The L6081A is a triple function controller; it is used as a
high limit, low limit, and circulator control. This controller
is designed to replace the controls listed in Table 1.
All require a 124904 Well Adapter to fit L6081A case to well (order separately, see form 68-0040, Wells and Fittings
for Temperature Controllers).
b
Well for L6081A must be added when replacing these models.
L52F
L52G
L52H
L52J
L52K
L52L
a
480
DA-36-153
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Explosion Hazard.
Can cause serious injury, death or property
damage.
Use this product only in systems with pressure
relief valves.
When replacing some of these controls, only 1 or 2 of the
L6081A switching functions may be needed. Refer to Fig.
2 to determine which terminals are used in a given
application.
Best thermal response is obtained with a well
that snugly fits the sensing bulb.
If well does not snugly fit bulb, use the
heat-conductive grease. Fold the plastic bag of
grease lengthwise and twist it gently. Then snip
off end of bag and work the open end all the
way into the well. Slowly pull out bag while
squeezing it firmly to distribute grease evenly in
the well. Insert bulb all the way to the bottom of
the well. Bend the tubing, if necessary, to hold
the bulb against the bottom of the well and to
hold the outer end of the bulb in firmly to the
side of the well (Fig. 1). Wipe excess grease off
outer end of the well.
CONTROLLER
CASE
IMMERSION
WELL CLAMP
IMMERSION
WELL SPUD
ADAPTER
(C)
2
CAPILLARY
TUBE
SETSCREW
IMMERSION
WELL CLAMP SCREW
1
BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).
2
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE TENSION OF THE CAPILLARY TUBE AT POINT (C)
HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D).
BOILER
1
SHORT TUBE
FITS IN CENTRAL
RECESS OF ADAPTER
Fig. 1. Use of adapter and proper position of sensing bulb in immersion well.
6. If the immersion well from the old control does not
fit into the clamp on the back of L6081A case, use
the 124904 Well Adapter (order separately, see
form 68-0040, Wells and Fittings for Temperature
Controllers).
a. Fit sensing element capillary into the adapter
groove (Fig. 1).
b. Fasten the adapter to the case. Make certain
that the clamp is properly positioned on the
adapter and the adapter flange fits snugly into
the opening in the case.
c. Apply heat-conductive grease as instructed
above.
d. Insert the bulb and adapter into the well. The
sensing element bulb must bottom in the well
for best temperature response. (A slight bend
in the tubing will hold the bulb against the well.)
See Fig. 1.
e. Tighten the setscrew. Make certain that the
adapter groove is on the opposite side of the
setscrew (Fig. 1).
4. Loosen the insertion well clamp screw (Fig. 1).
5. If the immersion well from the old control fits into
the clamp on the back of the L6081 case, proceed
as follows. If it does not, go to step 6 below.
a. Apply heat-conductive grease as instructed
above.
b. Insert the sensing element into the well.
c. Fasten the case to the well with the clamp
screw. Make certain that the clamp is properly
positioned on the well and the well flange fits
snugly into the opening in the case. The
sensing element bulb must bottom in the well
for best temperature response. (A slight bend
in the tubing holds the bulb against the well.)
See Fig. 1.
(A)
BACK OF
CONTROLLER
CASE
OLD IMMERSION
WELL ASSEMBLY
IMMERSION
WELL CLAMP
SCREW
HEAT-CONDUCTIVE COMPOUND
ADAPTER
IMMERSION
WELL CLAMP
SENSING
BULB
(B)
M8830
(D)
WIRING
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or property
damage.
Disconnect power supply to prevent electrical
shock or equipment damage.
All wiring must comply with local electrical codes. Make
certain that the electrical requirement of the controlled
equipment does not exceed the rating shown inside the
L6081A cover. Follow the hookup instructions furnished
by the system manufacturer.
IMPORTANT:
L6081A terminals are approved for copper wire
only.
Use Fig. 2 to determine which switches to use when
replacing the existing control. For example, if the existing
control has high limit and circulator control switch
terminals, use terminals R and B on the left side of the
switch for the high limit and the R and W terminals on the
right side of the switch to control the circulator.
95-6701—52
Page 3
L6081A AQUASTAT® CONTROLLER
Fig. 3 shows a typical L6081A hookup.
NOTE: If the 128975 Field Addable Jumper (included)
is used (Fig. 2 and 3), make sure that the two
prongs of the jumper face the center of the
controller.
OPERATION AND SETTING
High Limit
The high limit opens and turns off the burner when the
water temperature reaches the setpoint. The high limit
automatically resets after the water temperature drops
past the setpoint and through the 10°F (6°C) differential.
R4184D PROTECTORELAY™ CONTROL
SS
1K
CAD
CELL
SOLID
STATE
F
SWITCH
SAFETY
SWITCH
F
HEATER
1K1
L2
HIGH LIMIT
3
B
2
R
MAKES R-B, BREAKS R-W ON TEMPERATURE FALL.
1
BREAKS ON TEMPERATURE RISE.
2
3
B TERMINALS ARE TAB TERMINALS.
LOW LIMIT/CIRCULATOR
JUMPER
3
W
B
1
R
M8874A
Fig. 2. Internal wiring of L6081A.
JUNCTION BOX
BLACK
1K2
ORANGE
WHITE
L1
(HOT)
1
BURNER MOTOR
OIL VALVE
IGNITION
CIRCULATOR
24V
THERMOSTAT
2431
T
T
RA89A SWITCHING RELAY
Fig. 3. Typical L6081A hookup.
WARNING
Explosion Hazard.
Can cause severe injury, death or property
damage.
Use this product only in systems with a pressure
relief valve.
Low Limit and Circulator Controls
On a temperature rise, with the adjustable differential at
the minimum setting of 10°F (6°C), the burner circuit
R-B breaks and the circulator control R-W makes at the
B
B
W
1R1
1R
control setpoint. On a temperature drop of 10°F (6°C)
below the setpoint, the R-B circuit makes and the R-W
circuit breaks.
At any differential setting greater than 10°F (6°C), the
R-B make temperature and R-W break temperature
remain the same (control setting minus 10°F [6°C]). The
R-B break and R-W make temperature are the setpoint
temperature plus the difference between the differential
setting and 10°F (6°C).
2
RR
L6081A
POWER SUPPLY. PROVIDE DISCONNECT
1
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
B TERMINALS ARE TAB TERMINALS.
2
JUMPER
ADDED
395-6701—5
M8855
Page 4
L6081A AQUASTAT® CONTROLLER
WELL CLAMP
STRIP
SCREW
GAUGE
LOW LIMIT/
CIRCULATOR
DIFFERENTIAL
ADJUSTMENT
LOW LIMIT
SETPOINT
ADJUSTMENT
HIGH LIMIT
SETPOINT
ADJUSTMENT
JUMPER
SLOT
M8848
Fig. 4. Internal view of L6081A.
At any differential setting greater than 10°F (6°C), the
R-B make temperature and R-W break temperature
remain the same (control setting minus 10°F [6°C]). The
R-B break and R-W make temperature are the setpoint
temperature plus the difference between the differential
setting and 10°F (6°C).
Example: Setpoint of 140°F (60°C); differential set at
25°F (14°C). On a temperature rise, R-B breaks and
R-W makes at 155°F (69°C). On a temperature fall, R-B
makes and R-W breaks at 130°F (55°C).
Setting Stop
The 126580 Setting Stop may be installed on the
adjusting knob to prevent turning the knob beyond a
predetermined point. Fig. 6 shows the stop installed on
the knob of a high limit switch at a setpoint of 180°F
(82°C). To install the setting stop, proceed as follows:
1. Turn the knob to the setting that is to be established as the limit.
2. Place the setting stop over the knob in position so
the arm of the setting stop (after stop is pressed
into place) strikes projection A and prevents
turning the knob beyond the desired limit setting.
IMPORTANT:
Be extremely careful when installing the setting
stop. It cannot be reset once it is in place. If the
stop must be removed, snip it off with cutters;
do not twist off.
3. Press setting stop tightly onto the knob so its inner
teeth engage the knob securely.
4. Turn the knob back and forth several times to
make sure the stop functions properly.
5. When all settings are made, replace the cover.
240°F (116°C)
SWITCH BREAKS ON
HIGH LIMIT
SETTING
LOW LIMIT
AND
CIRCULATOR
SETTING
10°F (6°C)
DIFFERENTIAL
25°F (14°C)
DIFFERENTIAL
10°F (6°C)
DIFFERENTIAL
110°F (43°C)
L6081A,C
Fig. 5. Relationship of setpoints and differential
SETTING STOP
SETTING
STOP ARM
adjustments.
KNOB SET AT 180°F (82°C)
RISE. BURNER TURNS OFF.
CIRCULATOR OPERATES
ON A CALL FOR HEAT.
SWITCH MAKES ON
FALL. BURNER
OPERATES ON A
CALL FOR HEAT.
SWITCH MAKES R-W
AND BREAKS R-B ON
RISE. 25°F (14°C)
DIFFERENTIAL.
SWITCH MAKES R-W
AND BREAKS R-B ON
RISE. 10
DIFFERENTIAL.
SWITCH MAKES R-B AND
BREAKS R-W ON
FALL. BURNER IS ON;
CIRCULATOR IS OFF.
200
220
°F (6°C)
M8875
1
180
160
PROJECTION "A"
1
SCALE MARKINGS IN FAHRENHEIT ONLY.
Fig. 6. Setting stop installed to prevent turning high
limit setting beyond 180°F (82°C).
140
M2844
CHECKOUT
Put system into operation. Carefully observe the
operation of all components for at least one complete
cycle.