Honeywell NFS2-640/E Programming Manual

Fire Alarm Control Panel
NFS2-640/E
Programming Manual
Document 52742 7/17/14 Rev:
P/N 52742:L2 ECN 13-838
L2
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication meth­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep the entire life safety system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be per­formed by authorized professional life safety system installers only. Adequate written records of all inspections should be kept.
Limit-D-1-2013
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH™, NIS™, NOTI•FIRE•NET™, eVance™, and SWIFT™ are all trademarks; and Acclimate® Plus, FAAST®, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark
and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

Table of Contents

Section 1: General Information................................................................................................7
1.1: UL 864 Compliance.......................................................................................................................................7
1.1.1: Products Subject to AHJ Approval......................................................................................................7
1.1.2: Programming Features Subject to AHJ Approval ...............................................................................7
1.2: About This Manual ........................................................................................................................................8
1.2.1: Cautions, Warning, and Notes.............................................................................................................8
1.2.2: Typographic Conventions....................................................................................................................8
1.2.3: Supplemental Information ...................................................................................................................9
1.2.4: Shortcuts to Operating Functions ......................................................................................................10
1.3: Introduction to the Control Panel ................................................................................................................10
1.4: Features........................................................................................................................................................11
1.5: How to Enter a Password.............................................................................................................................11
Section 2: Programming ........................................................................................................13
2.1: Overview......................................................................................................................................................13
2.2: How to Enter Programming.........................................................................................................................14
2.3: Basic Program..............................................................................................................................................14
2.3.1: Clear Memory (0=
2.3.2: Autoprogram the Control Panel (1=
2.3.3: Modify or Delete a Point (2=
2.3.4: Change a Password (3=
2.3.5: Create a System Message (4=
2.3.6: Create a Custom Zone Label (5=
2.3.7: Program Special Zones (6=
2.3.8: Change Global System Functions (7=
2.3.9: How to Check the Program for Errors (8=
2.4: The Network Program .................................................................................................................................47
2.5: The Utility Program.....................................................................................................................................48
2.6: FlashScan Poll .............................................................................................................................................49
2.7: Setting the Baud Rate of Serial Ports ..........................................................................................................50
2.7.1: Printer Serial Port ..............................................................................................................................50
2.7.2: CRT Serial Port .................................................................................................................................51
CLR)......................................................................................................................15
AUTO)........................................................................................15
POINT)..................................................................................................19
PASSWD) .......................................................................................................25
MESSAGE) ...........................................................................................26
ZONE).............................................................................................27
SPL FUNCT).............................................................................................27
SYSTEM) .................................................................................31
CHECK PRG).....................................................................47
Section 3: Status Change.......................................................................................................52
3.1: Overview......................................................................................................................................................52
3.2: How to Enter Status Change........................................................................................................................52
3.3: Disable or Enable a Point ............................................................................................................................53
3.4: Changing Detector Sensitivity .....................................................................................................................54
3.5: Clearing Alarm Verification Counters .........................................................................................................55
3.6: Clearing the History Buffer .........................................................................................................................55
3.7: Setting the System Time and Date...............................................................................................................55
3.8: Walk Test .....................................................................................................................................................56
3.8.1: Basic Walk Test.................................................................................................................................57
3.8.2: Advanced Walk Test .........................................................................................................................58
3.8.3: Walk Test Activation Indications......................................................................................................58
3.8.4: Viewing Walk Test Results ...............................................................................................................59
A.1: Overview.....................................................................................................................................................60
A.1.1: Description of Releasing Zones........................................................................................................60
A.1.2: NFPA Releasing Applications..........................................................................................................61
A.2: How to Program a Releasing Zone .............................................................................................................61
A.2.1: Programming a Delay Timer ............................................................................................................61
A.2.2: Abort Switches..................................................................................................................................62
A.2.3: Using Cross Zones............................................................................................................................70
A.2.4: Programming a Soak Timer..............................................................................................................72
A.2.5: Using Type Codes for Releasing Zones ...........................................................................................73
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 5
Table of Contents
A.3: Initiating Devices ........................................................................................................................................91
A.4: Warning Sounders .......................................................................................................................................91
A.5: Auxiliary Control Functions .......................................................................................................................91
A.6: ACS Annunciation ......................................................................................................................................91
B.1: Presignal and Positive Alarm Sequence (PAS) ...........................................................................................92
B.1.1: What is Presignal and PAS?..............................................................................................................92
B.1.2: Selecting Presignal and PAS Outputs ...............................................................................................93
B.2: Time Control Zones.....................................................................................................................................93
B.3: Coding Functions for NACS .......................................................................................................................93
C.1: Overview .....................................................................................................................................................95
C.2: Features .......................................................................................................................................................95
C.2.1: Drift Compensation and Smoothing .................................................................................................95
C.2.2: Maintenance Warnings – Three Levels ............................................................................................96
C.2.3: Self-Optimizing Pre-Alarm...............................................................................................................97
C.2.4: Detector Sensitivity...........................................................................................................................97
C.2.5: Cooperative Multi-Detector Sensing ................................................................................................98
C.3: Pre-Alarm ....................................................................................................................................................99
C.3.1: Definition ..........................................................................................................................................99
C.3.2: Alert Level ........................................................................................................................................99
C.3.3: Action Level....................................................................................................................................100
C.3.4: How to Select a Pre-Alarm Level ..................................................................................................100
C.4: Detector Sensitivity Settings .....................................................................................................................101
C.4.1: How to Select Pre-Alarm and Alarm Sensitivity ............................................................................101
C.4.2: How to Test Detectors Set Below 0.50% Obscuration per Foot.....................................................102
C.5: Detector Maintenance Features.................................................................................................................103
C.5.1: Overview.........................................................................................................................................103
C.5.2: How to Access Detector Maintenance Information........................................................................103
C.5.3: View Detector Maintenance for a Detector ....................................................................................103
C.5.4: Print a Detector Maintenance Report..............................................................................................104
C.5.5: Interpreting a Detector Status Display or Maintenance Report ......................................................104
D.1: Description ................................................................................................................................................106
D.2: Input and Outputs......................................................................................................................................106
D.3: Equations...................................................................................................................................................106
D.4: Equation Entry ..........................................................................................................................................107
D.4.1: Logic Functions ..............................................................................................................................107
D.4.2: Equation Syntax Example...............................................................................................................108
D.4.3: Evaluating an Equation ...................................................................................................................108
D.4.4: Argument Entries............................................................................................................................108
D.4.5: Time Delay Functions.....................................................................................................................109
D.5: CBE Example............................................................................................................................................109
E.1: Overview ...................................................................................................................................................110
E.2: System Testing and Detector Initialization................................................................................................110
E.3: How to Replace a Detector.................................................................................................
.......................110
E.4: How to Manually Initialize a Detector ......................................................................................................111
F.1: What are Type Codes? ...............................................................................................................................112
F.2: How to Select a Type Code........................................................................................................................112
F.3: In this Appendix .........................................................................................................................................112
F.4: Type Codes for Input Devices....................................................................................................................112
F.4.1: Overview .........................................................................................................................................112
F.4.2: Type Codes for Intelligent Detectors ..............................................................................................112
F.4.3: Type Codes for Monitor Modules ...................................................................................................114
F.5: Type Codes for Output Devices .................................................................................................................115
F.5.1: Overview .........................................................................................................................................115
F.5.2: Type Codes for Control Modules ....................................................................................................115
F.5.3: NAC Type Codes ............................................................................................................................116
Index ......................................................................................................................................121
6 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Section 1: General Information
1.1 UL 864 Compliance
1.1.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition.
A complete listing identifying which products have or have not received UL 864 9th Edition certification is located in the installation manual of this fire alarm system. Those products which have not received UL 864 9th Edition certification may only be used in retrofit applications. Operation of the NFS2-640/E with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and /or UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
1.1.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below must be approved by the local AHJ.
Table 1.1 Programming Settings
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
IP downloads over a local area network (LAN) or the internet (WAN - WIde Area Network)
Releasing: Abort Switch Yes NYC
Detector Programming: Supervisory Type Codes
ALA.SCROLL (Scroll Display) No Y
TBL.REMIND Yes *, 1, 2, 3, 4, 5 2
REGION No 0 (No special setting)
No Yes
Yes SUP L(DUCTI)
No Timed
AHJ ULI IRI
SUP T(DUCTI) SUP T(DUCTP) SUP L(DUCTP) SUP L(ION) SUP T(ION) SUP L(PHOTO) SUP T(PHOTO) SUP L(LASER) SUP T(LASER) PHOTO/CO (P SUP)
N
1 (China)
No
ULI IRI
SUP L(DUCTI) SUP T(DUCTI) SUP L(DUCTP) SUP T(DUCTP)
N
0 (No special setting)
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 7
General Information About This Manual
!
!
1.2 About This Manual
1.2.1 Cautions, Warning, and Notes
The following graphics appear in the manual to indicate a caution or a warning.
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment damage.
WARNING:
Information about procedures that could cause irreversible damage to the control panel, irreversible loss of programming data or personal injury.
NOTE: Information that highlights an important part of the preceding or subsequent text or illustration.
1.2.2 Typographic Conventions
This manual uses the following conventions as listed below:
Table 1.2 Typographic Conventions in this Manual
When you see Specifies Example
the text as it appears in
text in small caps
text in quotes
bold text
italic text a specific document NFS2-640 Installation Manual
a graphic of the key
the LCD display or on the control panel
a reference to a section or an LCD menu screen
In body text, a number or character that you enter
In a graphic, a key as it appears on the control panel
MARCH TIME is a selection that appears
in the LCD display; or Press the key
“Status Change” specifies the Status Change section or menu screen
Press 1; means to press the number “1” on the keypad
Press means to press the Escape key
ENTER
NOTE: The term NFS2-640 is used in this manual to refer to the NFS2-640 and NFS2-640E unless otherwise noted.
8 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
About This Manual General Information
1.2.3 Supplemental Information
The table below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices. The document series chart (DOC-NOT) provides the current document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable) Document Number
Device Compatibility Document 15378
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
NFS2-640/E Installation, Operations, and Programming Manuals 52741, 52742, 52743
SLC Wiring Manual 51253
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility Document Number
Ver iFir e Veri•Fire Medium Systems Help File
Cabinets & Chassis Document Number
CAB-3/CAB-4 Series Cabinet Installation Document 15330
Battery/Peripherals Enclosure Installation Document 50295
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
ACPS-610 Addressable Power Supply Manual 53018
ACPS-2406 Installation Manual 51304
APS-6R Instruction Manual 50702
APS2-6R Instruction Manual 53232
CHG-120 Battery Charger Manual 50641
FCPS-24 Field Charger/Power Supply Manual 50059
FCPS-24S Field Charger/Power Supply Manual (Sync) 51977
Networking Document Number
Noti•Fire•Net Manual, Network Version 4.0 & Higher 51584
High-Speed Noti•Fire•Net Manual 54013
HS-NCM Installation Document 54014
NCM-W/F Installation Document 51533
NCS Network Control Station Manual, Network Version 4.0 & Higher 51658
NCA-2 Network Control Annunciator Manual 52482
ONYXWorks™ Workstation Manuals 52305, 52306, 52307
System Components Document Number
DVC Digital Voice Command Manual 52411
DAL Device Reference Document 52410
DVC-RPU Manual 50107425-001
DVC-RPU UL Listing Document 50107424-001
DS-DB Digital Series Distribution Board and Amplifier Manual 53622
DAA2 and DAX Amplifiers Manual 53265
Annunciator Control System Manual 15842
Annunciator Fixed Module Manual 15048
®
Tools CD help file
VERIFIRE-TCD VERIFIRE-CD
Table 1.3 Related Documentation (1 of 2)
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 9
General Information Introduction to the Control Panel
AFM-16A Annunciator Fixed Module Manual 15207
ACM-8R Annunciator Control Module Manual 15342
LCD-80 Manual 15037
LCD2-80 Manual 53242
FDU-80 Remote Annunciator Manual 51264
LDM Series Lamp Driver Annunciator Manual 15885
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
FireVoice-25/50ZS & FireVoice 25/50ZST Manual 52290
FirstCommand Emergency Communication System LS10001-001NF-E
RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater Manual 15640
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
UDACT-2 (Universal Digital Alarm Communicator/Transmitter) Listing Document 54089LD
UDACT-2 Manual (Universal Alarm Communicator/Transmitter) 54089
ACT-2 Installation Document 51118
RM-1 Series Remote Microphone Installation Document 51138
RA100Z Remote LED Annunciator Installation Document I56-0508
Table 1.3 Related Documentation (2 of 2)
1.2.4 Shortcuts to Operating Functions
To the left of each program function, you’ll find a keypad shortcut, which contains a series of keypad entries required to access the program function. All shortcuts start with the control panel in normal operation.
For example, the keypad shortcut to the left shows how to enter the Read Status function with the control panel in normal operation.
1.3 Introduction to the Control Panel
The NFS2-640 is an intelligent, field-programmable Fire Alarm Control Panel. Field-programming the control panel lets you customize the fire alarm system by selecting and setting program options for intelligent/addressable detectors and modules, and Notification Appliance Circuits (NACs).
This manual provides information for programming using the NFS2-640 keypad connected to the control panel. VeriFire™ Tools must be used for programming if no keypad is used, or if a network control annunciator is used as the keypad in either a network or standalone application. Refer to VeriFire™ Tools for information on programming without the NF2S-640 keypad, and the NF2S- 640 Installation Manual and NCA-2 Manual for installation information.
For details on control panel operation, refer to the NFS2-640 Operations Manual.
The NF2S-640 provides two methods for field-programming the control panel:
• Using the built-in “Program Change” interface
• The VeriFire™ Tools Programming Utility
10 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Features General Information
The benefits of each method are listed below:
Programming method Benefits Refer to
1.4 Features
Programming features include the following:
Program Change Speed and convenience of
putting the control panel on line quickly (using the Autoprogram function) and changing programming information.
VeriFire™ Tools Programming Utility
Efficient means of creating and editing programs that require a lot of data entry.
Section “Programming” on page 13
Product documentation & Software help file
• Ease-of-use – Field program the control panel without needing special software skills.
• Autoprogram option – Automatically detects newly installed, addressable devices, allowing quicker installation.
• Local programming – program directly from the control panel keypad to reduce installation time.
• PC programming – input long data entry programming information on a PC; transfer programming data between a PC and the control panel using VeriFire™ Tools programming utility.
• Security – use passwords to control access to the control panel and protect memory.
• 80-Character (2x40) Liquid Crystal Display – view programming and device information on the control panel.
1.5 How to Enter a Password
The control panel provides two types of selectable passwords:
Program Change
•Status Change
Listed below are uses and the factory-setting for each password type:
Table 1.4 Programming Passwords
Password type
Program Change (high level)
Status Change (low level)
Use to
Enter Program Change option to program essential control panel functions, including basic system functions and utility options.
Enter Status Change option to program minor functions.
Factory Setting
00000
11111
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 11
General Information How to Enter a Password
Enter password here (00000 or 11111)
ENTER PROG OR STAT PASSWORD, THEN ENTER. (ESCAPE TO ABORT) _
From the “SYSTEM NORMAL” screen: Press ENTER, press 1 (the password screen will display). Enter a password, then press
ENTER
Figure 1.1 Password Screen
In Program Change or Status Change, the control panel does the following:
• Activates the System Trouble relay
• Shuts off the panel sounder
• Flashes the
SYSTEM TROUBLE LED, which continues to flash while programming
For security purposes, passwords can be changed. To do so, follow the instructions in “Change a Password (3=passwd)” on page 25.
NOTE: The Read Status selection, which does not require a program password, is covered in the NF2S-640 Operations Manual.
NOTE: The NF2S-640 continues to monitor and report alarms in programming mode, except in autoprogramming.
12 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
2.1 Overview
Choose one of the Program Change selections: 1, 2, 3 or 4
1 Basic Program options
3 Utility Program options
4 FlashScan Poll options
2 Network Program options
1=BASIC PROGRAM 2=NETWORK 3-UTILITY 4=FLASHSCAN POLL
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE 5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
THRESHOLD CH.A:H, THRESHOLD CH.B:H NODE: .000, STYLE7:Y, <ENTER>
REGION=0 TBL.REMIND=2 ALA.SCROLL=N LOCAL CONTROL=0
FLASHSCAN L1DET L1MOD L2DET L2MOD
NYNY
Program Change is the programming level that lets you change the essential control panel functions, such as point programming, changing passwords, changing system functions. Included are four options: Basic Program, Network, FlashScan Poll, and Utility Program.
The structure of the Program Change option is shown below:
Section 2: Programming
This section contains instructions and sample screens for using the Programming selections:
Figure 2.1 Program Change Selections
Basic Program The Basic Program lets you program essential functions, such as clearing the program, Autoprogramming the system, programming points, and setting system functions. Refer to “Basic Program” on page 14.
Network Program The Network Program allows programming of network channel thresholds, network node number, and wiring style.“The Network Program” on page 47.
Utility Program The Utility Program screen provides selections for selecting a Trouble Reminder per NFPA, a Region setting, and enabling or disabling local control of the
ACKNOWLEDGE/SCROLL DISPLAY, SIGNAL SILENCE, SYSTEM RESET and DRILL keys. Refer to
“The Utility Program” on page 48.
FlashScan Poll The FlashScan Poll screen provides the option for selecting between CLIP
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 13
(Classic Loop Interface Poll) and FlashScan Poll. Refer to “FlashScan Poll” on page 49.
Programming How to Enter Programming
1=PROGRAMMING 2=READ STATUS ENTRY (ESCAPE TO ABORT)
ENTER PROG OR STAT PASSWORD, THEN ENTER. (ESCAPE TO ABORT) _
1=BASIC PROGRAM 2=NETWORK 3-UTILITY 4=FLASHSCAN POLL
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE 5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
2.2 How to Enter Programming
To enter Program Change, follow these steps:
1. At the “SYSTEM NORMAL” screen, press the “Entry” screen, as shown below:
2. At the “Entry” screen, press the 1 key. The control panel displays the “Enter Password” screen as shown below:
3. Enter your Program Change password (See “How to Enter a Password” on page 11). The control panel displays the “Program Change Selection” screen, as shown below:
4. Select a Program Change selection: 1, 2, 3 or 4.
2.3 Basic Program
From the “Program Change Selection” screen, press the 1 key to display the “Basic Program” screen which provides nine (9) options as shown below:
ENTER key. The control panel displays the
Press the number of any one of the nine (9) options as detailed below
Option 0=CLR - Clears all existing user programming. For details, refer to How to Clear Memory (0=
CLR) on page 15. Note: The user is prompted to double-check that this is what is really wanted.
Option 1=AUTO - Add or remove addressable devices to the control panel program. For details, refer to How to Autoprogram the Control Panel (1=
AUTO) on page page 15.
Option 2=POINT - Modify or delete a point. For details, refer to “How to Modify or Delete a Point (2=
POINT)” on page page 19.
Option 3=PASSWD - Change the Program Change or the Alter Status password. For details, refer to “How to Change a Password (3=
PASSWORD)” on page page 25.
Option 4=MESSAGE - Edit the 40-character message that displays on the first line. For details, refer to “How to Create a System Message (4=
MESSAGE)” on page page 26.
Option 5=ZONES - Edit the 20-character custom zone label for zones 01-99. For details, refer to “How to Create a Custom Zone Label (5=
ZONE)” on page page 27.
Option 6=SPL FUNCT - Program Releasing Zones and Special Zones. For details, refer to “How to Program Special Zones (6=
SPL FUNCT)” on page page 27.
Option 7=SYSTEM - Program Global System Functions. For details, refer to “How to Change Global System Functions (7=
SYSTEM)” on page page 31.
Option 8=CHECK PRG - Check the program for errors. For details, refer to “How to Check the Program for Errors (8=check prg)” on page 47.
14 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Program Change Password
PRESS ENTER TO CLEAR ENTIRE PROGRAM OR ESCAPE TO ABORT
Program Change Password
2.3.1 Clear Memory (0=CLR)
The Clear option removes all programming information from control panel memory. If installing the control panel for the first time, use option 0 to clear control panel memory. To do so, follow these steps:
1. From the “Basic Program” screen, press the 0 (zero) key to display the Clear Program screen. The control panel prompts for verification as shown below:
2. Press the
ENTER key to clear control panel memory or press the ESC key to exit the screen
without clearing.
2.3.2 Autoprogram the Control Panel (1=AUTO)
Purpose
The Autoprogram option identifies all addressable devices connected to the control panel. Devices include addressable detectors and modules connected to SLC 1 or SLC 2, and NACs. You can use the Autoprogram option to create a new program and add or remove devices. A summary of the Autoprogram functions, when to use the functions, and where to find information on using the functions is found below:
Autoprogram Function Control Panel Configuration Refer to...
Create a new program for the control panel
Add one or more SLC-connected detectors and modules to an existing program
Remove one or more SLC-connected detectors and modules from an existing program
A new control panel or a control panel with no existing program in memory.
A program exists in memory and you want to add a detector or module to the existing program—without modifying information for existing detectors and modules.
A program exists in memory and you want to remove an installed detector or module from the existing program—without modifying information for existing detectors and modules.
“Create a New Program for the Control Panel” on page 15
“Add a Device to the Program” on page 16
“Remove a Device from the Program” on page 17
View system defaults A program exists in memory and you want to
view system settings assigned during Autoprogram, such as custom labels, passwords, and so on.
Page 19 “Change Autoprogram Default Value” to see the system defaults
Create a New Program for the Control Panel
This section covers how to use the Autoprogram option to create a new program for the control panel. The control panel will identify all addressable detectors and modules connected to the SLC.
To create a new program for the control panel, follow these steps:
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 15
Programming Basic Program
AUTOPROGRAM PLEASE WAIT
L1:010Dets, 159Mods L2:159Dets, 159Mods SB L1:000, L2:159 Bells: 04
ACCEPT ALL DEVICES Please Wait!!!
PROGRM SMOKE(PHOTO) DETECTOR ADDR 1D147
03 __ __ __ __A8P8** 1D147
1. Use the Clear option to clear program information from memory. For instructions on clearing memory, refer to “How to Clear Memory (0=
NOTE: Once Step 1 is completed, Step 2 will cause the panel to assess whether a loop is comprised of all FlashScan devices or not. If they are all FlashScan, autoprogramming will change the loop setting to FlashScan if it was not already at that setting. If the devices are not all FlashScan, autoprogramming will not make a change to the default setting of CLIP. (See “FlashScan Poll” on page 49 for FlashScan settings.)
CLR)” on page page 15.
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. While the control panel scans the system to identify all SLC devices and NACs, it displays the following screen:
When the autoprogram is finished identifying SLC devices and NACs, it displays a summary screen that gives a count of all the devices it has located. Refer to the following screen for an example of this display.
SB represents detectors with B200 series sounder bases. Refer to VeriFire Tools for B200 sounder base programming.
3. Press
ENTER. All devices are automatically accepted during initial autoprogramming. The
following screen displays briefly, followed by the
SYSTEM NORMAL screen.
To edit the autoprogramming default values for a point, refer to “How to Modify or Delete a Point (2=
POINT)” on page page 19.
To edit the autoprogram default values assigned to all modules and detectors during autoprogramming, refer to “Change Autoprogram Default Values” on page 18.
Add a Device to the Program
You can also use the Autoprogram option to add addressable devices to the control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not change program information for installed and programmed devices. However, it will assess whether a loop contains all FlashScan devices and change the loop setting to FlashScan if necessary.
The following steps describe how to add a new detector at SLC address 1D147 with 10 detectors in the existing program:
1. Physically install the addressable detector to SLC 1 at address 147 (for instructions, refer to the NF2S-640 Installation Manual and the installation document that comes with the detector).
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. The Autoprogram Prompt screen appears in the LCD display as the control panel identifies addressable devices. When finished identifying addressable devices, the control panel displays information for the new detector at SLC address 1D147 on the LCD display as shown below:
16 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Note that the number of detectors increases (in this example from 10 to 11) to show the addition of the detector to SLC 1.
L1:011Dets, 159Mods L2:159Dets, 159Mods SB Bells: 04
Type Code
SLC loop number
D (detector) or M (module)
Three-digit address (001-159)
PROGRM SMOKE (ION) DETECTOR ADDR 1D133 DEVICE NOT ANSWERING DELETE FR MEM?1D133
Note that the number of detectors decreases (from 11 to
10) to show the removal of the detector from SLC 1.
L1:010Dets, 159Mods L2:159Dets, 159Mods SB Bells: 04
3. Press the ENTER key to add detector 147 to the program with the default program information. If you want to change the default information, use the programming keys to do so, then press the
ENTER key to add detector 147 to the program.
The Autoprogram Summary screen appears. You can verify addition of the detector to the program by noting the new count of detectors as shown below:
4. Press the
ENTER key, then press the esc key to save the program in memory and return to the
“Basic Program” screen).
Remove a Device from the Program
You can also use the Autoprogram option to remove addressable detectors and modules from the control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not change program information for installed and programmed devices.
The following steps describe how to delete a detector at SLC address 1D133 with 11 detectors connected to SLC 1 in the existing program:
1. Disconnect and remove the detector from SLC 1 at address 1D133.
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. The Autoprogram Prompt screen displays while the control panel identifies addressable devices.
3. When finished identifying addressable devices, the control panel displays a screen, indicating a missing detector at SLC address 1D133 as shown below:
4. Press the
ENTER key to delete detector 1D133 from the program.
The Autoprogram Summary screen appears. You can verify removal of the detector from the program by noting the new count of detectors as shown below:
5. Press the
ENTER key, then press the ESC key to save the program in memory and return to the
“Basic Program” screen.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 17
Programming Basic Program
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the DELAY TIME and SOK (soak time) entries.
Change Autoprogram Default Values
To assign system default values from the basic program screen, Press 0 (clear), then press 1 (autoprogram). Refer to the chart below for default values and how to modify them.
Table 2.1 Autoprogram Defaults (1 of 2)
Function Default Values To Alter, refer to
Software Zones 01-99
F0 PRG PRESIGNAL FUNCT PRESIGNAL DELAY
Releasing Zones R0-R9
Default custom label “Zone xx” where xx is the number of the zone Note: Zone 00 is reserved for a general alarm.
DELAY=180 PAS=NO F00
PRG RELEASE FUNCT RELEASE CONTROL DELAY=00 ABORT=ULI CROSS=N SOK=0000
“How to Create a Custom Zone Label (5=
“F0 (Presignal/PAS) The Presignal screen provides fields for changing the delay time or PAS. For details on Presignal selections, refer to “Presignal and PAS Time” on page 92. From the Special Function Change screen, press the F key, then press the 0 key to display the Presignal Function screen.” on page 29
“R0-R9 (Releasing Functions) The Releasing Function screen provides fields for changing releasing functions: Delay Timer, Abort Switch, Cross Zone, and Soak Timer. For details on releasing applications, refer to “NFPA Releasing Applications” on page 61.” on page 29 and “How to Program a Releasing Zone” on page 61.
ZONE)” on page 27
F5 and F6 PRG TIME FUNCTION TIME CONTROL
ON=**:** OFF=**:** DAYS=********
F7 PRG HOLIDAY FUNCTION **/** **/** **/**
**/** **/** **/** **/** **/** **/**
F8 PRG CODING FUNCTION CODE TYPE
MARCH TIME F08
F9 PRE-ALARM FUNCT ALERT
F09
System Parameters
Passwords Default programming passwords are:
SYSTEM NORMAL message
SIL INH=0000 AUTO=0077 0 VERIFY=30 USA TIME TERM=N AC_DLY=Y LocT BLINK=01 ST=4 ACS=N
Program Change=00000 Status Change=11111
(YOUR CUSTOM SYSTEM MESSAGE HERE) SYSTEM NORMAL 10:23A 041508 Tue A message, along with the current day, time, and date, that displays on the second line of the LCD display during normal operation.
“F5-F6 (Time Control Functions) The Time Control screen provides fields for changing the start time, stop time, or days of the week. For details on time selections, refer to “Time Control Zones” on page 93. From the Special Function Change screen, select F5 or F6 to display the Time Control screen:” on page 30
“F7 (Holiday) The Holiday screen provides fields for specifying up to nine holiday dates. For details on holiday selections, refer to “Time Control Zones” on page 93. From the Special Function Change screen, press F7 to display the Holiday screen:” on page 30
“F8 (Coding Function) The Coding Function screen provides fields for specifying one of the following coding functions: March Time, Two-stage, California, Temporal, Two-Stage Canada (3 minutes), Two-Stage Canada (5 minutes), Two-Stage Canada Manual, System Sensor Strobe, Gentex Strobe, and Wheelock Strobe. For details on selecting coding functions, refer to “Coding Functions for NACS” on page 93. From the Special Function Change screen, press F8 to display the Coding Function screen:” on page 30
“F9 (Pre-Alarm) The Pre-Alarm screen provides fields for programming the Alert or Action Pre-Alarm functions. For details on Pre-Alarm selections, refer to “Pre-Alarm” on page 99. From the Special Function Change screen, press F9 to display the Pre-Alarm screen:” on page 31
“How to Change Global System Functions (7= page 31
“How to Change a Password (3=
Note: The second line, “SYSTEM NORMAL”, is a standard system message that you cannot change
PASSWD)” on page page 25
SYSTEM)” on
18 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Program Change Password
POINT PROG. 1=MODIFY POINT 2=DELETE POINT
Press for module point
SLC number
Three-digit address (001-159)
E - press the
ENTER key
Press for detector point.
SLC number Three-digit address (001-159)
Press for NAC
Modify Point Screen
Delete Point Screen
E - press the
ENTER key
POINT PROG. ENTER:DETECTOR=*,LDAAA,E MODULE=#,LMAAA,E OUTPUT CKT=&,A-A,E
E - press the
ENTER key
Two-digit address for NAC (01-04)
DELETE POINT. ENTER:DETECTOR=*,LDAAA,E MODULE=#,LMAAA,E OUTPUT CKT=&,A-A,E
Table 2.1 Autoprogram Defaults (2 of 2)
Function Default Values To Alter, refer to
System Message
IP ACCESS
DCC Mode Default setting is N, no DCC participation. “The Utility Program” on page 48
(YOUR CUSTOM SYSTEM MESSAGE HERE) SYSTEM NORMAL 10:23A 041508 Tue The first line of the LCD display contains 40 blank characters for a custom message.
Default setting is zero (0), IP Access not enabled. “The Utility Program” on page 48
“How to Create a System Message (4= page 26
MESSAGE)” on page
2.3.3 Modify or Delete a Point (2=POINT)
After programming all SLC-connected devices into the system, you can modify or delete points. From the “Basic Program” screen, press the 2 key to display the Point Programming screen:
To modify a point for a detector, module, or NAC: press the 1 key to display the “Modify Point” screen.
NOTE: When programming points, take the following into design consideration: Each general zone must be dedicated to a single event type (i.e. Fire, MN, Security, etc.) Map inputs only to general zones designed for the input’s event type. For example, map mass notification devices to general zones designed for mass notification. Outputs can be mapped to multiple general zones that are dedicated to different event types. For instance, a single output can be mapped to an MN general zone and a Fire general zone.
To delete a point for a detector, module, or NAC: press the 2 key to display the “Delete Point” screen.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 19
Programming Basic Program
12 spaces for extended custom label
PROGRM SMOKE(PHOTO) DETECTOR ADDR 1D101
03 __ __ __ __A8P8AV 1D101
Blinking Type Code selection
CBE list (five zones)
D (detector)
SLC address (001-159)
20-character user-editable custom label (in this example, autoprogramming has used the first 19 and left a space at the end.)
SLC Loop number
Alarm sensitivity level
Pre-alarm sensitivity level
Cooperative multi-detector mode indicator
Alarm verification setting
The Modify Point and Delete Point screens let you edit or delete points for a detector, a monitor or control module, or NAC. To select a point, follow these steps:
To select Do the following Refer to
an addressable detector
an addressable monitor module
an addressable control module
a NAC Press
Press
Type the SLC number (1 or 2) and detector (D) and address (001-159)
Press
Press
Type the SLC number (1 or 2) and module (M) and address (001-159)
Press
Press
Type the SLC number (1 or 2) and module (M) and address (001-159)
Press
Type the NAC address (01-04)
Press
The next four sections describe how to program the points selected.
Modify an Addressable Detector Point
This section contains a sample detector programming screen, detector default selection, and instructions for modifying a detector point. Autoprogram default values for a detector are shown:
“Modify an Addressable Detector Point” on page 20.
“Modify an Addressable Monitor Module Point” on page 22.
“Modify an Addressable Control Module Point” on page 23.
“Modify NAC Points” on page 24.
Field Description Set as Follows
Type Code Detector function
Custom Label
20 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.2 Detector Program Values
specification ­SMOKE(PHOTO) in example.
20 character custom label. Change by placing the cursor into the first space of the field using the arrow
Press the Type Code selections. See F.4.2 on page 112 for lists and descriptions.
keys, then typing the descriptor. DETECTOR ADDR 1D101 is the autoprogram default custom label for the detector at address 101 on SLC 1.
NEXT or PREVIOUS Selection keys to scroll through valid detector
Basic Program Programming
Zone 01 (Heat detectors) Zone 02 (Ion detectors) Zone 03 (Photo detectors, Beam detectors) Zone 04 (Laser detectors) Zone 05 (Multisensor)
A8 (Photo) A6 (Ion) A6 (Laser) A5 (Multisensor)
P8 (Photo) P6 (Ion) P6 (Laser) P5 (Multisensor)
Table 2.2 Detector Program Values
Field Description Set as Follows
Extended Label
12 character custom label extension.
CBE List Five zones can be listed - one
zone, Z03, is shown in the example. Up to 4 more could be added to this detector.
Alarm Sensitivity
The alarm sensitivity level, with 9 the least sensitive alarm level and 1 the most sensitive alarm level.
Pre-alarm level
Shows the Pre-Alarm level setting—a number between 0 and 9—as follows: 0 – no Pre-Alarm 1 – self optimizing 2 – most sensitive Pre-Alarm level 9 – least sensitive Pre-Alarm level
See “Custom Label” above. Note that spaces must be input by the user, including any space necessary between the custom and extended label fields. An 80-column printout will run the two fields together.
Zones can be changed or added to the CBE list by placing the cursor in the zone field using arrow keys, then typing. Defaults:
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in the field using the arrow keys, then either pressing the
NEXT or PREVIOUS
keys to make the selection, or typing the value. Defaults:
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in the field using the arrow keys, then either pressing the
NEXT or PREVIOUS
keys to make the selection, or typing the value. Defaults:
Cooperative Multi­detector mode
Alarm verification
Indicates the cooperative multi-detector mode (A in the example).
Indicates the alarm verification setting (V in the example).
Select by placing the cursor in the field using the arrow keys, then either pressing the
NEXT or PREVIOUS keys to make the selection, or typing the
value.
* = OFF (Default) A combines the detector's alarm decision with the next address above B combines the detector's alarm decision with the next address below C combines the detector's alarm decision with the next address above and
the next address below
Indicates Alarm Verification (V=on, *=off). Select by placing the cursor in the field using the arrow keys, then pressing the
NEXT or PREVIOUS keys to make
the selection. Refer to “Interpreting a Detector Status Display or Maintenance Report” on page 104 for more information on the alarm verification feature. Note: Do not use this setting when an alarm activation requires activation of two or more automatic detection devices.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 21
Programming Basic Program
Default zone
Blinking Type Code selection
CBE list (five zones)
12 spaces for extended custom label
SLC number (1 or 2)
M (module)
SLC address (001-159)
PROGRAM MONITOR WESTERN ENTRANCE AND HALLWAY 09 __ __ __ __ 2M101
20-character user-editable custom label.
Modify an Addressable Monitor Module Point
When you select a point address, the control panel returns a screen that displays information about the point. Below is an example of information for a monitor module (2M101) in the LCD display:
Table 2.3 Modifying Monitor Module Programming Selections
Field Description Set as Follows
Type Code Monitor Module function specification
-
MONITOR in example.
Custom Label 20 character custom label. Change by placing the cursor into the first space of the field
Extended Label 12 character custom label extension. See “Custom Label” above.
CBE List Five zones can be listed - one zone,
Z09, is shown in the example. Up to 4 more could be added to this module.
Press the valid monitor module Type Code selections. Lists and descriptions are in See Table F.2 on page 114.
using the arrow keys, then typing the descriptor. Note: Spaces must be input by the user, including any space necessary between the custom and extended label fields. An 80-column printout will run the two fields together.
Zones can be changed or added to the CBE list by placing the cursor in the zone field using arrow keys, then typing. See Table 2.4 on page 22 for defaults.
NEXT or PREVIOUS Selection keys to scroll through
When finished modifying a point, press the
ENTER key; then press the NEXT or PREVIOUS key to
select another point.
Monitor Module Default Zone Assignments
Listing of the monitor module address range and the default zone assignment for each range:
Table 2.4 Monitor Module Default Zones
Monitor Module Address Zone Default
01 through 19 Z04
20 through 39 Z05
40 through 59 Z06
60 through 79 Z07
80 through 99 Z08
100 through 119 Z09
120 through 139 Z10
140 through 159 Z11
22 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Walk Test Selection: *=off (default); W=selected
Silenceable: O =selected; *=off (default)
Default zone
Blinking Type Code selection
CBE list (five zones)
12 spaces for extended custom label
SLC number (1 or 2)
M (module)
SLC address (001-159)
Switch Inhibit: I=selected; *=off (default)
PROGRAM CONTROL MODULE CONTROL 2M101
00 __ __ __ __ IOW 2M101
20-character user-editable custom label
NOTE: On a control module, the default zone is always set to Zone 00 (general alarm).
Modify an Addressable Control Module Point
When you select a point address for modification, the control panel returns a screen that displays information about the point. For example, the illustration below shows sample information for a control module (2M101) in the LCD display.
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1. From the programming screen, use the arrow keys to move to a field that you want to modify. See below for descriptions and settings.
Table 2.5 Modifying Control Module Programming Selections (1 of 2)
Field Description Set as follows:
Type Code Specifies the function of the control
module
Custom Label 20 character custom label. Change by placing the cursor into the first space of the
Extended Label
CBE list Up to five software zones can be
Switch Inhibit Specifies if an operator can manually
Silenceable Specifies if an operator can manually
12 character custom label extension. See “Custom Label” above.
entered to define the output responses of the control module based on various initiating conditions (events)
activate an output
silence an activated output
Press the through valid control module Type Code selections (listed in Table F.3 on page 115)
field using the arrow keys, then typing the descriptor. Note: Spaces must be input by the user, including any space necessary between the custom and extended label fields. An 80-column printout will run the two fields together.
Type the number of up to five zones, including E0-E9, F0­F9, L0-L9, R0-R9, and zones 00-99. The first zone default is Z00 (general alarm).
Type one of the following entries.
I = Switch Inhibit enabled * = no switch inhibit (default for all but releasing circuits)
Type one of the following entries.
* = output nonsilenceable F = silenceable, resound by fire alarm U = silenceable, resound by supervisory alarm B = silenceable, resound by security alarm T = silenceable, resound by trouble O = silenceable, does not resound
If the “Strobe” Type ID is used with System Sensor, Gentex or Wheelock Strobe synchronization,“*” will silence the horn portion only, and resound will occur only by fire alarm. F, U, B, T, or O will silence the entire circuit, and resound will occur according to the above definitions.
NEXT or PREVIOUS Selection keys to scroll
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 23
Programming Basic Program
The address of a NAC connected through NAC 1 (B01), NAC 2 (B02), NAC 3 (B03), or NAC 4 (B04)
Five zones for CBE list; the default zone selection is 00 (general alarm)
Default zone
12 spaces for extended custom label
Switch Inhibit: I=selected; *=off (default)
Walk Test Selection: *=off (default); W=selected
Silenceable: O=selected; *=off (default)
Type Code
20-character user-editable custom label
PROGRAM CONTROL Notification Dev No1
00 __ __ __ __ *OW B01
Table 2.5 Modifying Control Module Programming Selections (2 of 2)
Field Description Set as follows:
Walk Test Specifies if outputs sound during Walk
Te st
Type one of the following entries.
W = devices sound (Basic Walk Test) * = devices do not sound (Silent Walk Test) (default)
2. When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to select another point.
Modify NAC Points
Modifying NACs (four NACs on the NFS2-640) is like modifying control modules—except for the Type Code and device address.
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1. From the programming screen, use the arrow keys to move to a field that you want to modify and refer to information below for descriptions and settings.
Table 2.6 Modifying a NAC Programming Selections (1 of 2)
Field Description Set as follows:
Type Code Specifies the function of the NAC. Press the
through the NAC Type Code selections (listed in Table F.4 on page 116)
Custom Label 20 character custom label. Change by placing the cursor into the first space of the
field using the arrow keys, then typing the descriptor. Note: Spaces must be input by the user, including any space necessary between the custom and extended label fields. An 80-column printout will run the two fields together.
Extended Label
CBE zones Specifies up to five software zones to
Switch Inhibit Specifies if an operator can manually
12 character custom label extension. See “Custom Label” above.
define the output responses of the NAC based on various initiating conditions (events)
activate an output
Type the numbers of up to five zones, including E0-E9, F0-F9, L0-L9, R0-R9, and zones 00-99. The first zone default is 00 (general alarm)
Type in one of the following values.
I = Switch Inhibit enabled * = Switch Inhibit disabled (default for all but releasing
circuits)
NEXT or PREVIOUS Selection keys to scroll
24 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Program Change Password
CHANGE PASSWORD *,NNNNN,E=PROGRAM #,NNNNN, E=STATUS
Entry area for new password
Table 2.6 Modifying a NAC Programming Selections (2 of 2)
Field Description Set as follows:
Silenceable Specifies if an operator can manually
silence an activated output
Walk Test Specifies if outputs sound during Walk
Te st
Type in one of the following values.
* = output nonsilenceable F = silenceable, resound by fire alarm U = silenceable, resound by supervisory alarm B = silenceable, resound by security alarm T = silenceable, resound by trouble O = silenceable, does not resound
If the “Strobe” Type ID is used with System Sensor, Gentex or Wheelock Strobe synchronization,“*” will silence the horn portion only, and resound will occur only by fire alarm. F, U, B, T, or O will silence the entire circuit, and resound will occur according to the above definitions.
Type in one of the following values.
W = devices sound (Basic Walk Test) - default * = devices do not sound (Silent Walk Test)
2. When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to select another point.
2.3.4 Change a Password (3=PASSWD)
Password Change lets you select a custom Program Change (high level) or Status Change (low level) password. From the “Basic Program” screen, press the 3 key to display the “Change Password” screen.
.
To change a password, follow the instructions below:
Table 2.7 Changing a Password
To Pr ess T hen
Change the Program Change password
Change the Status Change password
Save the password The Verify Password screen appears.
Leave the Change Password screen without changing a password
Enter the new Program Change password. Use five digits, no characters.
Enter the new Status Change password. Use five digits, no characters.
Press
ENTER to verify.
The Basic Program screen appears.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 25
Programming Basic Program
INCORRECT PASSWORD PROGRAM: 9066-21F5-7D78-5FA4-6163
Code
Program Change Password
YOUR CUSTOM MESSAGE HERE SYSTEM NORMAL 02:24P 041508 Tue
Blinking cursor prompt
Message change area
SYSTEM NORMAL
A Forgotten Password?
If a password is entered incorrectly, the panel will respond by displaying an message and a code. The programmer may hit escape and reenter the password correctly. However, if the password has been forgotten, record the code and contact Notifier. After proper authentication, the original password can be determined by deciphering the code. An example of an
INCORRECT PASSWORD display is given below:
2.3.5 Create a System Message (4=MESSAGE)
The Message option lets you create a 40-character custom System Message that displays on the first line of the “ below:
From the “Basic Program” screen, press the 4 key to display the “System Message Change” screen:
SYSTEM NORMAL’ screen as shown
INCORRECT PASSWORD
To create the system message, follow these guidelines:
• Enter one character at a time, indicated by the blinking cursor on the second line of the
display.
• Enter up to 40 characters maximum.
Instructions for entering characters in the Message Change screen:
Table 2.8 Creating Messages
To Do this
Change a blinking character Enter a character from the keypad
Move to the next character
Enter lower case characters
Enter additional characters !
@ = , % : \ . I ?
Save the new message
Press
Press , then press the character of your choice.
Press , then press a number key as follows:
For example, press , then press the a “=” character.
Press
3 ( ) key to enter
26 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Program Change Password
CHANGE ZONE LABEL SELECT ZONE 01-99: ENTER UP TO 20 CHAR
blinking cursor prompt
Custom zone label (characters 21-40)
Program Change Password
SPECIAL FUNCTION: F0=PRESIG R0-R9=REL F5-F6=TIME F7=HOL F8=CODE F9=PRE-ALARM
2.3.6 Create a Custom Zone Label (5=ZONE)
The Zone option lets you change the custom label assigned to zones 1-99. From the “Basic Program” screen, press the 5 key to display the “Zone Change” screen as shown below:
The zone number displays in the first line, characters 39 and 40. When changing a zone label, follow these guidelines.
• For single-digit numbers, enter a leading zero before the digit.
• Enter an alphanumeric zone label into line 2, characters 21–40.
To change a custom label for a zone, follow these instructions:
Table 2.9 Create or Change a Custom Zone Label
To Do t his
Change a zone label Enter a new zone label from the keypad.
Save the zone label in memory Press .
The program stores the zone label in memory and displays the Zone Change screen with all fields blank.
Leave the Zone Change screen without changing a zone label
Press .
The display returns to the Program Change screen.
2.3.7 Program Special Zones (6=SPL FUNCT)
The Special Zone Change option lets you change the program for Special Zones F0-F9, Releasing Zones R0-R9, FA (Verification), FB (Custom drill zone) or FC (CO Alarm). From the “Basic Program” screen, press the 6 key to display the “Special Function Change” screen as shown below:
.
Special Zone Descriptions
Descriptions for each Special Zone that appears in the “Special Function Change” screen are detailed below:
NOTE: Special Zones F0-F9 appear in the CBE list of a device as ZF0-ZF9. For example, if you list F0 for a detector, one of the five zones in the CBE list of the detector will display as ZF0.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 27
Programming Basic Program
Table 2.10 Summary of Special Zones
Special Zone Lets you
F0=
PRESIG Select a Presignal Delay Timer and select PAS (Positive Alarm
Sequence)
F5-F6=
TIME Specify Time Control functions such as the start time, stop time, or
days of the week
F7=
HOL Specify up to nine holiday dates. An F7-programmed device
activates on the specified holiday dates
F8=
CODE Specify one of the following coding function selections: March Time,
Temporal, California, Two-Stage, Two-Stage Canada (3 minute or 5 minute), Two-Stage Canada Manual, System Sensor Strobes, Gentex Strobes, or Wheelock Strobes. F8 only takes effect if you program one or more NACs to F8
F9=
PRE-ALARM Select a Pre-Alarm level: Alert or Action
FA (ZF10*) Turn on when detector in verification mode. This is a fixed point and
is not programmable
FB (ZF16*) Turn on if custom drill set to Y and the panel in Drill mode
FC (ZF18*) Turn on when a CO alarm occurs
FD (ZF20*) Turns on when a mass notification alarm occurs (Not applicable for
FirstCommand applications)
FE (ZF21*) Turns on when a mass notification supervisory occurs
FF (ZF22*) Turns on when a mass notification trouble occurs
NOTE: Special Function Zones FA through FF are not field programmable.
R0-R9=
REL Program up to ten Releasing Zones, each with a selection for a
Delay Timer, an Abort Switch, a Cross Zone selection, or a Soak Timer
* VeriFire Tools settings
Mass Notification
When used for mass notification, special zones ZF20, ZF21, and ZF22 can be used to signal the MN event.
NOTE: During local or network Walk Test, activating a Mass Notification device will activate associated special function zones according to CBE programming and simulate a Mass Notification event. Any network nodes, zones, or devices not participating in Walk Test will not participate in the simulated Mass Notification event.
Special Zones F1-F4
The control panel also provides four Special Zones, F1-F4, which are outputs that do not appear on the Special Function Change screen. You can program Special Zones F1 to F4 into the CBE of an output device. Descriptions of F1, F2, F3, and F4 are detailed below:
To view the status of Special Functions F1-F4, use the Read Status function (refer to the NFS2-640 Operations Manual).
Table 2.11 Special Output Functions F1-F4 (1 of 2)
Special Function Specifies
F1 (Trouble less AC) An output programmed to turn on/off if a system trouble—other
than an AC power loss—occurs
28 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program Programming
Presignal delay time: 60-180 seconds
PAS selection: YES (PAS selected) or NO (PAS not selected)
Presignal programming status banner
Presignal (zone F0)
PRG PRESIGNAL FUNCT PRESIGNAL DELAY DELAY=180 PAS=NO F00
Delay Timer for releasing application: 1-60 seconds or 00 (no delay)
Releasing Zone programming status banner
Abort Switch: a thee-letter Abort switch Type Code (ULI, IRI, NYC, or AHJ)
Cross Zone option: specifies type of Cross Zone: N (none), Y, Z, or H
Soak Timer option:0000 (not used) or delay time (0001-9999 seconds)
Releasing zone (R0 shown)
PRG RELEASE FUNCT RELEASE CONTROL DELAY=00 ABORT=ULI CROSS=N SOK=0000 R00
Table 2.11 Special Output Functions F1-F4 (2 of 2)
Special Function Specifies
F2 (AC Trouble) An output programmed to turn on/off if an AC power loss or a
brownout condition occurs
F3 (Security) An output programmed to turn on/off if a Security input activates
F4 (Supervisory) An output programmed to turn on/off if a Supervisory input
activates
Selecting Special Zones
Select Special Zones by entering the Special Zone letter and number (for example, F0, R0, and so on) from the Special Function Change screen. The following sections show sample screens that display when you select a Special Zone.
F0 (Presignal/PAS) The Presignal screen provides fields for changing the delay time or PAS. For details on Presignal selections, refer to “Presignal and PAS Time” on page 92. From the Special Function Change screen, press the F key, then press the 0 key to display the Presignal Function screen.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 29
R0-R9 (Releasing Functions) The Releasing Function screen provides fields for changing releasing functions: Delay Timer, Abort
Switch, Cross Zone, and Soak Timer. For details on
releasing applications, refer to “NFPA Releasing Applications” on page 61.
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the DELAY TIME and SOK (soak time) entries.
From the Special Function Change screen, select a function (R0-R9) to display the Releasing Function screen:
Programming Basic Program
Time Control programming status banner
Time Control zone (F5 shown)
Eighth day-of-week selection (H) that specifies when time control settings take effect. Press the
NEXT or PREVIOUS
key to toggle each selection.
ON time: Start Time for Time Control function (in 24-hour time) that must precede the OFF time.
OFF time: End time for Time Control function (in 24-hour time) that must be later than the ON time.
PRG TIME FUNCTION TIME CONTROL ON=08:00 OFF=12:00 DAYS=SMTWTFSH F05
Holiday programming status banner
Nine fields for selecting holidays: USA time (mm/dd)
PRG HOLIDAY FUNC **/** **/** **/** **/** **/** **/** **/** **/** **/**
Coding Function selection (refer to “Coding Functions for NACS” on page 93)
Coding Function programming status banner
Coding Function (Zone F8)
PRG CODING FUNCTION CODE TYPE MARCH TIME F08
F5-F6 (Time Control Functions) The Time Control screen provides fields for changing the start time, stop time, or days of the week. For details on time selections, refer to “Time Control Zones” on page 93. From the Special Function Change screen, select F5 or F6 to display the Time Control screen:
F7 (Holiday) The Holiday screen provides fields for specifying up to nine holiday dates. For details on holiday selections, refer to “Time Control Zones” on page 93. From the Special Function Change screen, press F7 to display the Holiday screen:
30 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
F8 (Coding Function) The Coding Function screen provides fields for specifying one of the following coding functions: March Time, Two-stage, California, Temporal, Two-Stage Canada (3 minutes), Two-Stage Canada (5 minutes), Two-Stage Canada Manual, System Sensor Strobe, Gentex Strobe, and Wheelock Strobe. For details on selecting coding functions, refer to “Coding Functions for NACS” on page 93. From the Special Function Change screen, press F8 to display the Coding Function screen:
Loading...
+ 96 hidden pages