Honeywell L4006 Installation Manual

95-6120B-05
L4006,L4007 Aquastat Controllers
CAUTION
INSTALLATION INSTRUCTIONS

APPLICATION

These boiler-mounted, immersion type controllers operate in response to temperature changes in hydronic heating systems.
L4006B, L4007Bmake the circuit on a temperature rise. They are used as a circulator controller, delaying circulator operation if boiler water temperature is below the control setting.
L4006E (horizontal well with vertical option) models include trip-tree manual reset switch. Whenever the temperature of the controlled medium reaches the high limit setting, these models are designed to break the control circuit. A reset button at the front of the case must be pressed to re-establish the control circuit.
L4006G includes two switches which break simultaneously on temperature rise to the control setting. This model is used tor high limit and circulator control.
Depending on the model, the Aquastat controllers may include:
• bulb compression titting (L4006C only),
• immersion well tor mounting vertically, or
• immersion well for mounting horizontally.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a haz­ardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.

Mounting

The boiler manufacturer generally provides a tapping for insertion of the Aqua stat controller's sensing element. This tapping is located in a representative point where typical boiler water temperature can be measured. Depending on model, the element is either inserted in an immersion well or through a bulb compression fitting.
It immersion well or bulb compression fitting must be ordered, refer to form 68-0040 “Wells and Fittings for Temperature Controllers,” for part numbers and ordering information.

For Models Using an Immersion Well

The well of the Aquastat controller must always be exposed to average temperature circulating water, and must never be located close to a hot or cold inlet or steam coil. Where the tapping is on the side of the boiler, use an Aquastat controller in which the well can be mounted horizontally. Where the tapping is on top ot the boiler, use a model in which the well can be mounted vertically. Some models include an adapter for vertical or horizontal mounting. See Fig. 2.
IMPORTANT
Controller may be used with or without immer­sion well. Well, if used, must fit sensing bulb snugly tor good thermal response. Bulb should be inserted until it rests against bottom of well. then hold it there while tightening the tubing clamp.
NOTE: Some models have an adjustable tubing length
to 3 in. [716 mm]. In these models, extra tubing inside the case may be pulled out, if needed.
Follow the mounting instructions furnished by the system manufacturer if available; otherwise. proceed as follows.
L4006,L4007 AQUASTAT CONTROLLERS
M38422
VERTICAL MOUNTING
HORIZONTAL MOUNTING

Installing the Immersion Well

On existing installations, shut off the power and remove the old control. If the old immersion well appears suitable, and if the adapter clamp on the Aquastat controller fits the old well spud, this well need not be replaced.
To install new well:
1. If the system is filled, drain system to a point below the boiler tapping.
2. Remove old well from boiler tapping.
3. Install the immersion well. Both 1/2 and 3/4 inch x
14 NPT wells are available. Depending on size of boiler tapping and model ordered, a reducer fitting may be required.
4. Fill the system. Make sure that the well is screwed in tightly enough to prevent leakage. Do NOT use the case as a handle to tighten well after controller is secured to well.
SETPOINT INDICATING DIAL
SPST SWITCH
3
DIFFERENTIAL ADJUSTMENT WHEEL
ADAPTER CLAMP SCREWS
2
1
IMMERSION WELL
3. Fasten the case of the Aquastat controller to the well with the adapter clamp. Make certain that the clamp is properly positioned over the groove of the well spud. Also be sure the flange at the opening of the well fits snugly into the opening of the case. The sensing bulb must bottom in the well for best temperature response.
MODELS WITH FIXED DIFFERENBTIALS DO NOT INCLUDE
1
ADJUSTING WHEEL.
VERTICALLY MOUNTED IMMERSION WELL IS ATTACHED
2
TO THE BOTTOM OF THE CASE.
3
L4006G INCLUDES TWO SPST SWITCHES.
Fig. 1. Internal view showing L4006 (model with
horizontal well).
M38421

For Installation of Sensing Bulb in Immersion Well

1. Loosen screw (at top of case, above scale setting), and remove cover. Loosen 2 screws that secure adapter clamp. See Fig. 1.
2. Insert the sensing element into the immersion well.
95-6120B—05 2
Fig. 2. Mounting bracket placement for vertical or
horizontal mounting.
ADAPTER
L1 (HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
PROTECTORELAY
CONTROL
L4006A OR L4007A HIGH LIMIT CONTROLLER
IGNITION
24 VOLT THERMOSTAT
BURNER MOTOR
OIL VALVE (IF USED)
M1054C
1
2
3
4
T
T
1
2
3
4
T
T
IGNITION
BURNER
L4006B OR L4007B CIRCULATOR AQUASTAT CONTROLLER
CIRCULATOR
L4006A OR L4007A LOW LIMIT AQUASTAT CONTROLLER
L1 (HOT)
L2
L4006A OR L4007A HIGH LIMIT AQUASTAT CONTROLLER
24 VOLT THERMOSTAT
RA832A SWITCHING RELAY
PROTECTORELAY CONTROL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE L4006E FOR MANUAL RESET.
1
2
M2855C
TT
XX
4
2
1
1
2
®
®
®
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE L4006E FOR MANUAL RESET.
1
2
M2856D
2
L1 (HOT)
L2
1
24 VOLT THERMOSTAT
LOW WATER CUTOFF
PRESSURE CONTROL
L4006A OR L4007A LOW LIMIT AQUASTAT CONTROLLER
GAS VALVE
PILOTSTAT CONTROL
®
CLAMP
SPLIT SLEEVE
ADAPTER CLAMP FITS OVER GROOVE
L4006,L4007 AQUASTAT CONTROLLERS
SEALING WASHER
BULB COMPRESSION FITTING
SENSING BULB
Fig. 3. Direct Immersion model with bulb compression
fitting partially removed.

Models Designed for Direct Immersion (without well)

For either horizontal or vertical placement of the mounting bracket, see Fig. 2. Some models, which provide for direct immersion of the sensing element into the boiler, include a bulb compression fitting instead of an immersion well. Install fitting in boiler tapping. Be sure sealing washer is in place as shown in Fig. 3. Make sure that spud of fitting is screwed in tightly enough to prevent leaking. Insert sensing bulb through fitting. Adjust the adapter clamp so that it fits over the groove at the opening of the fitting. Tighten adapter clamp screws so that Aquastat controller is firmly attached to fitting.

WIRING

Disconnect power supply before connecting wiring to avoid electrical shock or equipment damage.
All wiring must comply with local electrical codes and ordinances.
Refer to Fig. 4–9 for typical diagrams of Aquastat controllers used in heating systems.
Fig. 4. Typical hookup for oil-fired gravity system, using
M8774C
Fig. 5. Hookup for oil-fired, summer-winter hydronic
system with domestic hot water using L4006A or B,
L4007 A or B. This Is typical where control for domestic
hot water is added, or where each Aquastat controller is
Fig. 6. Typical hookup for gas-fired system with domestic hot water, using L4006A,E or L4007A.
3 95-6120B—05
L4006A or L4007A.
mounted in a separate location.
Loading...
+ 5 hidden pages