Honeywell L4188B, L4189B, L6188A, L6188C, L6189C User Manual

...
0
Honeywell
THESE BULB-TYPE CONTROLLERS PRO­VIDE OPERATING OR LIMIT CONTROL OF WATER TEMPERATURE IN HOT WATER HEATING SYSTEMS AND WATER HEATERS.
Cl L4188 and L4189 provide spst switching
for low limit and circulator control. Cl L4188, L6188 models are direct-
mounted.
0 L4189, L6189 models are remote bulb.
Cl Diaphragm-operated switch breaks on temperature rise (spst and normally closed spdt contacts).
q Compact controller case for application
flexibility. 0 3116 in. diameter bulb for faster
response. Cl All models available with or without
setting knob. Models without knob are ad-
justed with screwdriver.
Cl Choice of manual or auto reset. Auto reset models available with fixed or adjust-
able differential. Cl l/4 in. male quick-connects standard;
combination screw and l/4 in. quick­connects available.
0 Field adjustable high or low limit stop available.
Cl Bracket for surface mounting available on remote bulb models.
Cl Capillary on remote bulb models avail­able in several lengths.
Cl Immersion well with l/2 in. NPT spud available as accessory.
J.A.
2-86.
Form Number 68-0061
Qlioneywell Inc. 1986
SPECIFICATIONS
THE SPECIFICATIONS GIVEN IN THIS PUBLICATION DO NOT INCLUDE NORMAL MANUFACTURING TOLERANCES. THEREFORE, THIS UNIT MAY NOT MATCH THE LISTED SPECIFICATIONS EXACTLY. ALSO, THIS PRODUCT IS TESTED AND CALIBRATED UNDER CLOSELY CONTROLLED CONDITIONS, AND SOME MINOR DIFFERENCES IN PERFORMANCE CAN BE EXPECTED IF THOSE CONDITIONS ARE CHANGED.
MODELS: See Table 1.
TABLE l-AQUASTAT CONTROLLER SELECTION GUIDE
APPLICATION SWITCHING 1 MOUNTING
High or low limit
Low limit and
and circulator
Spst, breaks on
temp. rise.
Spdt, breaks C-l,
makes C-2 on
temp. rise.
Direct
Remote bulb
r
aSpecify when ordering. ELECTRICAL RATINGS:
24 Vat
Full Load Locked Rotor
SWITCHING: Diaphragm-operated, snap-acting switch.
L4188, L4189: switch breaks on temperature rise to
set point, remakes when temperature drops below set point and through differential.
L6188, L6189: switch breaks C-l and makes C-2 on
temperature rise to set point; switches back when temperature drops below set point and through
differential.
1 2.0A
- 1 48.0
1
120 Vat
1 8.0
A 1 5.1 A 1 30.6
IMPORTANT
Screwdriver slot
7,14or22F[4,8or12C],
Giizbkj adjustablea
Knob
Screwdrh
240 Vat
A
A
rer slot
TERMINALS: l/4 in. male quick-connects standard.
Options (specify when ordering):
-Combination screw and l/4 in. quick-connects.
-Separate grounding terminal.
TEMPERATURE SETTING RANGE: 80 to 200 F, 110 to
230 F, and 160 to 280 F [43 to 93 C, 38 to 110 C, and 71 to 138 C] available. Specify when ordering.
Temperature setting minus differential must be no
SETTING SCALE: Marked every 20 degrees F
111 degrees Cl, with subdivisions every 10 degrees F [6 degrees Cl. Includes OFF setting.
fixeda. or 7-18 F [4-10 C].
7,14,or22F[4,8,or12C],
fixeda, or 7-18 F [4-10 C],
more than 9 F [5 C] below bottom of setting range.
Manual reset L6188C
adiustablea
Manual reset
L4189B
I
L6189A
L6189B
I
L6189C
continued on page 3
I
WHEN PURCHASING THIS HONEYWELL PRODUCT, REFER TO THE PRICE SHEETS FOR COMPLETE ORDERING NUMBER, OR SPECIFY-
1. Order number.
2. Temperature setting range.
3. Differential.
IF YOU HAVE ADDlTlONAL QUESTIONS, NEED FURTHER INFORMATION, OR WOULD LIKE TO COMMENT ON OUR PRODUCTS OR SERVICES, PLEASE WRITE OR PHONE:
1. YOUR LOCAL HONEYWELL RESIDENTIAL DIVISION SALES OFFICE (CHECK WHITE PAGES OF PHONE DIRECTORY).
2. RESIDENTIAL DIVISION CUSTOMER SERVICE HONEYWELL INC., 1865 DOUGLAS DRIVE NORTH GOLDEN VALLEY, MINNESOTA 55422-4386 (612)542-7500
IN CANADA-HONEYWELL CONTROLS LIMITED/HONEYWELL LIMITEE, 740 ELLESMERE ROAD, SCARBOROUGH, ONTARIO MlP 2V9. INTERNATIONAL SALES AND SERVICE OFFICES IN ALL PRINCIPAL CITIES OF THE WORLD.
4. Immersion well or capillary compresslon ffttlng, If needed.
5. Optional specifications, if desired.
2
_
0
LIMIT STOP: Limits dial rotation beyond desired high or
low limit temperature. Can be set at 5 F [2.5 C] intervals. Optional, available on models with knob only. Specify when ordering.
AMBIENT TEMPERATURE RANGE: 32 F to 158 F 10 C
to 70 C].
MOUNTING: Must be mounted in an enclosure that
meets local electrical codes. Direct: Unit mounts on immersion well at desired
sensing location.
Remote bulb: Sensing bulb is inserted into immer-
sion well at desired sensing location. Controller
KNOB MODEL
r*~‘s~‘I
case mounts behind remote panel with two self­tapping M4 or No. 8 sheetmetal screws (supplied). Optional mounting bracket allows mounting on front of panel. Specify bracket when ordering.
DIMENSIONS: See Fig. 1. SENSING BULB Liquid-filled copper. See Fig. 1. UNDERWRITERS LABORATORIES INC. COMPONENT
RECOGNIZED: File No. MP466, Guide No. MBPR.
CANADIAN STANDARDS ASSOCIATION LISTED: File
No. LR62051-1.
-
0
-
SCREWDRIVER SLOT MODEL
IMMERSION WELLS
a
i-uIMtNSIUNS
IN In.
[mm In brackets 1 OF AQUASTAT CONTROLLER
AND IMMERSION WELL.
68-0061