AQUASTAT IMMERSION THERMOSTAT L6188A/B/C
■ Installation
T
he L6188 Aquastats can be installed
horizontally or vertically. The temperature
probe should be inserted in
1
/2" dry
w
ell.
■ Ordering Specification
L6188A2002
Controller, external adjustment knob
setting 25 to 95˚C, Diff. 4 to 10˚C.
With well assembly
L6188A2010
As above, but setting 40 to 110˚C
L6188A2036
As above, but setting 70 to 140˚C
L6188A2044
Controller, external adjustment knob
setting 40 to 110˚C, Diff 4 to 10˚C.
With high & low limit stops
L6188A2028
Controller, external adjustment knob
setting 25 to 95˚C, Diff. 4 to 10˚C.
With 1500mm capillary
L6188B2000
TP
*
Controller, setting 25 to 95˚C, Diff.
4˚C. Without wiring terminal cover
L6188B2018
TP
*
Controller, setting 70 to 140˚C,
Diff 4 to 10˚C. With 1500mm capillary
L6188B2026
TP
*
Controller, setting 40 to 110˚C,
Diff. 4 to 10˚C
L6188B2034
TP
*
Controller, setting 25 to 95˚C, Diff.
4˚C. With well assembly
L6188C2008
TP
*
Limit, internal setting 70 to 140˚C,
with manual reset
L6188C2016
TP
*
Limit, internal setting 25 to 95˚C,
with manual reset. With well assembly
45.900.409-003
Single dry well assembly for above.
1
/2"
BSPT thread. Length 105mm
*TP = Tamperproof. Temperature adjustment from dial
under top cover.
■ Specification
Switch Rating : 250VAC, 10A resistive, 2.5A inductive
Switch Type : Single pole, double throw (SPDT)
A
mbient Temperature Range : 0 to 70˚C
IP Rating : IP40
Standards : CE, UL, AGA, CSA
Approvals : 73/23/EEC, DIN3440
■ Dimensions (mm)
■ Wiring