Honeywell LP920 Catalog Page

Pneumatic Temperature Controllers
BM
3-1/8
(80)
2-11/16
(68)
2-3/4
(70)
5-9/16 (142)
2-1/4
(57)
M18367
M
M B
COIL
DA
C5400
LP920 Remote Bulb Temperature Controllers
Two-pipe, single temperature, pneumatic temperature controller used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell two-pipe pneumatic temperature controller.
• Fahrenheit or Celsius scales for all adjustments.
• Pilot operated for high capacity.
• Direct Acting (DA) and Reverse Acting (RA) models are available.
• Adjustable setpoint and throttling ranges.
• Scales in bold type for high visibility.
• Replaceable filter cartridge.
• Single point or averaging elements.
Dimensions Diagram in inches (millimeters)
Airflow Usage: 0.011 scfm (5.2 mL/s) Maximum Operating Temperature: Element: 230 F, Controller: 150 F
(Element: 110 C, Controller: 66 C)
Maximum Storage Temperature: 150 F (66 C) Maximum Safe Operating Pressure: 30 psi (207 kPa) Throttling Range:
(Factory set at 6K with adjustment range of 3 to 15 K)
Remote Bulb Sensor: yes Comments:
Scale plate is revers ble for F and C applications
Accessories:
315046B-Well, 1/2 NPT Copper, 7 1/2 in. (191 mm) long 315904B-1/2 in. NPT stainless steel Well, 7 5/16 in. (186 mm) long 14001865-001-Filter Cartridge Assembly 14002172-001-Gage Tap repair plug
Factory set at 10 F with adjustment range of 5 to 25 F
Pneumatic
Scale Range
Includes(F) (C)
Product Number Action
Number of Pipes
LP920A1005/U Direct Acting 2 30 F to 150 F -1 C to +66 C 8 ft (2.4 m) averaging element for duct mounting
LP920A1013/U Direct Acting 2 30 F to 150 F -1 C to +66 C 3/8 x 5 1/4 in. (10 x 133 mm) bulb with 3 in. (76 mm) capillar y,
LP920A1021/U Direct Acting 2 30 F to 150 F -1 C to +66 C 3/8 x 5 1/4 in. (10 x 133 mm) bulb with 10 in. (254 mm) capillary,
LP920A1039/U Direct Acting 2 30 F to 150 F -1 C to +66 C 3/8 x 5 1/4 in. (10 x 133 mm) bulb with 5 ft. (1.5 m) capillary,
LP920B1037/U Reverse Acting 2 30 F to 150 F -1 C to +66 C 3/8 x 5 1/4 in. (10 x 133 mm) bulb with 5 ft. (1.5 m) capillary,
well mount
integral duct mount
remote duct mount
remote duct mount
Typical coil discharge control Typical mixed air control
DAMPER
E.P.
OPERATOR
RELAY
O.A. D.A.
LP920B
M B
REVERSE ACTING SET 75F (24C) T.R. 5F (3C)
R.A.
N.O.
N.C.
M B
M
COIL
LP920A DIRECT ACTING SET 55F (13C) T.R. 10F (5.5C)
C6501
Controls
70-6910 663