Honeywell IntelliPath, LTE-CFV, LTE-CFA Installation And Setup Manual

IInntteelllliiPPaatth
h
M
TTM
SSeerriieess CCoommmmuunniiccaattoorr
LLTTEE--C
LLTTEE--C
CCoommmmeerrcciiaall FFiirree PPaanneell IInntteerrnneett aanndd CCeelllluullaarr CCoommmmuunni
CFFVV
CFF
A
A
iccaattoorr
Installation and Setup Guide
800-24454 9/18 Rev A
Table of Contents

SECTION 1: General Information ..................................................................................................................... 1
System Overview .......................................................................................................................................... 1
Introduction ............................................................................................................................................ 1
General Information ............................................................................................................................... 1
System Features ........................................................................................................................................... 2
About AlarmNet-i Internet Application .......................................................................................................... 2
Encryption ..................................................................................................................................................... 2
Operation ...................................................................................................................................................... 2
Supervision Features .................................................................................................................................... 2
Specifications ................................................................................................................................................ 3
Compatibility ................................................................................................................................................. 4
Compliance ................................................................................................................................................... 4
SECTION 2: Mounting and Wiring ................................................................................................................... 5
Determine the Signal Quality and Select a Location .................................................................................... 5
Mount the Communicator ............................................................................................................................. 6
Wire the Communicator ................................................................................................................................ 7
Wire the Internet Connection ........................................................................................................................ 8
Power Up the Communicator ....................................................................................................................... 8
SECTION 3: Programming the Communicator............................................................................................... 9
General Information ...................................................................................................................................... 9
Programming the Control Panel to work with the LTE-CF ..................................................................... 9
Programming for UL864 Compliance ................................................................................................... 10
Using the AlarmNet 360 Website ......................................................................................................... 10
Using a 7720P Programming Tool ....................................................................................................... 11
Using the Control Panel Programming Mode ...................................................................................... 11
Programming Conventions .................................................................................................................. 12
Programming .............................................................................................................................................. 12
Exiting Programming Mode ........................................................................................................................ 15
Setting Factory Defaults ............................................................................................................................. 15
SECTION 4: Registration ................................................................................................................................ 17
Registering the Communicator ................................................................................................................... 17
Registering through the AlarmNet 360 Website .................................................................................. 17
Register using the TEST / REGISTRATION Switch ............................................................................ 18
Register using the Programming Tool ................................................................................................. 18
Replacing an existing communicator ................................................................................................... 19
Register by Phone ................................................................................................................................ 19
i
LTE-CF Installation and Setup Guide
SECTION 5: Programmer Keyboard Commands ......................................................................................... 21
Identification Displays ................................................................................................................................. 21
Cell Status Displays .................................................................................................................................... 22
System Status Display ................................................................................................................................ 25
SECTION 6: Network Diagnostics ................................................................................................................. 27
Running Network Diagnostics .................................................................................................................... 27
Possible Errors Running Network Diagnostics ........................................................................................... 28
Appendices ..................................................................................................................................................... A-1
Appendix A : Summary of LED Operation ................................................................................................. A-1
Appendix B : Central Station Messages .................................................................................................... B-1
Appendix C : Glossary ............................................................................................................................... C-1
Wiring Diagram………………………………………………………………………………..………………...Inside Back Cover
ii
SECTION 1
General Information

System Overview
Introduction
Congratulations on your purchase of Honeywell's LTE-CFV/LTE-CFA Commercial Fire Panel Internet and LTE Communicator (henceforth referred to as LTE-CF). It represents the latest and most innovative communication technology for the security industry and uses the most sophisticated encryption to ensure the highest level of security for your customer.
The new cellular connectivity brings faster cellular data transfers with lower latency (response time); together it results in speedier data transfers.
This communicator uses the Internet as its primary reporting path, and switches to cell service (secondary path as backup) when the Internet is not available.
The communicator requires an AlarmNet–i account. For new installations, please obtain the account information from the central station prior to programming this communicator. For detailed information about enrolling the communicator and replacing communicators,
refer to the AlarmNet 360 Online Help Guide.
In addition to alarm reporting, the communicator provides upload/downloading capability of Honeywell's control panel data over the Internet, using cellular technology.
UL
General Information
The LTE-CF communicates via the Internet (when service is available) and switches to cellular (here-in known as “cell”) service when the Internet is not available.
In normal operation (with Internet connectivity), the LTE-CF communicates from your customer's network connection to the Honeywell Network Operations Center, (NOC) via the AlarmNet-i network. The NOC receives data and routes the information to the Central Station of your choice, based on the account number you assign to the communicator. Note that your Central Station needs to give you the account number. The same account number is used for both Internet and cell transmissions. If your current Central Station is capable of receiving signals from the Honeywell NOC, they are capable of receiving signals from the communicator.
If, for some reason, Internet connectivity is not available, (for example, your customer's ISP is off line or disconnected), the communicator will transmit signals via the cellular network. These transmissions are sent to the Honeywell NOC and then forwarded to your Central Station exactly the same way as if they were received via the Internet.
If the Internet and Cell network are both unavailable (fail), the message will not be sent from this communicator.
When performing remote downloading, a technician must be on-site to test the system after any programming is changed.
For maximum reliability, it is recommended the device be operated in dual path mode with Internet and Cell both enabled and connected.
1
System Features
Basic features include: Supports dynamic or static IP addressing, and installs behind firewalls without compromising
network security.
Quick connection to compatible Honeywell series control panels. Simple programming using a 7720P programming tool. Reports fire and status messages via the Internet. Reports messages via the Internet and uses Cellular as backup. Allows uploading and downloading of control panel data over the Internet.
(UL: A technician must be on-site to test the system after any programming is changed.)
About AlarmNet-i Internet Application
AlarmNet-i is a fully encrypted, secure method of delivering alarm messages from a protected premise to an AlarmNet equipped central station. The internet communicator transmits status, supervisory, and alarm messages to the AlarmNet Control Center using a broadband Internet connection.
The AlarmNet Control Center identifies, validates, and forwards the messages to the appropriate AlarmNet central station. AlarmNet-i has an unlimited account capacity.
Encryption
The communicator uses 256 bit AES (Rijndael) encryption (which is required for certain government installations). The AlarmNet-i AES Encryption Software Module Version 1.0 contained in the Honeywell products has NIST approval. Listings for this approval can be found at https://csrc.nist.gov/projects/cryptographic-algorithm-validation-program/validation/validation­list/aes and search for “Certification number 979.”
LTE-CF Installation and Setup Guide
UL
Operation
The communicator interfaces with the control panel using Honeywell’s ECP bus.
Used with any UL Listed control panel that supports ECP communication. The communicator connects to the control panel’s keypad terminals and provides 2-way
communication with the control panel using ECP messaging.
The control panel treats the communicator as an ECP device, so ensure to program the
control panel with the communicator’s device address.
Supervision Features
Reports are sent in Contact ID format.
The communicator provides the following types of supervision and fault detection: Network communication failure: In the event the AlarmNet network does not hear a
supervisory message from the communicator within a specified time, AlarmNet notifies the central station of a communication failure.
Communication path failure: In the event the module detects a communication path failure,
both the Central Station and the control panel can be notified of the trouble condition. Both failures are considered true faults when their fault times have expired. If the Internet or Cell communications path fails, a message is reported.
Primary power loss and low battery conditions (detected by the control panel, and may be
reported via the communicator if programmed to do so).
The IP and Cell signaling paths are suitable for encrypted line security. The system configurations are not suitable as a Dual Line Signal transmission system.
2
Section 1: General Information
Specifications
Mechanical:
Input Power:
Dimensions: 15.0"H x 12.75" W x 3.0" D Weight: 10 lbs.
12VDC supplied by the Control Panel.
Current Drain:
Ethernet:
90mA (rms) standby, 105mA (rms) active
Network Standard: IEEE 802.3u compliant Data Rate: 10Base-T / 100Base-T with auto detect Ethernet Cable: Cat. 5 (min), MDI / MDI-X auto crossover
Environmental:
Operating temperature: 0ºC to +49ºC Storage temperature: –40º to +70ºC Humidity: 0 to 85% relative humidity, non-condensing Altitude: to 10,000 ft. operating, to 40,000 ft. storage
Frequency Bands
LTE-CFV X X X
LTE-CFA X X X X X X X
Output Power
LTE, Class 3 23dBm
WCDMA Class 3 24dBm
LTE
Band 2
LTE
Band 4
LTE
Band 5
LTE
Band 12
LTE
Band 13
WCDMA
Band II
WCDMA
Band V
3
Compatibility
LTE-CF Installation and Setup Guide
UL – Compatible Control Panels
VISTA-32FB FA1670C (First Alert)
VISTA-32FBT FA1670CT (First Alert)
VISTA-128FBP FA1700C (First Alert)
VISTA-128FBPT FA1700CT (First Alert)
VISTA-250FBP
VISTA-250BPT
UL – Compatible Receivers
7810iR-ENT Must be the primary alarm receiver.
8810iR Must be the primary alarm receiver.
MX8000 Can be used for supplemental reporting in ECP mode when connected to
model 7810iR-ENT.
Compliance
Ademco 685 Can be used for supplemental reporting in ECP mode when connected to
model 7810iR-ENT.
7810PC Must be the primary alarm receiver
UL
The Automation System must be UL1981 listed.
To meet UL864/NFPA, ensure the following:
It must be installed in accordance with NFPA (National Fire Protection Association)
standards 70 and 72.
It must be mounted in the same room and within 20 feet of the fire panel. Conduit is required for all interconnections between the Fire Panel and communicator. All equipment used for the IP connection (such as the router, hub, modem, etc.) shall be
listed, must be powered from an un-switched branch circuit, and be provided with appropriate standby power.
4
SECTION 2
Mounting and Wiring

Determine the Signal Quality and Select a Location
The communicator must be mounted indoors within the protected premises. When choosing a suitable mounting location, understand that signal strength is very important for proper operation. For most installations using the supplied antenna, mounting the unit as high as practical, and avoiding large metal components provides adequate signal strength for proper operation.
In this procedure, you will use the communicator to determine signal strength to find a suitable mounting location.
RF Exposure
Warning – The internal or external antenna(s) used with this product must be installed to
provide a separation distance of at least 7.8 in. (20 cm) from all persons and must not be co­located or operating in conjunction with any other antenna or transmitter except in accordance with FCC multi-transmitter product procedures.
* LTE-CF Initial Power Up: Upon initial power up, the communicator LEDs blink in repeated sequence from top to bottom indicating network initialization.
Green (REG) Yellow (TX/RX) Red (FAULT) This sequence may take up to 15 minutes. Do not reset power during this time. When initialization is complete, the Signal Quality display LEDs will light and the yellow and
red LEDs may blink (per their respective functions). After initial network setup, subsequent resets or power ups can take up to 90 seconds.
1. For this procedure, you will need a fully charged 6V battery.
2. Attach the two Antenna Mounting Adapters, two RF cable, and two Antennas. Remove the top knockout if necessary. Refer to the Wiring Diagram on the inside of the back cover for wiring and component identification.
3. Temporarily connect the battery to the communicator (Jumper wire between TB1 pins 2 and 3, Battery Positive on TB1 pin 3, and Battery Negative on TB1 pin 4). Wait about one minute for the communicator to initialize.
4. Position the assembly near a suitable mounting position and observe the signal quality display. Choose a location with the best signal strength by observing the signal quality bar
graph (refer to Appendix A for information about signal quality and status indications).
Signal quality should be within 2-5 bars lit solid. For optimal performance 4 or 5 bars are better. The best signal strength is usually found at the highest point in the building, near a window.
5. Verify the signal strength remains steady for a few minutes, then mark that mounting position. Disconnect the battery.
5
Mount the Communicator
This communicator comes fully assembled with all the components mounted except the external Antenna, and Antenna Mounting Adapter.
Refer to the Wiring Diagram on the inside of the back cover for wiring and component identification.
For UL compliant installations, refer to the topic on Compliance in Section 1 of this manual. For Dry/Indoor use only. Unless otherwise specified, use 18AWG. Installation must be in accordance with the National Fire Alarm and Signaling Code,
ANSI / NFPA 72.
1. Remove knockouts from cabinet to accommodate the wiring to the control panel, and internet connection to a router. Then mount the cabinet securely to the wall using 4 screws or bolts. Use mounting screws or bolts that are suitable for the material being anchored to.
2. Ensure the cabinet door lock is installed.
3. Connect and route 16AWG (minimum) insulated wire from facility power ground (typically a cold-water pipe) to the cabinet's ground post. Ensure all ground connections are tight.
4. Ensure the following:
All wiring terminals and connectors are tight. All wiring has been completed and secured with cable ties.
5. When the communicator wiring and programming (next section) is complete, lock the cabinet.
LTE-CF Installation and Setup Guide
6
Section 2: Mounting and Wiring
Wire the Communicator
UL
Installation must be in accordance with; the National Electrical Code. The communicator must be connected to a UL Listed compatible control panel. All interconnecting wires between the UL Listed control panel and the communicator must be less
than 20 feet in length contained in the same room. All interconnecting wiring must be installed in rigid metal conduit or EMT (Electrical Metallic Tubing) where exposed on interior walls; or in flexible metal tubing if run in the walls or ceiling.
All equipment used for the IP connection (such as the router, hub, modem, etc.) shall be listed, must
be powered from an un-switched branch circuit, and be provided with appropriate standby power.
A UL listed control panel must monitor the radio fault output of the communicator.
Most Honeywell control panels support ECP data communication. Check the Installation and Setup Guide for the control panel you are using to see if it supports ECP communication.
The communicator’s ECP wiring will be in parallel with keypads and other peripheral devices such as RF receiver, etc., of the control panel. Wire length/gauge limitations are the same for the communicator as they are for keypads and other peripheral devices. To wire the communicator, see the figure below and make the following connections:
TB1
AC INPUT 1
1
AC INPUT 2
2
ECP (+) VOLTAGE INPUT
3
GND
4
5
ECP DATA IN
6
ECP DATA OUT
J1
NO CONNECTION
CONTROL PANEL
+12 V AUX
GND
DATA OUT
DATA IN
NO CONNECTION
NO CONNECTION
RED
BLK
YEL
GRN
COMMUNICATOR
IGSMCFP4G-013-V1
Item Notes
Wiring
UL: Use minimum 18AWG wire.
Power The communicator is powered from the control panel.
Ensure a jumper is installed between TB1 pins 2 and 3.
ECP data The control panel treats the communicator as an ECP device, so ensure to program the
control panel with the communicator’s device address.
7
Wire the Internet Connection
For UL installations, the Ethernet connection between the communicator and the router can-
not exceed 20 feet with both the communicator and the router located within the same room.
UL
All equipment used for the IP connection (such as the router, hub, modem, etc.) shall be
listed, must be powered from an un-switched branch circuit, and be provided with appropriate standby power.
Connect one end of the Ethernet cable to the communicator’s RJ45 Ethernet connector and the other end to the cable / DSL router as shown in the figure below.
7720P PROGRAM CONNECTOR
LTE-CF Installation and Setup Guide
RJ45 (FOR INTERNET CONNECTION)
Power Up the Communicator
Power up the control panel. (Initially, all communicator programming options are set to the factory default settings.)
TO ROUTER
LTE-CF-001-V1
8
Loading...
+ 28 hidden pages