-character user-editable custom label.
Modify an Addressable Monitor Module Point
When you select a point address, the control panel returns a screen that displays information about
the point. Below is an example of information for a monitor module (2M101) in the LCD display:
Custom Label20 character custom label. Change by placing the cursor into the first space of the field
Extended Label 12 character custom label extension.See “Custom Label” above.
CBE ListFive zones can be listed - one zone,
Z09, is shown in the example. Up to 4
more could be added to this module.
Press the
valid monitor module Type Code selections. Lists and
descriptions are in See Table F.2 on page 114.
using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any space
necessary between the custom and extended label fields. An
80-column printout will run the two fields together.
Zones can be changed or added to the CBE list by placing the
cursor in the zone field using arrow keys, then typing.
See Table 2.4 on page 22 for defaults.
NEXT or PREVIOUS Selection keys to scroll through
When finished modifying a point, press the
ENTER key; then press the NEXT or PREVIOUS key to
select another point.
Monitor Module Default Zone Assignments
Listing of the monitor module address range and the default zone assignment for each range:
NOTE: On a control module, the default zone is always set to Zone 00 (general alarm).
Modify an Addressable Control Module Point
When you select a point address for modification, the control panel returns a screen that displays
information about the point. For example, the illustration below shows sample information for a
control module (2M101) in the LCD display.
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1.From the programming screen, use the arrow keys to move to a field that you want to modify.
See below for descriptions and settings.
Table 2.5 Modifying Control Module Programming Selections (1 of 2)
FieldDescriptionSet as follows:
Type CodeSpecifies the function of the control
module
Custom Label20 character custom label. Change by placing the cursor into the first space of the
Extended
Label
CBE listUp to five software zones can be
Switch InhibitSpecifies if an operator can manually
SilenceableSpecifies if an operator can manually
12 character custom label extension.See “Custom Label” above.
entered to define the output responses
of the control module based on
various initiating conditions (events)
activate an output
silence an activated output
Press the
through valid control module Type Code selections (listed
in Table F.3 on page 115)
field using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any
space necessary between the custom and extended label
fields. An 80-column printout will run the two fields
together.
Type the number of up to five zones, including E0-E9, F0F9, L0-L9, R0-R9, and zones 00-99. The first zone default
is Z00 (general alarm).
Type one of the following entries.
I = Switch Inhibit enabled
* = no switch inhibit (default for all but releasing circuits)
Type one of the following entries.
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
If the “Strobe” Type ID is used with System Sensor,
Gentex or Wheelock Strobe synchronization,“*” will
silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit,
and resound will occur according to the above definitions.
The address of a NAC connected
through NAC 1 (B01), NAC 2
(B02), NAC 3 (B03), or NAC 4
(B04)
Five zones for CBE list; the default zone
selection is 00 (general alarm)
Default zone
12 spaces for extended
custom label
Switch Inhibit: I=selected; *=off (default)
Walk Test Selection: *=off (default);
W=selected
Silenceable: O=selected; *=off (default)
Type Code
20-character user-editable custom label
PROGRAM CONTROL Notification Dev No1
00 __ __ __ __ *OW B01
Table 2.5 Modifying Control Module Programming Selections (2 of 2)
FieldDescriptionSet as follows:
Walk TestSpecifies if outputs sound during Walk
Te st
Type one of the following entries.
W = devices sound (Basic Walk Test)
* = devices do not sound (Silent Walk Test) (default)
2.When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to
select another point.
Modify NAC Points
Modifying NACs (four NACs on the NFS2-640) is like modifying control modules—except for the
Type Code and device address.
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1.From the programming screen, use the arrow keys to move to a field that you want to modify
and refer to information below for descriptions and settings.
Table 2.6 Modifying a NAC Programming Selections (1 of 2)
FieldDescriptionSet as follows:
Type CodeSpecifies the function of the NAC.Press the
through the NAC Type Code selections (listed in
Table F.4 on page 116)
Custom Label20 character custom label. Change by placing the cursor into the first space of the
field using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any
space necessary between the custom and extended label
fields. An 80-column printout will run the two fields
together.
Extended
Label
CBE zonesSpecifies up to five software zones to
Switch InhibitSpecifies if an operator can manually
12 character custom label extension.See “Custom Label” above.
define the output responses of the
NAC based on various initiating
conditions (events)
activate an output
Type the numbers of up to five zones, including E0-E9,
F0-F9, L0-L9, R0-R9, and zones 00-99. The first zone
default is 00 (general alarm)
Type in one of the following values.
I = Switch Inhibit enabled
* = Switch Inhibit disabled (default for all but releasing
Table 2.6 Modifying a NAC Programming Selections (2 of 2)
FieldDescriptionSet as follows:
SilenceableSpecifies if an operator can manually
silence an activated output
Walk TestSpecifies if outputs sound during Walk
Te st
Type in one of the following values.
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
If the “Strobe” Type ID is used with System Sensor,
Gentex or Wheelock Strobe synchronization,“*” will
silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit,
and resound will occur according to the above definitions.
Type in one of the following values.
W = devices sound (Basic Walk Test) - default
* = devices do not sound (Silent Walk Test)
2.When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to
select another point.
2.3.4 Change a Password (3=PASSWD)
Password Change lets you select a custom Program Change (high level) or
Status Change (low level) password. From the “Basic Program” screen, press
the 3 key to display the “Change Password” screen.
.
To change a password, follow the instructions below:
Table 2.7 Changing a Password
ToPr essT hen
Change the Program Change
password
Change the Status Change
password
Save the passwordThe Verify Password screen appears.
Leave the Change Password
screen without changing a
password
Enter the new Program Change
password. Use five digits, no characters.
Enter the new Status Change password.
Use five digits, no characters.
YOUR CUSTOM MESSAGE HERE
SYSTEM NORMAL 02:24P 041508 Tue
Blinking cursor prompt
Message change area
SYSTEM NORMAL
A Forgotten Password?
If a password is entered incorrectly, the panel will respond by displaying an
message and a code. The programmer may hit escape and reenter the password correctly. However,
if the password has been forgotten, record the code and contact Notifier. After proper
authentication, the original password can be determined by deciphering the code. An example of an
INCORRECTPASSWORD display is given below:
2.3.5 Create a System Message (4=MESSAGE)
The Message option lets you create a 40-character custom System Message
that displays on the first line of the “
below:
From the “Basic Program” screen, press the 4 key to display the “System Message Change” screen:
SYSTEMNORMAL’ screen as shown
INCORRECTPASSWORD
To create the system message, follow these guidelines:
• Enter one character at a time, indicated by the blinking cursor on the second line of the
display.
• Enter up to 40 characters maximum.
Instructions for entering characters in the Message Change screen:
Table 2.8 Creating Messages
ToDo this
Change a blinking characterEnter a character from the keypad
Move to the next character
Enter lower case characters
Enter additional characters !
@ = , % : \ . I ?
Save the new message
Press
Press, then press the character of your choice.
Press, then press a number key as follows:
For example, press, then press the
a “=” character.
CHANGE ZONE LABELSELECT ZONE 01-99:
ENTER UP TO 20 CHAR
blinking cursor prompt
Custom zone label (characters 21-40)
Program Change
Password
SPECIAL FUNCTION: F0=PRESIG R0-R9=REL
F5-F6=TIME F7=HOL F8=CODEF9=PRE-ALARM
2.3.6 Create a Custom Zone Label (5=ZONE)
The Zone option lets you change the custom label assigned to zones 1-99.
From the “Basic Program” screen, press the 5 key to display the “Zone
Change” screen as shown below:
The zone number displays in the first line, characters 39 and 40. When changing a zone label,
follow these guidelines.
• For single-digit numbers, enter a leading zero before the digit.
• Enter an alphanumeric zone label into line 2, characters 21–40.
To change a custom label for a zone, follow these instructions:
Table 2.9 Create or Change a Custom Zone Label
ToDo t his
Change a zone labelEnter a new zone label from the keypad.
Save the zone label in memoryPress .
The program stores the zone label in memory and
displays the Zone Change screen with all fields blank.
Leave the Zone Change screen
without changing a zone label
Press .
The display returns to the Program Change screen.
2.3.7 Program Special Zones (6=SPLFUNCT)
The Special Zone Change option lets you change the program for Special
Zones F0-F9, Releasing Zones R0-R9, FA (Verification), FB (Custom drill
zone) or FC (CO Alarm). From the “Basic Program” screen, press the 6 key to
display the “Special Function Change” screen as shown below:
.
Special Zone Descriptions
Descriptions for each Special Zone that appears in the “Special Function Change” screen are
detailed below:
NOTE: Special Zones F0-F9 appear in the CBE list of a device as ZF0-ZF9. For example, if you
list F0 for a detector, one of the five zones in the CBE list of the detector will display as ZF0.
PRESIGSelect a Presignal Delay Timer and select PAS (Positive Alarm
Sequence)
F5-F6=
TIMESpecify Time Control functions such as the start time, stop time, or
days of the week
F7=
HOLSpecify up to nine holiday dates. An F7-programmed device
activates on the specified holiday dates
F8=
CODESpecify one of the following coding function selections: March Time,
Temporal, California, Two-Stage, Two-Stage Canada (3 minute or 5
minute), Two-Stage Canada Manual, System Sensor Strobes,
Gentex Strobes, or Wheelock Strobes. F8 only takes effect if you
program one or more NACs to F8
F9=
PRE-ALARMSelect a Pre-Alarm level: Alert or Action
FA (ZF10*)Turn on when detector in verification mode. This is a fixed point and
is not programmable
FB (ZF16*)Turn on if custom drill set to Y and the panel in Drill mode
FC (ZF18*)Turn on when a CO alarm occurs
FD (ZF20*)Turns on when a mass notification alarm occurs (Not applicable for
FirstCommand applications)
FE (ZF21*)Turns on when a mass notification supervisory occurs
FF (ZF22*)Turns on when a mass notification trouble occurs
NOTE: Special Function Zones FA through FF are not field programmable.
R0-R9=
RELProgram up to ten Releasing Zones, each with a selection for a
Delay Timer, an Abort Switch, a Cross Zone selection, or a Soak
Timer
* VeriFire Tools settings
Mass Notification
When used for mass notification, special zones ZF20, ZF21, and ZF22 can be used to signal the
MN event.
NOTE: During local or network Walk Test, activating a Mass Notification device will activate
associated special function zones according to CBE programming and simulate a Mass
Notification event. Any network nodes, zones, or devices not participating in Walk Test will not
participate in the simulated Mass Notification event.
Special Zones F1-F4
The control panel also provides four Special Zones, F1-F4, which are outputs that do not appear on
the Special Function Change screen. You can program Special Zones F1 to F4 into the CBE of an
output device. Descriptions of F1, F2, F3, and F4 are detailed below:
To view the status of Special Functions F1-F4, use the Read Status function (refer to the NFS2-640 Operations Manual).
Table 2.11 Special Output Functions F1-F4 (1 of 2)
Special FunctionSpecifies
F1 (Trouble less AC)An output programmed to turn on/off if a system trouble—other
Delay Timer for
releasing application:
1-60 seconds or 00
(no delay)
Releasing Zone programming status banner
Abort Switch: a thee-letter Abort switch
Type Code (ULI, IRI, NYC, or AHJ)
Cross Zone option: specifies type of
Cross Zone: N (none), Y, Z, or H
Soak Timer option:0000
(not used) or delay time
(0001-9999 seconds)
Releasing zone
(R0 shown)
PRG RELEASE FUNCTRELEASE CONTROL
DELAY=00 ABORT=ULI CROSS=N SOK=0000 R00
Table 2.11 Special Output Functions F1-F4 (2 of 2)
Special FunctionSpecifies
F2 (AC Trouble)An output programmed to turn on/off if an AC power loss or a
brownout condition occurs
F3 (Security)An output programmed to turn on/off if a Security input activates
F4 (Supervisory)An output programmed to turn on/off if a Supervisory input
activates
Selecting Special Zones
Select Special Zones by entering the Special Zone letter and number (for example, F0, R0, and so
on) from the Special Function Change screen. The following sections show sample screens that
display when you select a Special Zone.
F0 (Presignal/PAS) The Presignal screen provides fields for changing the delay time or PAS. For
details on Presignal selections, refer to “Presignal and PAS Time” on page 92. From the Special
Function Change screen, press the F key, then press the 0 key to display the Presignal Function
screen.
Coding Function selection (refer to
“Coding Functions for NACS” on
page 93)
Coding Function programming status banner
Coding Function
(Zone F8)
PRG CODING FUNCTION CODE TYPE
MARCH TIMEF08
F5-F6 (Time Control Functions) The Time Control screen provides fields for changing the start
time, stop time, or days of the week. For details on time selections, refer to “Time Control Zones”
on page 93. From the Special Function Change screen, select F5 or F6 to display the Time Control
screen:
F7 (Holiday) The Holiday screen provides fields for specifying up to nine holiday dates. For
details on holiday selections, refer to “Time Control Zones” on page 93. From the Special Function
Change screen, press F7 to display the Holiday screen:
F8 (Coding Function) The Coding Function screen provides fields for specifying one of the
following coding functions: March Time, Two-stage, California, Temporal, Two-Stage Canada (3
minutes), Two-Stage Canada (5 minutes), Two-Stage Canada Manual, System Sensor Strobe,
Gentex Strobe, and Wheelock Strobe. For details on selecting coding functions, refer to “Coding
Functions for NACS” on page 93. From the Special Function Change screen, press F8 to display
the Coding Function screen:
Loading...
+ 96 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.