L404 and L604 Pressuretrol® Controllers are
line voltage pressure controllers that provide operating control, automatic limit protection, or manual
reset limit protection for pressure systems of up to
300 psi (21.1 kg/cm2 or 2068 kpa).
■ Can be used with steam, air, non-combustible gases,
or fluids non-corrosive to the pressure sensing element.
L404A-D,F; L604A,L,M
SPECIFICATIONS • ORDERING INFORMATION
Specifications
TRADELINE® MODELS
TRADELINE® models are selected and packaged to
provide ease of stocking, ease of handling, and maximum
replacement value. Specifications of TRADELINE
®
controls are the same as those of standard models except as
noted below.
®
TRADELINE
L604A Pressuretrol® Controllers—Available in 2 to 15, 5 to
50, 10 to 150, and 20 to 300 psi (.14 to 1.1 kg/cm
103 kPa], .4 to 3.5 kg/cm
MODELS AVAILABLE:
2
[34 to 345 kPa], .7 to 10.6 kg/
2
[14 to
cm2 [69 to 1034 kPa], and 1.4 to 21.0 kg/cm2 [138 to
2068 kPa]) .
ADDITIONAL FEATURES: TRADELINE® pack with
cross-reference label.
STANDARD MODELS
MODELS: L404A-D,F and L604A,L,M Pressuretrol® Con-
trollers. See Table 1. A 14026 Steam Trap (siphon loop)
is available, except where noted in Table 1. The steam
trap is necessary for boiler installations.
SWITCH(ES): Mercury switch(es) in all models except the
L404F, which has a Micro Switch snap-acting switch.
PRESSURE SENSING ELEMENT: Stainless steel dia-
phragm (brass bellows in 300 psi [21.1 kg/cm
(2068 kPa)] models).
MAXIMUM AMBIENT TEMPERATURE: 150!F (66!C).
MINIMUM AMBIENT TEMPERATURE: Minus 35!F
(minus 37!C); also refer to the note in the Location and
Mounting section.
ADJUSTMENT MEANS: Screws on top of controller case.
Scales are marked in psi and kPa.
ELECTRICAL CONNECTIONS: Internal screw terminals;
hole in side of case for 1/2 in. conduit.
MOUNTING MEANS: Hexagonal fitting on diaphragm has
1/4-18 NPT internal threads for mounting on a pipe or
steam trap (siphon loop). Also can be surface-mounted
using screws through two holes (knockouts) in back of
case.
2
,
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the Tradeline
Catalog or price sheets for complete ordering number, or specify—
1. Order number (TRADELINE® model, if desired).
2. Operating range (see Table 1).
3. Model without steam trap, if desired and available (see Table 1, Note b).
4. Optional specifications, if desired (see Table 1).
5. Replacement parts, if desired.
6. Accessories, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and
Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2150—102
Ordering Information
L404A-D,F; L604A,L,M
SPECIFICATIONS
TABLE 1—MODELS AVAILABLE.
Switching
Action on
Pressure Rise
Model
L404Aspst, breaks
L404B
L404Cspst, breaks
L404Dspst, makes
L404Fspdt snap-acting
L604A2 isolated spst
L604Lspdt circuit
L604Mspdt circuit
a
Scaleplates are marked in both psi and kg/cm
b
Model available with special fixed low differential. Switch rated for 0.5A at 120 Vac.
c
L404A,B and L604A models are available with 1 to 6 psi midscale subtractive differential in 2 to 15 psi models.
d
Brass bellows replaces stainless steel diaphragm. Not suitable for use with ammonia, oxygen, or other corrosive materials.
e
Model available with minimum operating pressure of 1.25 psi (0.09 kg/cm2 or 8.62 kPa) and minimum subtractive differential of 0.5 psi
(0.035 kg/cm
f
Model available with special fixed low differential. Switch rated for 0.5A at 120 Vac.
g
L404C,D and L604L models are designated as Manual Reset 2 controllers; the trip-free reset mechanism does not permit the controller to
to Setpoint
circuit
i
spst, makes
circuit
circuit
circuit
switch,
R-W, breaks R-B
circuits, or 1
j
spdt,
makes R1-
W, breaks R2-B
makes R-W,
breaks R-B
makes R-W,
breaks R-B
2
or 3.45 kPa).
h
makes
2 to 15
10 to 150
20 to 300
2 to 15d,
10 to 150
20 to 300
10 to 150
20 to 300
10 to 150
10 to 150
20 to 300
10 to 150
20 to 300
10 to 150.66 to 10.169 to 1034fixed: 3.5 psi (24.1 kPa)22515.81550
Operating Ranges
psikg/cm
b,c
.14 to 1.0
b
d
c,e,f
e,b
d
d
i
d
c
d
.35 to 3.5
.66 to 10.6
1.4 to 21.0
.14 to 1.1
.35 to 3.5
.66 to 10.6
1.4 to 21.0
.14 to 1.0
.35 to 3.5
.66 to 10.6
1.4 to 21.0
.14 to 1.0
.66 to 10
.14 to 1.0
.35 to 3.5
.66 to 10
1.4 to21.0
.14 to 1.0
.35 to 3.5
.66 to 10
1.4 to21.0
2
5 to 50
5 to 50
2 to 15
5 to 50
2 to 15
2 to 15
5 to 50
2 to 15
5 to 50
2 to 15.14 to 1.0 14 to 103manual resetg
2
a
kPapsikg/cm
14 to 103
34 to 345
69 to 1034
138 to 2068
14 to 103
24 to 345
69 to 1034
138 to 2068
14 to 103
34 to 345
69 to 1034
138 to 2068
14 to 103
69 to 1068
14 to 103
34 to 345
69 to 1034
138 to 2068
14 to 103
34 to 345
69 to 1034
138 to 2068
MidscaleSubtractive Differential
2 to 6
4 to 12
8 to 16
15 to 40
2 to 6
4 to 12
8 to 16
15 to 40
2 to 6
6 to 14
10 to 22
20 to 50
2 to 6
4 to 12
8 to 16
15 to 40
(Adjustable)
2
.14 to .41
.28 to.82
.56 to 1.10
1.04 to 2.76
.14 to .41
.28 to .82
.56 to 1.10
1.04 to 2.76
manual reset
(fixed, subtractive differential)
manual reset
(fixed, subtractive differential)
.14 to .41
.41 to .97
.69 to 15.2
1.4 to 3.5
.14 to .41
.28 to .82
.56 to 1.10
1.04 to 2.76
(fixed, subtractive differential)
103 to 276
103 to 276
g
138 to 345
103 to 276
function as an automatic-reset device when the manual reset lever is held in the reset position. The subtractive differential is fixed at the
minimum value of the adjustable differential of the L404A for each corresponding operating range.
h
L404F only; all other models have mercury switches.
i
Model available with sealed bell crank adjustment.
j
Spst switches operate in unison; spdt action when jumper is installed between R1 and R2.
k
Also recommended for supervision of atomizing medium pressure (air or steam) in an oil burner system.
a
Maximum Surge
Pressure
kPapsi kg/cm2kPa
14 to 4
127 to 83
55 to 110
14 to 41
27 to 83
55 to 110
14 to 41
41 to 97
60 to 152
14 to 41
27 to 83
55 to 110
50
3.5
85
225
500
225
500
225
500
225
225
500
225
500
6.0
15.8
35.2
50
3.5
85
6.0
15.8
35.2
50
3.5
85
6.0
15.8
35.2
50
3 5
15.8
50
3.5
85
6.0
15.8
35.2
25
1.8
85
6.0
15.8
35.2
251.8172
1550
3445
1550
3445
1550
3445
1550
1550
3445
1550
3445
345
586
345
586
345
586
345
345
586
172
586
SWITCH CONTACT RATING (in amperes at 50/60 Hz):
ModelLoad120 Vac240 Vac120 Vdc240 Vdc
L404 AFull Load
Locked Rotor
Noninductive
L604A,L
b
Full Load
Locked Rotor
Noninductive
L604MFull Load1. 00. 51. 00. 5
a
L404F (snap-acting) does not have non-inductive or dc ratings.
b
L604A and L have also been tested (and listed by Underwriters Laboratories Inc.) and breaking (not making) a load with a total
rating of 9.8 A full load, plus 360 VA ignition, plus 250 VA pilot duty at 120 Vac.
8.0
a
48.0
10.0
8.0
48.0
10.0
5.1
30.6
5.0
5.1
30.6
5.0
2.4
24.0
5.0
2.0
20.0
8.0
1.2
12.0
2.0
1.0
10.0
4.0
360-2150—10
L404A-D,F; L604A,L,M
SPECIFICATIONS
DIMENSIONS: See Fig. 1. See Fig. 2 for mounting steam