Honeywell JADE Economizer Module with Sensors and Actuators Catalog Page

Honeywell JADE Economizer Module with Sensors and Actuators Catalog Page

Economizer Logic Modules

JADE™ Economizer Module with Sensors and Actuators

Dimensions, Approximate: 4.98 in. high x 6.3 in. wide x 1.34 in. deep (126.4 mm high x 160 mm wide x 34mm deep)

Contact Ratings: 1.5 A Run @ 30 Vac; 3.5 A Inrush @ 30 Vac

Voltage: 24 Vac Frequency: 50 Hz; 60 Hz

Operating Temperature Range: -40 F to -150 F (-40 C to +65 C) Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Color: Gray

The JADE™ Economizer System is an expandable economizer control system, which includes a W7220 Economizer Module (controller) with an LCD and keypad. The W7220 can be configured for 4 different economizer strategies: referential or differential dry bulb, referential or differential enthalpy.

The W7220 Economizer Module can be used as a standalone economizer module wired directly to a commercial set back space thermostat and sensors to provide Outdoor Air dry-bulb economizer control.

The W7220 Economizer Module can be connected to optional Sylk Bus sensors for single or differential enthalpy control. The W7220 Economizer Module provides power and communications on the Sylk Bus for the sensors.

The W7220 Economizer Module automatically detects sensors by polling to determine which sensors are present. If a sensor loses communications after it has been detected, the W7220 Economizer indicates a device fail error on the display or through the AUX 1 OUT terminal programmed to SYS.

Used With: C7232; Honeywell Series 72 actuators; C7250A and C7400S sensors

Approvals

CE: CE Compliance

C-Tick: Approved

Federal Communications Commission: Compliant Underwriters Laboratories, Inc: Flammability Rating UL94V-5V

Other Agencies: Complies with California Title 24

 

 

 

 

Product Number

Input

Output

Use with Sensor

 

 

 

 

W7220A1000/U

Y1, Y2 and occupied input in from thermostat or unitary controller,

Y1 and Y2 out to the mechanical

C7250A1001/U and

 

24 VAC power, Mixed air sensor, OA sensor and optional CO2 and

cooling, AUX 1 out

C7400S1000/U sensors.

 

(programmable), 2-10 or SYLK

 

 

RA sensors. And Programmable AUX 2 In.

communicating to the actuator.

 

 

 

 

 

Jade Y-packs

 

 

 

 

 

 

 

Product Number

Control Type

Includes

Comments

 

 

 

 

Y7220A7215/U

Dry Bulb with black motor

W7220A1000 Logic Module; C7250A1001 OAT sensor;

Output - 2-10 Vdc to actuator

 

 

C7250A1001 MAT sensor; M7215A1008 Black motor

 

 

 

 

 

YL7220A7503/U

Dry Bulb with non-communicating DCA

W7220A1000 Logic Module; C7250A1001 OAT sensor;

Output - 2-10 Vdc to actuator

 

 

C7250A1001 MAT sensor; MS7503A2030 DCA OA

 

 

 

 

 

YL7220AJ3103/U

Dry Bulb with communicating 27 lb-in DCA

W7220A1000 Logic Module; C7250A1001 OAT sensor;

Sylk communicating actuator

 

 

C7250A1001 MAT sensor; MS3103J1030 DCA OA

 

 

 

 

 

YL7220AJ3105/U

Dry Bulb with communicating 44 lb-in DCA

W7220A1000 Logic Module; C7250A1001 OAT sensor;

Sylk communicating actuator

 

 

C7250A1001 MAT sensor; MS3105J3030 DCA OA

 

 

 

 

 

YL7220ACW3103/U

Dry Bulb with communicating 27 lb-in DCA

W7220A1000 Logic Module; C7250A1001 OAT sensor;

Sylk communicating actuator

 

and CO2 wall sensor without a display

C7250A1001 MAT sensor; MS3103J1030 DCA OA;

 

 

 

C7632A1004 CO2 sensor

 

 

 

 

 

Y7220S7215/U

Enthalpy with black motor

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Output - 2-10 Vdc to actuator

 

 

C7250A1001 MAT sensor; M7215A1008 Black motor

 

 

 

 

 

Y7220SCW7215/U

Enthalpy with black motor and CO2 wall

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Output - 2-10 Vdc to actuator

 

sensor with a display

C7250A1001 MAT sensor; M7215A1008 Black motor;

 

 

 

C7232A1016 CO2 sensor

 

 

 

 

 

Y7220SCD7215/U

Enthalpy with black motor and CO2 duct

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Output - 2-10 Vdc to actuator

 

sensor with a display

C7250A1001 MAT sensor; M7215A1008 Black motor;

 

 

 

C7232A1016 CO2 sensor

 

 

 

 

 

YL7220S7503/U

Enthalpy with non-communicating DCA

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Output - 2-10 Vdc to actuator

 

 

C7250A1001 MAT sensor; MS7503A2030 DCA OA

 

 

 

 

 

YL7220SJ3103/U

Enthalpy with communicating 27 lb-in DCA

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Sylk communicating actuator

 

 

C7250A1001 MAT sensor; MS3103J1030 DCA OA

 

 

 

 

 

YL7220SJ3105/U

Enthalpy with communicating 44 lb-in DCA

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Sylk communicating actuator

 

 

C7250A1001 MAT sensor; MS3105J3030 DCA OA

 

 

 

 

 

YL7220SCW3103/U

Enthalpy with communicating 27 lb-in DCA

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Sylk communicating actuator

 

and CO2 wall sensor with a display

C7250A1001 MAT sensor; MS3103J1030 DAC OA ;

 

 

 

C7232A1016 CO2 sensor

 

 

 

 

 

YL7220SCD3103/U

Enthalpy with communicating 27 lb-in DCA

W7220A1000 Logic Module; C7400S1000 OAE sensor;

Sylk communicating actuator

 

and CO2 duct sensor with a display

C7250A1001 MAT sensor; MS3103J1030 DAC OA ;

 

 

 

C7232B1014 CO2 sensor

 

 

 

 

 

404

customer.honeywell.com

70-6910