►When performing any work (installation, mounting, start-
up), all instructions given by the manufacturer and in
particular the safety instructions provided in these
Installation and Commissioning Instructions are to be
observed.
►The LION System (including the CLLIONLC01, I/O
modules, manual disconnect modules, and the auxiliary
terminal packages) may be installed and mounted only
by authorized and trained personnel.
►Rules regarding electrostatic discharge should be
followed.
►If the LION System is modified in any way, except by the
manufacturer, all warranties concerning operation and
safety are invalidated.
►Make sure that the local standards and regulations are
observed at all times. Examples of such regulations are
VDE 0800 and VDE 0100 or EN 60204-1 for earth
grounding.
►Use only accessory equipment which comes from or has
been approved by CentraLine.
►It is recommended that devices are to be kept at room
temperature for at least 24 hours before applying power.
This is to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
►The LION System must be installed in such a manner
(e.g., in a lockable cabinet) as to ensure that uncertified
persons have no access to the terminals.
►Investigated according to United States Standard UL916
(USL-listed).
►Investigated according to Canadian National Standard(s)
C22.2 (CNL-listed).
Safety Information as per EN60730-1
Purpose
The LION System is an incorporated electronic control
system for cabinet mounting.
It is used for the purpose of building HVAC control and is
suitable for use only in non-safety controls for installation on
or in appliances.
Pollution degree
Overvoltage
category
Rated impulse
voltage
Automatic action
Software class Class A
Ball-pressure test
temperature
Electromagnetic
interference
System transformer Europe: safety isolating
Pollution Degree 2,
suitable for use in residential
controls, commercial controls,
in a clean environment.
Category II
for mains-powered (16A) controls
Category I
for 24 V powered controls
2500 VAC
Type 1.C
(micro-interruption for the relay
outputs)
75 °C for all housing and plastic
parts
125 °C in the case of devices
applied with voltage-carrying parts
and connectors
Tested at 230 VAC,
with the modules in normal
condition.
transformers according to
IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers
Table 1 System data as per EN60730-1
EN1Z-0921GE51 R0315 2
LION System System Overview
System Overview
System Architecture
A LION System consists of the CLLIONLC01 Controller and various I/O modules.
The CLLIONLC01 Controller provides interface connections, which allow connection to external systems.
Auxiliary parts enable special features.
Panel I/O (CLIOPxx)
Panel Bus (<40 m)
existing XL500
controllers
C-Bus
CLLIONLC01 + CLIOxx
LonWorks Bus
LonWorks I/O (CLIOLxx)
Fig. 1 LION System architecture
ControllerI/O Modules
Fig. 2 CLLIONLC01 Controller and I/O modules
CLMMI00N22 or CLMMI00N31MODEM
XFCLxxxXFCxxxSERVAL
3 EN1Z-0921GE51 R0315
System Overview LION System
X
X
X
X
I/O Modules
Pluggable I/O Modules
There are 2 variants of pluggable I/O modules (consisting of
a terminal socket and a removable electronic module):
Panel Bus I/O modules with communication via Panel
Bus (light gray housings)
Modules are automatically commissioned (with firmware
download) by the CLLIONLC01 Controller
L
ONWORKS Bus I/O modules (dark gray housings) with
communication via L
compatible) for easy integration and use with 3
controllers
Mixed I/O Module
Besides the pluggable I/O modules, there are also mixed
Panel Bus I/O modules. Specifically: the CLIOP830A and
CLIOP831A are mixed Panel Bus I/O modules featuring an
integrated terminal socket and a variety of inputs and
outputs.
The CLIOP830A has a light-gray housing.
The CLIOP831A has a black housing.
Their firmware is automatically updated and configured by
the controller, and the controller automatically configures the
mixed Panel Bus I/O modules as needed by the application.
ONWORKS (FTT10-A, link power
pluggable
ANALOG INPUT
ANALOG OUTPUT
pluggable
rd
-party
pluggable
BINARY INPUT
Terminal Sockets
Pluggable I/O modules are mounted on the appropriate
terminal sockets. Pluggable Panel Bus I/O modules and
pluggable L
ONWORKS Bus I/O modules use the same
terminal sockets. The terminal sockets are available with
push-in terminals (XS821-22, XS823, and XS824-25) or with
screw-type terminals (XSU821-22, XSU823, and XSU824-
25). The mixed Panel Bus I/O modules (i.e. the CLIOP830A
with push-in terminals, and the CLIOP831A with screw-type
terminals) feature an integrated terminal socket.
Color Coding
To distinguish modules and components, the following color
coding is used:
Color Part
Red
All user-accessible adjustable mechanical
parts (i.e., bridge connectors and locking
mechanism) and operating controls (manual
overrides, etc.)
Light-gray Panel Bus I/O modules (exc. CLIOP831A)
Black CLIOP831A mixed Panel Bus I/O module
Dark-gray LONWORKS Bus I/O modules
Table 2 Color coding of LION Modules
pluggable
RELAY OUTPUT
pluggable
FLOATING
OUTPUT
MIXED I/Os
(with integrated electronic module)
LonWorks
CLIOLR822A
BUS MODULES
CLIOL821A
PANEL
CLIOL822A
CLIOPR822A
BUS MODULES
CLIOP821A
CLLIONLC01
CLIOP822A
XS821-22
XSU821-22
LonWorks or Panel Bus
Fig. 3 Overview of I/O modules and terminal sockets
CLIOL823A
CLIOP823A
S823
SU823
CLIOLR824A
CLIOL824A
CLIOPR824A
CLIOP824A
CLIOPR825A
S824-25
SU824-25
Honeywell
Install. Instr.
MU1B-0473GE51
Honeywell
Install. Instr.
MU1B-0473GE51
123456789101112
DI
123456789101112
DI
CLIOP830A
Analog Outputs
Binary Inputs
Analog Inputs
GND
AO5
AI5 AI6 AI7 AI8
B10
B11
B9
B8
B7
B12
12
11
10
9
8
7
17 18 19 20
25 26 27 28
5
6
4
3
2
1
41 42
14 15 16
13
21
AO1
AI1
B1 B2 B3 B4 B5 B6
G1 G2
AI2 AI3 AI4
CLIOP831A
Binary Inputs
Analog Outputs
Analog Inputs
GND
AO5
AI5 AI6 AI7 AI8
B11
B10
B9
B8
B7
B12
12
11
10
9
8
7
17 18 19 20
25 26 27 28
6
5
4
3
2
1
41 42
14 15 16
13
21
AO1
AI1
B1 B2 B3 B4 B5 B6
G1 G2
AI2 AI3 AI4
CLIOP830A
CLIOP831A
24V Relays
AO6
AO7
AO8
CO1CO2CO3CO4CO5CO6
35
36 37 38 39 40
22 23 24
29 30 31 32 33 34
AO2
AO3
AO4
NO1NO2NO3NO4NO5NO6
!
123456
DO
24V Relays
AO6
AO7
AO8
CO1CO2CO3CO4CO5CO6
35
36 37 38 39 40
22 23 24
29 30 31 32 33 34
AO2
AO3
AO4
NO1NO2NO3NO4NO5NO6
!
123456
DO
EN1Z-0921GE51 R0315 4
LION System System Overview
1
)
I/O Module Overview
Panel Bus
module
LONWORKS
Bus module
Description Inputs OutputsManual controls LEDs 1)
CLIOP821A CLIOL821A Analog input module 8 – – –
CLIOP822A CLIOL822A Analog output module – 8 – 8 status LEDs
CLIOPR822A CLIOLR822A Analog output module – 8 8 Manual overrides 8 status LEDs
The manual override switches and potentiometers of the output modules (…R822A, …R824A, and CLIOPR825A) support direct
operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the
LION Controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding output LED will blink continuously, and the output module will send a feedback signal with the status "manual
override" and the given override position to the LION Controller (which will then also store this information in its alarm memory).
NOTE:When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
connected push-in terminals, for
distributing signals/power.
Two groups of four pairs of
push-in terminals, for converting
0…20 mA signals into
0…10 Vdc signals, and one
push-in ground terminal per
group.
Table 5 Auxiliary parts
Spare Parts
Module Type Figure
Cross connectors (red) XS815
Connector bridge XS816
Swivel label holder XAL10
Swivel label holder XAL11
Table 6 Spare parts
Corresponding
I/O modules
Information
CLIOP/CLIOL…
…824
…825
All LION I/O modules
Connects 6 relay commons.
Connects CLLIONLC01 and I/O
modules.
All pluggable LION I/O
modules
Can be plugged into socket, for
attaching label generated by the
engineering tool.
Can be plugged into module, for
CLIOP830A, only
attaching label generated by the
engineering tool.
NOTE: Phased out.
EN1Z-0921GE51 R0315 6
LION System System Overview
Interfaces and Bus Connections
The LION System can be connected to the following devices
and systems:
Panel Bus
For communication with up to 16 Panel Bus I/O modules
Polarity-insensitive
L
ONWORKS Bus
For communication with other L
within the building
FTT10, link power compatible
Polarity-insensitive
C-Bus
For communication with other controllers, e.g., existing
Excel 500 Controllers
HMI
For connecting an operator interface (e.g., CLMMI00N22
or CLMMI00N31) or a laptop, e.g., for engineering
Modem
For connecting a modem or an ISDN terminal adapter
ONWORKS Bus devices
Technical Data
System Data
Operating voltage 24 VAC, ± 20 %, 21 … 30 VDC
Max. number of C-Bus
participants
Current requirement
Push-in terminals 1.5 mm2
Screw-type terminals 1.5 mm2
Overvoltage protection All inputs and outputs are
Calculated lifetime of
weakest component
under typical operating
conditions
30
Max. 3.57 A
(1 CLLIONLC01 Controller
+ 16 I/O modules)
protected against 24 VAC and
40 VDC overvoltage as well as
against short-circuiting.
MTBF
13.7 years
Standards
Protection class IP20
Product standard
(EMC)
Testing electrical
components
Certification CE
System transformer
Low-Voltage Device
Safety Assessment
Table 8 Standards
EN 60730-1
EN 60730-2-9
IEC68
The system transformer(s) must
be safety isolating transformers
according to IEC 61558-2-6.
In the U.S.A. and Canada, NEC
Class 2 transformers must be
used.
EN 60730-1
EN 60730-2-9
Operational Environment
Ambient operating
temperature
Ambient operating
humidity
Ambient storage
temperature
Ambient storage
humidity
Vibration under
operation
Dust, vibration According to EN60730-1
RFI, EMI Home environment
Table 9 Operational environment
0 … 50 °C (32 … 122 °F)
5 … 93 % rel. humidity
(non condensing)
–20 … 70 °C (–4 … +158 °F)
5 … 95 % rel. humidity
(non condensing)
0.024” double amplitude
(2 … 30 Hz),
0.6 g (30 … 300 Hz)
Table 7 System data
7 EN1Z-0921GE51 R0315
Planning LION System
Planning
Overview
Engineering with CARE
During CARE engineering, the type of I/O modules, terminal
assignment and module configuration are defined
depending on the application. The same applies to
engineering with COACH (which is possible starting with
COACH version 2.02).
Planning
In this step, the following has to be defined, if applicable:
Power supply
Fusing
Earth grounding
Lightning protection
Panel Bus wiring
Design of a L
Design of a C-Bus network
Useful accessories
Cable selection
ONWORKS network
Transformer Selection
NOTE: In Europe, the system transformer(s) must be
Current Requirement
When selecting the appropriate transformer, take into
account the number of individual modules, accessories, and
field devices in determining the total current requirement.
Devices powered
CLLIONLC01 with
CLMMI00N22 (backlight ON)
and with watchdog load (max.
500 mA)
CLLIONLC01 with
CLMMI00N22 (backlight ON)
but without watchdog load
…821 130 mA 80mA
…822 160 mA 90 mA
…823 180 mA 130 mA
…824 140 mA 90 mA
…825 140 mA 90 mA
CLIOP830A 200 mA 95 mA
safety isolating transformers according to
IEC61558-2-6.
In the U.S.A. and Canada, NEC Class-2
transformers must be used.
Current requirement
24 VAC 24 VDC
690 mA 640 mA
190 mA 140 mA
Table 10 Current requirement of LION System components
depending on power supply
Connectable Power Supplies
CentraLine CRT Series (Europe)
Transformer Primary side Secondary side
CRT 2 220/230 VAC 24 VAC, 50 VA, 2 A
CRT 6 220/230 VAC 24 VAC, 150 VA, 6 A
CRT 12 220/230 VAC 24 VAC, 300 VA, 12 A
Table 11 CentraLine CRT series transformers data
EN1Z-0921GE51 R0315
8
LION System Planning
CentraLine 1450 Series (North America)
50/60 Hz
Insulated accessory outputs
Built-in fuses
Line transient /surge protection
AC convenience outlet
NEC Class-2
Part number
1450 7287
-001 120 VAC 24 VAC, 50 VA
-002 120 VAC
-003 120 VAC
-004 240/220 VAC 24 VAC, 50 VA
-005 240/220 VAC
-006 240/220 VAC
Table 12 CentraLine 1450 series transformers data
Standard Transformers (Europe, North America)
Standard commercially available transformers used to
supply power to LION Systems must fulfill the following
specifications:
Output voltage Impedance AC current
24.5 VAC to 25.5 VAC
24.5 VAC to 25.5 VAC
24.5 VAC to 25.5 VAC
Table 13 Requirements for standard transformers
RIN-APU24 Uninterruptable Power Supply
The RIN-APU24 Uninterruptable Power Supply can be wired
to power LION Systems.
See also RIN-APU24 Uninterruptable Power Supply –
Mounting Instructions (MU1B-0258GE51) for detailed wiring
diagrams.
Primary sideSecondary side
2 x 24 VAC, 40 VA,
and 100 VA from separate
transformer
24 VAC, 100 VA,
and 24 VDC; 600 mA
2 x 24 VAC, 40 VA,
and 100 VA from separate
transformer
24 VAC, 100 VA, and
24 VDC, 600 mA
1.15 Ω
0.40 Ω
0.17 Ω
max. 2 A
max. 6 A
max. 12 A
Power Supply of Field Devices
Depending upon the power consumption of the field devices
used, it is possible to use either a single transformer to
power both the CLLIONLC01 and attached field devices, or
it may be necessary to employ an additional transformer.
See also section "Field Device Cables" on page 12 and
connection examples on page 28.
Fusing Specifications
Please observe the following when selecting fusing (F1 / F2)
for the CLLIONLC01, I/O modules, and active field devices:
Use separate fusing for different loads (e.g., for the
CLLIONLC01 and I/O modules on one hand versus for
active field devices on the other).
Fuse ratings must always be calculated according to the
loads connected. Refer to the load tables appearing in
the documentation of your devices (Table 10 provides
information on LION device loads).
Use slow-acting fuses; this is because the CLLIONLC01,
the I/O modules, and active field devices have a high inrush current due to their built-in capacitors (current
typically limited by one internal 2 Ohm resistor per
device).
Fuses should be calculated to protect the transformer
against overloading and the wiring against shortcircuiting. The CLLIONLC01 and the I/O modules are
protected by an internal fuse (not user-replaceable)
against internal component defects.
For connection examples see description of the I/O modules
on page 38 and following.
System Protective Earth Grounding
LION Systems comply with SELV (Safety Extra-Low
Voltage). Earth grounding is therefore not recommended.
However, if compliance with EN60204-1 is required, see
Appendix 1.
Lightning Protection
Please contact your local CentraLine representative for
information on lightning protection.
Panel Bus Topologies
Up to 16 Panel Bus I/O modules can be controlled by a
single CLLIONLC01.
Panel Bus I/O modules must be addressed using the
HEX switch on the terminal socket.
Max. Panel Bus length: 40 meters. Any type of cabling
and topology (including star and loop topology) permitted.
Bus termination unnecessary
Polarity-insensitive
9 EN1Z-0921GE51 R0315
Planning LION System
X
LONWORKS Bus Topologies
The LONWORKS Bus is a 78-kilobit serial link that uses
transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two L
ONWORKS
Bus terminals are connected to each wire of the twisted pair.
The L
ONWORKS Bus does not need to be shielded on the
controller module side.
The L
ONWORKS Bus can be wired in daisy chain, star, loop
or any combination thereof as long as the max. wire length
requirements are met.
Configuration
The recommended configuration is a daisy chain with two
bus terminations. This layout allows for max. L
ONWORKS
Bus lengths, and its simple structure presents the least
number of possible problems, particularly when adding on to
an existing bus.
See also “L
ONWORKS Mechanisms”, Product Literature no.:
EN0B-0270GE51.
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The
C-Bus must be connected via the individual controllers
(open ring).
NOTE:Star connection is not allowed as this might
Instead of LION Controllers, other C-Bus controllers (e.g.,
the Excel 500, Excel 100, PANTHER) can also be
connected.
Fig. 4 C-Bus topology Excel 5000
cause uncontrollable line reflections.
LIONExcel 100Excel 500PANTHER
Accessories
Besides the auxiliary parts of Table 5 on page 6, the
following accessories are available.
Preconfigured Connection Cables
Type
XW882
XW582
+ XW586
XW884
XW885 Laptops
XW585
+ XW586
XW586 Modems
Table 14 Preconfigured connection cables
XW882 Cable Details
RJ45 plug with clip at front
Fig. 5 CLLIONLC01/CLMMI00N22 cable details
XW884 Cable Details
RJ45 plug with clip at front
Connecting
CLLIONLC01 with
CLMMI00N22 Operator
Interface
CLMMI00N22 Operator
Interface
Adapter cable for Excel
500/600 Controllers
Laptops
12
SHIELD
3678
4
5
+5V
XW882
12
SHIELD
3678
4
5
+5V
Features
5 m, shielded,
RJ45 plug with clip
See XW582 and
XW586
0.2 m, shielded,
RJ45 – 9 pin sub-D
3 m, shielded,
RJ45 plug with clip
See XW582 and
XW586
1.8 m, RJ45 – 9 pin
sub-D
LOOSE
ENDS
G
R
A
Y
L
E
L
R
B
O
G
R
E
W
H
CLMMI00N22
TERMINALS
e
s
u
t
o
n
(
Y
d
D
x
O
T
W
+
5
E
V
W
N
D
x
R
E
N
E
T
I
D
G
N
WIRING
)
RS232 plug
sub-D female
1
R
D
x
S
R
T
D
x
T
G
N
D
2
3
4
5
1
2
3
4
6
7
8
9
W884
Fig. 6 CLLIONLC01/Excel 500/600 cable details
EN1Z-0921GE51 R0315
10
LION System Planning
XW885 Cable Details
RJ45 plug with clip at front
and protective sheathing
1
SHIELD
2
36
4
5
7
+5V
8
XW885
Fig. 7 CLLIONLC01/laptop cable details
XW582 Cable Details
LOOSE
to XC5010C
1
6
2
7
3
8
4
9
5
SHIELD
ENDS
XW582
Fig. 8 XW582 cable details
XW585 Cable Details
RS232 plug
sub-D female
1
6
2
7
+5V
3
8
4
9
5
SHIELD
RS232 plug
sub-D female
D
C
D
R
D
x
R
T
S
T
D
x
T
C
S
D
R
T
I
R
G
N
D
CLMMI00N22
WIRING
TERMINALS
D
O
L
W
x
T
Y
L
E
+
5
W
R
E
N
O
B
V
D
E
x
E
N
R
G
R
W
E
T
I
H
D
G
N
RS232 plug
sub-D female
x
R
D
R
T
S
T
D
x
D
G
N
LONWORKS Bus Termination Modules
Type Description
1
XAL-Term2
6
2
7
3
8
4
9
5
L
ONWORKS connection and ter-
mination module, which can be
mounted on DIN rails and in fuse
boxes
Table 15 LONWORKS Bus termination modules
Cable Specifications
Power Supply Cables
When checking the length of the power supply cable, the
connection cables to all I/O modules must be taken into
account.
1
2
3
4
Max. length
Cross section min. 0.75 mm2 (AWG 18)
Table 16 Power supply cables specification
Panel Bus Cables
Max. length 40 m
Cable type twisted pair, e.g., J-Y-Y 2 x 2 x 0.8
1
Table 17 Panel Bus cables specification
6
2
7
3
8
4
9
5
3 m (per side of the controller),
see Fig. 32 on page 24
XW585
Fig. 9 XW585 cable details
XW586 Cable Details
RJ45 plug with clip at front
12
3678
4
5
+5V
XW586
RS232 plug
sub-D male
C
D
D
S
D
R
D
x
R
T
S
R
D
T
x
C
T
S
D
T
R
G
D
N
1
6
2
7
3
8
4
9
5
Fig. 10 XW586 cable details
11 EN1Z-0921GE51 R0315
Planning LION System
LONWORKS Bus Cables
Cable type Max. bus length
Belden 85102 (plenum) 2700 m (8900 ft)
Belden 8471 (non-plenum) 2700 m (8900 ft)
Level IV, 22 AWG 1400 m (4600 ft)
JY (St) Y 2 x 2 x 0.8 900 m (3000 ft)
TIA568A Cat. 5 24AWG, twisted pair 900 m (3000 ft)
Table 18 Doubly-terminated bus specifications
NOTE: The above-listed cable types are as
NOTE: CentraLine recommends the use of level IV,
NOTE: Belden part numbers are 9H2201504 (plenum)
FTT Specification
The FTT specification includes two components that must
be met for proper system operation:
The distance from each transceiver to all other
If multiple paths exist, the max. total wire length is the
Cable type
Belden 85102 500 m (1650 ft) 500 m (1650 ft)
Belden 8471 400 m (1300 ft) 500 m (1650 ft)
Level IV, 22AWG 400 m (1300 ft) 500 m (1650 ft)
JY (St) Y 2 x 2 x 0.8 320 m (1050 ft) 500 m (1650 ft)
TIA568A Cat. 5
24AWG, twisted pair
recommended by Echelon in their FTT-10A User
Guide.
22 AWG, solid core, non-shielded cable.
and 9D220150 (non-plenum).
transceivers and to the termination must not exceed the
max. node-to-node distance.
total amount of wire used.
Max. node-tonode distance
250 m (825 ft) 450 m (1500 ft)
Max. total wire
length
NOTE: In the event that the limit on the total wire length
is exceeded, the FTT physical layer repeaters
(FTT 10A) can be added to interconnect segments. This increases the overall length by an
amount equal to the original specification for that
cable type and bus type for each repeater used.
For example, adding repeaters for a doublyterminated bus using JY (St) Y 2 x 2 x 0.8 cable
increases the max. length by 900 m (3000 ft) for
each repeater.
Field Device Cables
Cross-sectional area
Type of signal
24 VAC power
0…10 V signals 0.081 – 2.08 mm2 (28 – 14 AWG)
Table 20 Cable sizing for connection of field devices
D = XS831 Aux. Terminal Package (optional)A, B, and C = XS830 Aux. Terminal Packages (optional)
Fig. 13 Mixed I/O Module CLIOP830A (shown with four auxiliary terminal packages), dimensions (in mm)
External
COM a
40
24V
COM b
24V~0
IN3
IN5 IN6
IN1 IN2
IN4
36 37 38 39 40
29 30 31 32 33 34
B
B1 B2B3B4
D
76
77
24V~
78
DO
B5 B6 B7 B8 B9
!
110
69
28
15
SWIVEL LABEL HOLDER
92.5
45
51.5
15 EN1Z-0921GE51 R0315
Mounting/Dismounting ModulesLION System
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
► Do not touch any live parts in the cabinet.
► Disconnect the power supply before you start to install
the LION System.
More than one disconnect switch may be required to deenergize the system.
►Do not reconnect the power supply until you have
completed the installation.
►Unused terminals must be closed (by completely
screwing in the terminal screws), thus preventing the
accidental touching of “live” parts.
NOTE:The terminal socket of each pluggable I/O
module can be mounted and wired before
inserting and locking the corresponding electronic
module.
12
71 COM a
72 COM b
73 24V
~
74 24V 0
~
LON
C-BUS RESET PC/HMI
8765 4 32 18765 4 321
111
S1 S2
9.6k all
12285
13396
14410 7
C-Bus
LON
in
Panel
mid
76k
LON
end
76k
C-Bus
I/O Bus
C-Bus
out
4
S1 S2
71 COM a
72 COM b
73 24V
~
74 24V 0
~
123
AAA
11
21
31
12
22
32
13
23
33
144424543464 25
Modem
Rx Tx
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
PRESS
COM a
COM b
24V
~
24V 0
~
!
8765 43 21
Power/
Alarm
PRESS
0
AUTO
!
41
51
42
52
43
53
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
PRESS
5678
1234
22 12345678
21
AUX
GNDGND
10 11 12 13 14 15 16 17 18 25 26
9
5
S1 S2
PRESS
12345678
100
AAAAAAAA
5678
21
22 1 234
616261
62
AUX
6363
GNDGND
9
10 11 12 13 14 15 16 17 18 25 26
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
!
AI/AOV
PRESS
0
AUTO
!
AI/AOV
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
5 6 7 8 9 10
1 234
123456789101112
BI
GND
13 14 15 16 17 18 19 20 21 22 23 24 25 2 6
S1 S2
PRESS
123456
100
11
21
31
12
22
32
13
23
33
144424543464 25
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
11 12
!
--1
--0
--AUTO
!
41
51
616261
42
52
62
43
53
6363
Mounting/Dismounting Controller/Sockets
Mounting Sockets
NOTE: When using both Panel Bus and LONWORKS Bus
NOTE: Up to 10 Panel Bus I/O modules can be mounted
NOTE: The CLLIONLC01 and the mixed Panel Bus I/O
Fig. 15 Max. number of Panel Bus I/O modules
3
Fig. 16 Max. number of L
I/O modules in a LION System, group both
Panel Bus modules (light gray) and L
Bus I/O modules (dark gray), e.g., on different
rails.
to one side of the controller. In total, up to 16
Panel Bus I/O modules can be mounted to one
controller.
module are mounted on the DIN rail in the same
way as a terminal socket.
PAN EL
BUS
I/O
max. 10
LonWorks
BUS I/O
max. 10
PAN EL
BUS
I/O
LonWorks
BUS I/O
CLLIONLC01
max. 16
CLLIONLC01
max. 20
ONWORKS Bus I/O modules with
PANEL
BUS
I/O
LonWorks
BUS I/O
power supply via CLLIONLC01
ONWORKS
PAN EL
BUS
I/O
max. 10
LonWorks
LonWorks
BUS
BUS I/O
I/O
max. 10
6
Fig. 14 CLLIONLC01 and I/O modules mounted on
multiple DIN rails
Legend
1 CLLIONLC01
2 Swivel label holder
3 Cable connection
4 Stopper (from 3
rd
-party supplier)
5 Bridge connectors
6 Auxiliary terminal package
EN1Z-0921GE51 R0315
16
LION System Mounting/Dismounting Modules
►Angle the terminal socket at the upper edge of the DIN
rail until it snaps in.
►Swing the terminal socket down and apply gentle force
until it snaps into position with an audible "click".
►Position controller module and terminal sockets flush with
one another along the rail.
►If desired, mount stoppers at the ends of the rail to
prevent sliding.
Fig. 17 Mounting terminal sockets
Connecting Sockets
Controller, terminal sockets, and mixed I/O modules on the
same DIN rail can be connected mechanically and
electrically with bridge connectors.
Controller and terminal sockets on different DIN rails must
be connected using cables, see Fig. 14 and page 23.
NOTICE
Risk of malfunction!
►Wire Panel Bus I/O modules and LONWORKS Bus
I/O modules separately.
►When using both Panel Bus and LONWORKS Bus
I/O modules in a LION System, L
I/O modules must be connected to the controller via
LON terminals 11 … 14.
Position the bridge connector on terminals 71 … 74 of the
right hand terminal socket or mixed I/O module or controller
and on terminals 75 … 78 of the left hand terminal socket or
mixed I/O module or controller. Then press the bridge
connector down.
ONWORKS Bus
NOTE:Take care to not bend the Omega clamp, which
serves to establish the electrical contact with the
DIN rail and which located on the back of the
terminal socket.
Fig. 18 Connecting terminal sockets with bridge
connector
NOTE:Bridge connectors transmit both communication
signals and power supply between modules.
Removing bridge connectors will thus interrupt
the transmission of both communication signals
and power supply between the modules.
17 EN1Z-0921GE51 R0315
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.