ID50 Series Panel - Installation, Commissioning & Configuration Manual
Contents
1Introduction1
1.1Manual Purpose1
1.2System Design and Planning1
1.3General2
1.3.1Date-dependent Functions2
1.4CE Marking2
1.5EN54 Functions3
1.6Ancillary Functions4
1.7Related Documents5
1.8Warnings and Cautions5
1.9Tips5
1.10 Glossary of Icons6
2Installation Guide7
2.1How to Use this Section7
2.2Pre-Installation Check List7
2.1.1Some Panel DO’s and DON’T’s7
2.3Transient Protection8
2.4Product Inspection9
2.4.1Checking Your Panel for Damage9
2.4.2What to do if Panel is Damaged
or Suspect10
2.5Dismantling the Panel11
2.5.1Removing the Cover11
2.5.2Removing the Panel Electronics12
2.5.3Back Box Fixing13
2.5.4Semi-Flush Mounting Bezel (Optional)14
2.6Assembling the Panel15
2.7RS485 Communications Link16
2.7.1Fitting the RS485 Interface Module PCB17
2.8RS232 Interface Connections18
Contents
3Cabling19
3.1Cabling Instructions19
3.1.1Cable Terminations20
3.2Cabling Installation Notes21
3.2.1Introduction21
3.2.2Quality of Cable and of Cable Installation 21
3.3EMC Considerations22
i997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
3.3.1Screen Termination22
3.3.2Ferrite Sleeves (Optional)22
3.4MICC Cables22
4Commissioning23
4.1Introduction23
4.2Preliminary Checks23
4.3Internal Checks24
4.3.1Jumper Link Options24
4.4External Wiring Checks25
4.4.1Loop Wiring26
4.4.2RS485 Communications Link27
4.4.3DC Auxiliary Output27
4.4.4Sounder Circuit Outputs28
4.4.5CFG Outputs C and D30
4.4.6-VE Outputs31
Contents
4.4.7Digital / ÜE Inputs31
4.4.8Switch Connections31
4.5Powering the Panel32
4.5.1Start-up Language Selection32
4.5.2Batteries33
4.6Configuration and Handover34
4.7Commissioning Tests35
4.7.1Test LEDs35
4.7.2Test LCD35
4.7.3Test Zones35
4.7.4Test Auto High Test35
4.7.5Test Outputs35
4.7.6Test Buzzer35
4.7.7Test Keyboard35
4.8Sensors and Modules36
4.8.1EN54 Requirements36
4.8.2Loop Wiring Testing36
January 2010
5Configuration37
5.1Introduction37
5.2Navigation and Number Entry37
5.3Level 2 Configuration Options37
5.4Level 3 Configuration Options38
5.5Setup Options39
5.5.1Panel Options39
ii997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
5.5.2Site Details45
5.5.3Device Options46
5.5.4Peripheral Options53
5.5.5Day/Night Settings61
5.6Circuit Options67
5.6.1Signalling Line Circuit (SLC) - Devices 67
5.6.2Signalling Line Circuit (SLC) - Learn77
5.6.3On-Board Circuits79
5.7Control-By-Event Output Rules81
5.7.1Output Type84
5.7.2Filter-by-type85
5.7.3Evacuation86
5.7.4Silence86
5.7.5Interrupt Delay87
5.7.6Class Change87
5.7.7Two Zone88
5.7.8Zones89
5.7.9Device Inputs90
5.7.10 Soak Timer91
5.8Zone Texts91
5.9Access Options92
5.10 System Options93
5.10.1 Crystal Frequency94
5.10.2 Wipe Memory95
5.11 Normal95
Appendix 1 - SpecificationA1-1 to A1-6
Appendix 2 - ID60 Single Loop Panel
DifferencesA2-1 to A2-5
Appendix 3 - Fault Messages & Meanings A3-1 to A3-4
Appendix 4 - EN54-2 Options with
RequirementsA4-1 to A4-4
Appendix 5 - Configuration of a Fault Routing
Output Using a Zone MonitorA5-1
Contents
iii997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
1Introduction
1.1Manual Purpose
The purpose of this manual is to provide the user with all
recommended procedures and full technical details for
the successful installation, commissioning and
programming of a NOTIFIER ID50 Series Panel.
The descriptions and procedures also apply to the
NOTIFIER ID60 panel. Differences between the ID50 and
ID60 panels are given in Appendix 2.
Procedures described in this manual include appropriate
warnings and cautions to guide the user towards adopting
safe and methodical work practices during the installation,
commissioning and programming phases.
The ID50 Series panels support OPAL protocol devices.
These devices support both OPAL and CLIP loop polling
protocols so they can be added to an existing CLIP
protocol loop. However, when OPAL protocol is enabled
on a loop a maximum of 10 CLIP device addresses can
be supported as part of the total of 99 sensors and 99
modules.
Important Note
This manual must be read, and its content clearly
understood, before proceeding with any work relating to
the ID50 Series Panel. Damage to the control panel may
result from NOT following the recommended procedures
described in this manual.
This manual provides all necessary instructions for the
ID50 Series Panel and applies only to fire panels fitted
with compatible software.
CAUTION: In particular, care must be taken when
powering up/down any repeaters.
If there are any areas of doubt, consult your supplier
before continuing with the system installation,
commissioning and programming.
1.2System Design and Planning
It is assumed that the system, of which the ID50 Series
Panel equipment is a part, has been designed by a
competent fire alarm system designer in accordance with
the requirements of EN54 Part 14 and any other local
codes of practice that are applicable.
Introduction
The design drawings should clearly show the positions
of all the ID50 Series Panel control equipment and field
devices.
1
997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
1.3General
The ID50 Series Panel is designed for use with
NOTIFIER’s range of addressable analogue sensors,
control and monitoring modules and addressable call
points. A unique signalling protocol is used, having digital
address and control signals and analogue pulse width
monitoring for the reply data from devices.
The serial communications interface operates under
RS485 protocol and enables communications between
the fire panel and repeaters.
While every effort is made to ensure the accuracy of the
content of this manual, the manufacturer reserves the
right to change the information without notice.
Installation
Only suitably-qualified
engineers must install,
commission and
configure this product.
Only fit the electronics
module after all the other
trades have completed
their tasks!
The ID50 Series Panel is easy to install providing the
recommended procedures described in this manual are
followed. To avoid inadvertent contamination of the PCB
Assembly, the manufacturer recommends it be installed
in the back box only after all other trades have completed
their tasks.
Commissioning
To commission the ID50 Series Panel, follow the
recommended procedures described in this manual. The
manufacturer recommends that during commissioning
and maintenance, ALL RS485 signal cables are
disconnected at the Panel end, BEFORE powering down
the system and are connected AFTER powering up the
system.
Introduction
Configuration
To configure the panel and system, carefully read and
follow the procedures given in this manual. These
procedures describe the menus that are displayed on
the Liquid Crystal Display (LCD) Unit.
Refer to the ID50 Series Operating manual (ref: 997264-000-X) for a description of compatible addressable
Signalling Loop Circuit (SLC) analogue devices.
1.3.1Date-dependent Functions
The calendar end date for this product is 31/12/2063
(two thousand and sixty-three) and it will perform correctly
up to this date.
The calendar function has not been tested beyond
this date.
1.4CE Marking
CE
This panel is CE Marked to show that it conforms to the
requirements of the following European Community
Directives:
January 2010
2997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
The EMC Directive 2004/108/EEC, by the application of
the following EMC Standards:
EN 61000-6-3: Electromagnetic Compatibility (EMC)
Generic emission standard for Residential,
Commercial and Light industrial environments
EN 50130-4: EMC Product family standard: Immunity
requirements for components of fire, intruder and
social alarm systems.
Low Voltage Directive 2006/95/EEC, by the application
of the safety standard:.
EN 60950-1: Safety of information technology
equipment.
The Construction Products Directive 89/106/EEC, by the
application of the following standards:
EN 54-2:1998, (Amd. 1 & 2): Fire detection and fire
alarm systems - Control and indicating equipment.
EN 54-4: 1998 (Amd. 1 & 2): Fire detection and fire
alarm systems - Power supply equipment.
1.5EN54 Functions
This fire control panel is designed to comply with the
requirements of EN 54 Part 2/4. In addition to the basic
requirements of EN 54-2, the panel may be configured to
conform with the following optional functions - the applicable
clauses of EN 54-2 are referenced as follows:
OptionsClause
Indications:
Fault signal from fire protection equipment7.10.4
Recording of the number of entries
into fire alarm condition7.13
Fault signals from points8.3
Controls:
Delay to Outputs7.11.1
Manual or automatic switching of delays to outputs7.11.2
Dependency on more than one alarm signal, Type B7.12.2
Disablement of each address point9.5
Test condition10
Outputs:
Fire alarm device(s)7.8
Fire alarm routing equipment7.9.1
Fire alarm routing equipment with alarm confimation7.9.2
Automatic fire protection equipment: Type A7.10.1
Automatic fire protection equipment: Type C7.10.3
Fault warning routing equipment8.9
Introduction
3
997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
EN
12094-1
!
The following features are provided by the Power Supply
Unit (PSU) of the ID50 Series Panel to comply with EN 54-4.
Features of the ID50EN54-4
Power Supply Unit (PSU)Clause
Derive power supply from main power source5.1
Derive power supply from and monitor a
standby battery source5.2
Charge and monitor the standby
battery source5.3
Detect and signal PSU faults5.4
1.6Ancillary Functions
The following is a list of ancillary functions that are
provided by the ID50 Series panel in addition to the those
required by EN54-2/4. These functions are described in
the section of this manual as referenced (except those
marked thus ‘*’ which are described in 997-264-000-X,
ID50 Series Panel - Operating Manual):
Introduction
AncillaryManual
FunctionsSection Refs.
Site Specific Setup Options5.5
Access Options5.9
Voltage Indications*4.12
Control-by-Event5.7
Output modes5.7.1
Input type pattern5.7.9
Disable/enablement*4.9
Repeater interface2.7
Self-learn configuration - manual5.6.1
Self-learn configuration - auto5.6.2
Module supervision options5.6.1
Module silence options5.7.4
Text editing5.8
Sensor LED blinking on/off5.5.3.4
CAUTION:
12094-1
!
with EN 12094-1.
This product is not compliant
EN
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
January 2010
Bell pulsing ratio5.5.3.5
Display of alarm count*4.11.6
Extend delay timer5.5.5.3
Sounder Volt-free contact options4.4.5
Relay drive output option4.4.6
Extinguishing system features5.5.3.7, 5.5.3.8, 5.5.3.9,
5.7.1, 5.7.2, 5.7.10
4997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
1.7Related Documents
This manual only describes the installation,
commissioning and configuration of the ID50 Series
Panel. All operating functions are covered by the:
ID50 Series Panel Operating Manual (ref:
997-264-000-X)
The Panel can support repeaters via the RS485
communications link. This manual does not provide
details about the repeaters or Compact Mimics; these
are described in:
Note: The ‘000’ part of the manual reference is the UK
country code for the manual.
WARNING: High Voltage!
Take suitable precautions to
avoid electric shock
EN54-2:-8.8
One hardware-
configurable output
must be configured
as a fault relay
The ID50 Panel can also support the VIEWTM sensor. This
manual does not attempt to cover all the VIEWTM sensor
programming and calibration issues as these are
described in some detail in the following, which is available
from NOTIFIER’s Technical Support Department:
VIEW
TM
Application Guide (ref: 997-198).
1.8Warnings and Cautions
Where appropriate, the manual includes advisory
warnings and cautions to remind you to consider safety
at all times, especially when following the procedures
described herein.
You are alerted to any areas where high voltage [i.e. nonSafety Extra-Low Voltage (SELV)] is present, or where
there may be a risk of damage to static-sensitive devices
if the recommended procedures described in this manual
are not followed.
An example of a high voltage warning and an anti-static
caution is provided to the left of this paragraph.
The ID50 Series Panel incorporates some features
which, if used inappropriately, may contravene the
requirements of EN 54. Where there is a possibility of
such an occurrence, a suitable warning is given with brief
details of the EN 54 requirement. A typical EN 54 noncompliance warning is illustrated at left.
Introduction
Magnetise the tip of your
screwdriver to help when
offering small screws to
holes in confined spaces.
1.9Tips
‘Handy tips’ are included, where appropriate, to assist
you in following quick and safe procedures for fire
detection system installation and integration.
Look for the ‘TIP!’ icon and supporting text, typically
illustrated at left.
5
997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
1.10 Glossary of Icons
Throughout this manual, and the other related ID50
Series Panel manuals, a number of icons are used either
as part of the illustrated process descriptions, or in the
main text to help clarify, or simplify, particular
configuration procedures.
The following icons are used to advise or indicate:
a. DO follow the recommended procedure or method.
b. DO NOT use this procedure or method.
c. Inspection of an item or sub-assembly is required at
this point.
d. Following a defined process meets/ does not meet
the required approval/inspection criteria or standards.
Introduction
e. Additional items to be considered.
f. This icon placed next to a pushbutton requires you to
press it while configuring the panel. Where two or
more icons are used, a number may be placed on or
near each hand to indicate the order of selection: 1
coming before 2.
g. Activity process step - flow arrow for single action or
iterative actions.
h. Leader arrow - used with activity processes.
i. Internal buzzer operating/not-operating or silenced.
j. Sounder operating/not-operating or silenced.
k. Power connected and switched ON/disconnected and
switched OFF.
January 2010
l. Manual Call Point (MCP)/Sensor.
6997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
2Installation Guide
2.1How to Use this Section
This Installation Guide provides guidelines on how to
install an ID50 Series Panel quickly and safely.
For each stage in the panel installation and
commissioning procedures a brief description is given of
its purpose, complete with detail drawings, flow diagrams
and/or other graphics to make the instructions easy to
follow. Where required, procedures may be broken down
into one or more related diagrams, the number being
dependent upon the complexity of the defined task.
2.2Pre-installation Check List
Before installing the ID50 Series Panel or fitting sensors,
you must first ensure that the following criteria have been
met. Failure to do this may not only result in damage to
the equipment, but may also cause problems when
commissioning the equipment or adversely affect its
performance.
2.2.1Some Panel DO’s and DON’T’s
Before selecting a location for the ID50 Series Panel,
DO make sure that:
a. The operating ambient temperature is in the
recommended range:
+5oC to +35oC and
b. The relative humidity is between:
5% and 95%
c. The panel is wall mounted in a position which allows
clear visibility of displays and easy access to operating
controls. The height above floor level should be
chosen such that the LCD is just above normal eye
level (approximately 1.5 metres).
Installation Guide
7997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
d. DO NOT locate the panel where it is exposed to high
levels of moisture.
e. DO NOT locate the panel where there are high levels
of vibration or shock.
f. DO NOT site the panel where there would be restricted
access to the internal equipment and cabling/wiring
connections.
Installation Guide
2.3Transient Protection
This equipment contains transient-protection devices.
Although no system is completely immune from lightning
transients and interference, for these devices to function
correctly, and to reduce susceptibility, this equipment
must be earthed correctly.
As with all solid state devices, this system may operate
erratically or can be damaged if subjected to lightninginduced transients.
The use of overhead or outside aerial wiring is not
recommended due to the increased susceptibility to
nearby lightning strikes.
January 2010
8997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
2.4Product Inspection
The ID50 Series Fire Control Panels are relatively simple
to install providing the recommended procedures
described in this Installation Guide are followed.
To avoid damage to the
control panel ensure that
you follow these
instructions.
Follow all installation instructions described in this
manual. These instructions must be understood and
the manufacturer’s recommendations followed to
avoid damage to the control panel and associated
equipment.
2.4.1Checking Your Panel for Damage
It is important to check all supplied equipment for
damage before proceeding with the installation!
1
2
Before attempting to install your ID50 Series Panel, you
should do the following:
1 After removing the panel, from its packing, and before
you proceed with installing it in its chosen location,
check for any damage that may have been caused
during transit.
Note: In the unlikely event that the panel supplied has
been damaged, you MUST NOT install it but return
it to your supplier. The procedure for returning faulty
items is described in Section 2.4.2, What to do if
Your Panel is Damaged or Suspect.
2 If you are satisfied that the panel has NOT been
damaged you can now proceed with the installation
procedure. This manual addresses the recommended
installation methods of the panel. Refer to the relevant
sections that apply to your configuration requirements.
To prevent unnecessary damage to the electronic
components, the back box should be installed without
the electronics fitted. Refer to Sections 2.5.1 to 2.5.3
for details.
Installation Guide
9997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
2.4.2What to do if Panel is Damaged or Suspect
If you have problems regarding the quality of any supplied
order items including the control panel, its ancillaries or
this manual or items are missing, follow the procedure
below:
1
2
3
1 DO NOT continue with the installation but contact your
supplier for advice on what to do next.
Similarly, if the product is found to be faulty during
installation or while in use contact your supplier
immediately.
2 To aid your supplier and the manufacturer, you are
requested to:
a. Quote the manufacturer’s unique batch reference
number which can be found on the packaging or
inside the back box.
b. With reference to PCB’s, quote the part number
and revision level which can be found along one
edge of the PCB - refer to the applicable section
of this manual for specific details.
c. Note all the details relevant to your complaint, date
of receipt, packaging condition, etc. and forward
this to your supplier.
3 Where the product needs to be returned to your
supplier, you are requested to use the original
packaging, or suitable anti-static equivalent,
wherever possible.
Installation Guide
January 2010
10997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
1
2
2.5Dismantling the Panel
For installation purposes, it is recommended that the
cover is removed from the back box and stored in a safe
place until ready for commissioning.
If any other trades, e.g. plasterers or decorators, will be
working in the vicinity after fitting the ID50 Series Panel,
it is strongly recommended that before re-fitting the cover
you remove the panel electronics and store in a safe place
until ready for commissioning. The main components
A
B
C
D
within the ID50 Series Panel are shown below.
E
ID50 Series Panel Assembly
A. Back box
B. PCB Assembly
C. LCD Unit
D. Fascia & Control Keypad
E. Cover
2.5.1Removing the Cover
To remove the ID50 Series Panel cover, it is
recommended that the following procedure is carried out
on a work bench BEFORE siting the panel on the wall:
1 Remove the four M3 x 6mm screws and washers (A)
using a No. 1 Posidriv screwdriver, or the four hex
button-headed screws and clear washers (B) using a
2mm hex key, from the cover, and store safely.
2 Carefully withdraw the cover away from the back box,
until the earth blade terminal (C) within the cover is
accessible.
3 Carefully detach the shrouded earth lead spade
terminal (D) from the earth blade terminal (C) located
in the left-hand inner side wall of the cover.
2
E
Note: All blade connections to earth incorporate a locking
barb. To make a connection push the shrouded
receptacle on to the earth blade (1). To remove
2
3
D
this connection, pull the shroud (2), NOT the earth
wire.
4 Remove and store the cover in a safe place.
Installation Guide
3
C
NOTIFIER
byHoneywell
ID50
ID60
NF50-A
NF30-A
230VAC, 50Hz, 1.0A
‘E’
The power supply ratings label (view ‘E’) is affixed to the
inside face of the fire control panel cover.
Before installing the back box, remove the panel
electronics (see Section 2.5.2, Panel Electronics).
11997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
6
A
1
B
394-191
issue
XXX
TB3
J19
1
2.5.2Removing the Panel Electronics
The ID50 Series Panel electronics comprises the PCB
assembly with mounted LCD unit and the mounted fascia.
These are supplied as one spared item in kit
PN: 020-635-XXX. This assembly is located within the
back box, but should ONLY be removed when installing
the back box or if the PCB requires replacement.
CAUTION: The electronic circuits of the ID50 Series
Panel use CMOS devices which can be damaged by
static discharge. Suitable precautions MUST be taken
when handling circuit boards.
Procedure
When installing the back box or, if it becomes necessary
to remove the PCB assembly for another reason, follow
this recommended procedure:
1 Remove the cover and store in a safe place, see
Section 2.5.1, Removing the Cover. Then make a
back-up of the current system configuration,
remembering to disconnect the link at jumper J19.
Installation Guide
Note: The blade connection to the cover fitted in back
4
boxes incorporates a locking barb. To remove this
connection, pull the shroud (B), NOT the earth wire,
6
from the earth blade terminal (A).
2 Isolate the mains power supply and disconnect the
battery interlink wire if fitted.
3 At the two-part connector TB1 (on the PCB assembly),
4i
ue XXX
using a constant pulling action carefully disconnect
394-191 iss
the mains and battery power supply wiring.
4 Taking suitable anti-static precautions remove the
RS485 Interface PCB, if fitted (refer to Section 2.7.1,
Installing the RS485 Interface Module PCB).
5 At the PCB assembly, note the polarity and
connections of all cables and any jumper configuration
settings. Using a screwdriver, loosen all the connector
securing screws. Carefully secure all external cable
3
tails away from the electronics and from the back box.
6 Using a No. 1 Posidriv screwdriver, remove the eight
(8) M3 x 8mm clinch screws from the PCB assembly.
Gently lift the PCB assembly clear of the supporting
pillars, place it in an anti-static bag and store safely.
Note: If the PCB is to be returned to the manufacturer
note its Serial Number and Revision Level (located
along one edge).
12997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
376.00
301.00
365.00
37.50
188.00
45.00
275.00
45.00
All dimensions are in millimetres. Fixing
hole diameters are 6mm.
DO NOT use the back
box as a guide when
drilling
2.5.3Back Box Fixing
The ID50 Series Panels (PN: 002-455-XXX) are 110mm
deep (external dimensions including fixing dimples). The
back box holds two 12V batteries, up to a maximum rating
of 12Ah each.
The back box must be fixed to the wall with screws at
three fixing locations (see drawing) using the procedure
given below.
The back box must only be installed when the panel
electronics have been removed (see Section 2.5.2,
Removing the Panel Electronics).
Wall Flatness
To prevent distortion, the back box MUST be installed on
the wall as flat as possible, i.e. with a maximum flatness
deviation between any two points of 3mm. Where the
wall is out of tolerance, use appropriate packing pieces
when installing the back box to meet the above
requirements.
Failure to comply with this requirement will result in
the misalignment of the cover’s securing screws,
which may cause difficulties in fitting the cover.
Procedure
When a suitable location has been found for installing
the panel and the panel electronics have been removed,
fix the back box to the wall as follows:
1 Using a suitable-sized drilling bit - for holes to take up
1, 3
to 6mm (No. 12-sized) wood screws - drill a hole at
position A in the wall. Fit a suitable-sized Rawl-plug,
or equivalent.
2
A
B
B
2 Hold the back box in position at hole A (ensure the
panel is level) and mark the position of the remaining
fixing holes (B). Remove the back box and store safely.
3 Drill two holes at positions B in the wall, and fit suitable-
sized Rawl-plugs, or equivalent.
Installation Guide
4 Prepare apertures (20mm knockouts) required for
cable access.
Note: Make sure paint is scraped from the area
surrounding the knockouts, to ensure good
earthing for glands.
4
5
5 Secure the back box to the wall using all three fixing
holes and appropriate-sized screws (up to 6mm
[No. 12-sized] round or pan-head screws - do not use
countersunk screws).
13997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
367
437
383
453
329
375
D
B
C
2
5
2
WALL
RECESS
E (x4)
3
3
A
2.5.4Semi-Flush Mounting Bezel (Optional)
If semi-flush mounting of the ID50 Series Panel is
required, a recess 80mm deep and just large enough to
accommodate the back box must be cut in the wall (see
dimensions below).
All dimensions in millimetres
To fit the bezel:
Before drilling the back
box, make sure that no
equipment is fitted
E (x4)
WALL
RECESS
Installation Guide
1 Before continuing, remove panel electronics and
batteries (if fitted) - see Section 2.5, Dismantling the
Panel.
2 Offer the bezel (A), flat sideways towards you, to the
front of the back box (B) and position it so the bezel
front face (C) is lined up with the rear of the rounded
sides of the back box (D).
3 With the bezel held in position, use the slotted holes
(E) on the bezel as guides and drill four appropriate
sized holes to fit M3 screws centrally in the slots.
Remove any swarf created.
4 Secure the bezel using suitable M3 fixings. Ensure
the fixings are accessible from the outside of the back
box.
Note: The ID50 Series Panel back box must be fixed to
a solid vertical surface, or sub-frame inside the
recess, using its rear fixing holes. Do NOT rely on
the bezel as a means of fixing.
5 Fit back box with attached bezel to the wall recess
and assemble the panel, see Section 2.6.
January 2010
14997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
2.6Assembling the Panel
With the back box secured to the wall and all external
cabling ready for termination, assemble the panel as
follows:
1 Ensure that all power to the panel is isolated and
observe ALL safety and anti-static precautions when
installing the PCB assembly.
2 Install all kits that require the removal of the PCB
assembly.
3 Align the PCB assembly to the supporting pillars and,
using a No. 1 Posidriv screwdriver, screw the eight
(8) M3 x 8mm SEM screws into position.
4 Fit the labels. They may require the application of a
low tack adhesive:
iApply low tack adhesive to hatched area indicated.
ii Slide each label into position.
iii Apply slight pressure to the area along the bottom
edge of the fascia to ensure the labels are secure.
5 Apply the mains power supply and then connect the
batteries. Check the PCB assembly operates correctly
and then isolate all power to the panel.
6 At the PCB assembly:
iNoting the cable polarity, connect all cables and
secure at the correct termination blocks, see
Cables & Wiring.
ii Set all required hardware jumper configurations,
refer to the Section 4 Commissioning.
7 Fit the RS485 Interface Module PCB, if applicable,
refer to Section 2.7.1 Fitting the RS485 Interface
Module PCB.
8 Re-apply the mains power supply and then connect
the batteries.
9 Disconnect the links at the earth fault monitoring
jumper, J19, and configuration lock, J9. Then connect
the RS232 9-way ‘D’ type Data Transfer Lead
(PN 082-173) to the panel at the RS232 connector,
PL5. Using the Support Tool, transmit the latest system
configuration to the panel.
10 Remove the lead and fit the links at J9 and J19, then
fit the cover.
Installation Guide
Note: Connect the earth wire to the inner side wall of the
cover at the tag marked with the earth symbol.
Cables & Wiring
iPower Supply from transformer (TB1),
iiCFG Outputs D and C (TB3),
iii24 V Auxiliary Power Supply (TB4),
ivSounder Outputs B and A (TB4),
vLoop Cable Output (TB5),
viRS485 Communications Cable (TB6),
viiFBF Communications Cable (VdS Only) (TB10),
viiiFBF Power Supply (VdS Only) (TB9),
ixDigital / ÜE Cable (TB8), and
xSwitchable -VE Outputs (TB2),
xiKeyswitch (PL7).
15997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
RS485
B AB A
RS485
B AB A
RS485
B AB A
TB6
TB6
TB6
N
L
ZONEFIRE
ZONEFAULT
DISABLE/TEST
4
2.7RS485 Communications Link
The panel is capable of communicating with a maximum
of sixteen (16) repeaters (active IDR-2A or passive
IDR-2P) or mimic panels (IDR-M) (for further details
concerning the repeaters refer to 997-411, IDR-2A, -2P
& -6A Repeaters User Manual or 997-412, IDR Mimic
Installation and Commissioning Manual). The panel
is connected to the repeaters in a ‘daisy-chain’
arrangement via the RS485 Communications terminal
block, TB6, on the PCB assembly. The panel must be
fitted with the RS485 Interface Module PCB at connector
PL3 on the PCB assembly (see Section 2.7.1, Fittingthe RS485 Interface Module PCB).
The two end stations require a termination resistor to be
fitted as illustrated below.
To connect a panel to an RS485 communications link:
1 Ensure the following:
iAll power to the panel is isolated.
98
7
5
46
[
31
ZONEFIRE
1234567
ZONEFAULT
DISABLE/TEST
FIRE
DISABLEMENT
DELAYSACTIVE
FIREOUTPUT: FAULT/ DISABLED
FIREOUTPUT ACTIVE
PLANTALARM
POWER
TEST
8910
11 1 21314
ID50FIRE CONTROL PANEL
Complieswith EN54-2/4 1997
Periodof Manufacture 1999
FAULT
POWERSUPPLY FAULT
EARTHFAULT
SYSTEMFAULT
SOUNDER:FAULT / DISABLED
PRE-ALARM
FIRECONTROL O/P: FAULT/ DISABLED
15 16
MUTEBUZZER
EXTENDDELAY
ENDDELAY/
EVACUATE
SILENCE/
RESOUND
2
00..9
RESET
Installation Guide
TB6
TB6
ii Access to the panel electronics is possible.
ii The interlink wire is disconnected at the batteries.
2 Fit the RS485 Interface Module PCB as described in
the instructions in Section 2.7.1, Fitting the RS485
Note: If connecting the panel at either end of the RS485
communications link, connect a 150R termination
resistor (supplied separately) as shown below.
4 Using the configuration procedure - refer to
Section 5.5.4.6, Number of Repeaters, configure the
panel and RS485 communications link.
If Fitted As First
Station On RS485
Comms Link
January 2010
Intermediate
Station(s)
If Fitted As Last
Station On RS485
Comms Link
16997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
A
D
E
B
F
C
2.7.1Fitting the RS485 Interface Module PCB
With the back box fitted to the wall, install the RS485
Interface Module PCB as described below (ensure
suitable anti-static precautions are taken):
1 Remove the cover (see Section 2.5.1) to expose the
panel electronics. Disconnect the battery interlink wire
from the batteries and isolate the mains supply.
2 Carefully fit the two plastic PCB support pillars (A) in
to the holes (B) on the right-hand side of the PCB
Assembly (C).
3 Fit the RS485 Interface Module PCB (D).
Fitting to PCB Assembly PN: 394-191-001, 002 or 003
iMake sure the RS485 Interface Module PCB
components are facing the membrane and rest the
PCB in the PCB Support pillar guides.
iiGently ease the RS485 PCB and PCB Support
2
3
3
pillars away from the membrane and carefully slide
the RS485 PCB down the pillars until the 10-way
socket (E) aligns with the connector, PL3 (F) on
the PCB Assembly. Ensure that the components
do NOT foul on the membrane.
394-191 Issue XX
When fitted as first
station on RS485
Communications Link
Apply power BEFORE
When fitted as last
station on RS485
Communications Link
making any RS485
connections!
iii Carefully return the PCB Support pillars to their
normal position and, with a firm and constant
pushing action, connect the PCB.
Fitting to PCB Assembly PN: 394-191 Issue 4, or later,
or PCB Assembly PN: 394-390, or later.
iMake sure the RS485 Interface Module PCB
components are facing away from the membrane
and rest the PCB in the PCB Support pillars’ guides.
ii Carefully slide the PCB along the pillars until the
10-way socket (E) aligns with the connector, PL3
(F) on the PCB Assembly.
iii With a firm and constant pushing action, connect
the RS485 PCB to the PCB Assembly.
4 Connect RS485 Communications wiring at TB6 (see
left), ensuring correct polarity where applicable, and
fit the cover.
If the panel is the first or last station on the RS485
Communications Link, connect a 150R Termination
resistor to the PCB Assembly on the left-hand side
or the right-hand side terminals of TB6 respectively.
5 Apply the mains power supply and connect the battery
interlink wire. Configure the panel, refer to Section 5.
Removing the RS485 Interface Module PCB
If removing the RS485 Interface Module PCB, follow the
procedures above in reverse order.
Ensure a back-up of the current configuration has been
made and all power is isolated.
Installation Guide
17997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
N
L
TB3
J19
ZONEFIRE
ZONEFAULT
DISABLE/TEST
4
2.8RS232 Interface Connections
The panel is fitted with a standard 9-way ‘D’-type RS232
Interface connector, located at the bottom right-hand
corner of the PCB assembly. The RS232 connector is
used for the following purposes:
a. Configuration using the PC Support Tool (refer to
997-405, ID50 Series Panel - Offline Configuration
Manual).
b. Upgrading the Panel Software (refer to 997-415, ID50
Series Panel - Upgrading Instructions).
Before starting any of the above operations ensure
suitable anti-static precautions have been taken.
The RS232 connector has the following pin out:
PinDescription
1Data Carrier Detect (DCD)
2Receive (RX) Data*
3Transmit (TX) Data*
4Data Terminal Ready (DTR)
5GND*
6Data Set Ready (DSR)
7Request To Send (RTS)
8Clear To Send (CTS)
9Not Applicable
Installation Guide
ZONEFIRE
ZONEFAULT
DISABLE/TEST
DISABLEMENT
DELAYSACTIVE
FIREOUTPUT: FAULT/ DISABLED
FIREOUTPUT ACTIVE
PLANTALARM
1234567
FIRE
TEST
POWER
8910
ID50FIRE CONTROL PANEL
Complieswith EN54-2/4 1997
Periodof Manufacture 1999
POWERSUPPLY FAULT
EARTHFAULT
SYSTEMFAULT
SOUNDER:FAULT / DISABLED
PRE-ALARM
FIRECONTROLO/P: FAULT / DISABLED
11 121314
FAULT
15 16
MUTEBUZZER
EXTENDDELAY
ENDDELAY/
EVACUATE
SILENCE/
RESOUND
RESET
98
7
5
46
[
31
2
00..9
Note: Pin numbers marked thus ‘*’ are the only
required connections. Any others fitted will
be ignored.
A Data Transfer Lead (PN: 082-173) is required. Jumpers
must be removed as follows:
1 Remove the cover (refer to Section 2.5.1, Removing
the cover) to access the panel electronics.
2 Remove the Jumper Links J19 (earth fault monitoring)
and J9 (configuration memory lock).
Note: Refer to Section 4.3.1 Jumper Link Options/
Earth Fault Monitoring (J19) when connecting
third-party equipment to the panel.
3 Fit the Data Transfer Lead to the RS232 Interface
connector, PL5.
4 Perform required operation.
5 After satisfactory completion disconnect the lead and
then fit the jumpers.
RS232
January 2010
18997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
3Cabling
3.1Cabling Instructions
WARNING: Risk of electric
shock. Before working on
mains connections, ensure
mains power supply to the
panel is disconnected.
All wiring should comply with current IEE wiring
regulations (BS7671) or the applicable local wiring
regulations. Note also the requirements of EN54-14 for
cabling and interconnection of a fire detection and alarm
system.
For information on wiring inputs and outputs refer to the
appropriate module cable and wiring instructions to
identify terminals. Refer also to Commissioning,Section 4.4 External Wiring Checks for details.
Use the following rules when installing cables:
1 Cables should be brought into the cabinet through the
20mm knockouts provided on the top face of the back
box. Ensure that all openings in the back box are
closed before connecting power to the panel. For
example, if more knockouts than required have been
removed, then block the holes with blanking glands.
This is to prevent access to hazardous voltages.
2 Tails should be of sufficient length to connect to the
appropriate termination points at the commissioning
stage.
3 Cables should be screened and should be terminated
in appropriate glands to meet local wiring codes and
to preserve the integrity of the screen connection. The
cable screen is to be clamped inside the cable gland,
which must be fitted to ensure a 360o bond is formed
with the metal of the back box.
4 The supply to the panel must be provided with a
suitable and readily accessible double-pole mains
disconnect device. The mains supply must be suitably
fused and rated according to the specifications (see
Appendix 1, Specifications).
5 The knockout on the extreme left-hand side should
be used for mains cable entry. DO NOT bring mains
cables in through any other knockout holes and ensure
that the mains wiring is always separated from the
low voltage wiring. Tails of mains cables should be
provided with suitable additional sleeving before
connecting to the mains terminal block.
6 All low voltage cables should have a minimum 300Vac
rating.
General cable installation notes are given in Section 3.2,
Cable Installation Notes.
Earth Blade Connections
Note: All blade connections to earth incorporate a locking
barb. To remove this connection, pull the shroud
(1), NOT the earth wire from the earth blade
terminal (2).
Installation Guide - Cabling
19997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
3.1.1Cable Terminations
This section provides guidance on where to bring cables
into the back box for ease of termination:
a. The mains supply should be brought into the control
panel such that the cable path to the mains termination
block is kept as short as possible.
b. All loop and ancillary cable terminations should be
brought into the panel at suitable positions to ensure
tails are kept as short as possible.
The drawings below show recommended points of entry
so that cabling can meet these requirements.
Knockout/
Termination PointCable Type
aPower supply cable
bOutput D and C cables
cDC Auxiliary Supply
dSounder Output B and A
Installation Guide - Cabling
When preparing mains
wiring for termination,
ensure the earth wire is
longer than the L(ive)
and N(eutral) wires.
Section 4.4.1, Loop Wiring,
Section 4.4.2, RS485 Communications Link,
Section 4.4.3, DC Auxiliary Output,
Section 4.4.4, Sounder Circuits Outputs A and B,
eLoop Wiring
fRS485 Communications
gFBF Connections
(Not Supported)
hDigital / ÜE
(ÜE Not Supported)
iSwitched -VE Outputs
Note: The FBF Signal and Power supply
cables (g), and Digital / ÜE (h) port 2
are only valid when the panel is in VdS
mode.
For specific PCB cable termination details
see Commissioning:
January 2010
Section 4.4.5, CFG Outputs C and D,
Section 4.4.6, -VE Outputs, and
Section 4.4.7, Digital / ÜE Inputs.
20997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
3.2Cabling Installation Notes
3.2.1Introduction
The following notes are intended to assist installers of
analogue addressable control systems. They have been
produced from information derived from the supplier’s
technical resource and from information fed back
concerning existing systems.
3.2.2Quality of Cable and of Cable Installation
It is vitally important that good quality cable is used, and
that correct installation techniques are followed. In general,
the following cable installation requirements must be met:
a. All cable sections must be circular to allow effective
cable clamping using the cable glands.
b. The cable must be screened (sheathed) to provide
protection against Radio Frequency Interference (RFI)
and the screen must be connected to earth at the
control panel.
c. Multiple earthing of the screen should be avoided.
NOTIFIER’s field products use insulated mounting
bases and back boxes to achieve this. We recommend
that this practice be continued if other connections are
made. To achieve this with MICC cable may require
the use of insulated cable glands at one end of the cable.
d. The screen must be continuous throughout the loop.
e. The maximum resistance of the loop should not
exceed 40 ohms. You may check this by joining the
return legs IN+ and IN- together and measuring across
the start legs OUT+ to OUT-. Also the cable
capacitance should be less than 0.5μF. Typically this
will allow a maximum loop length of 2000m of screened
1.5mm2 cable. Cable recommended for use is MICC
with a LSF PVC overcovering, a fire-resilient cable to
BS7629 or PVC/SWA/PVC to BS6387.
Recommended Cables:
ManufacturerProduct NamePart NumberType
AEIMICC2L1.5Enhanced
AEIFiretech298-052Standard
DrakaFiretufPlusFTPLUS2E1.5RDEnhanced
DrakaFiretufFTZ2E1.5Standard
PirelliFP PlusFP Plus 2x1.5 RedEnhanced
PirelliFP200 GoldFP200 Gold 2x1.5 RedStandard
Arrow-7-2-4SNot rated
1
For a definition of ‘Standard’ and ‘Enhanced’ cable requirements and their different
applications, refer to BS 5839-1 Section 26. Enhanced cable is typically required
for spur sounder outputs, while standard cables may be adequate for other firerelated I/O provided there is diverse cable routing. The multi-core cable from Arrow
is suitable for RS232 connections to a printer.
1
Installation Guide - Cabling
f. We recommend that the system should be wired in
2-core cables and each 2-core cable should be specific
to one function.
g. The RS485 communication cable used should be rated
as suitable for up to 200mA in a short circuit condition.
21997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
3.3EMC Considerations
Following the above instructions and by using suitable
cables EMC problems will be avoided. In particularly
difficult EMC environments, or where non-preferred
cabling is used, it is possible to fit additional ferrite
suppressors (sleeves) to cables entering the control
panel.
3.3.1Screen Termination
Use the following method to terminate the cable screens:
Use a metal gland with slots (A) that allow the drain
wire or screen (B) to be clamped between flat washers
(C). Use a steel locking washer (D) between the brass
washers and the internal surface of the back box (E).
This will provide the best EMC termination. Suitable
glands are the CTX range available from CMP UK
Ltd. The part chosen should fit the 20mm knockouts.
3.3.2Ferrite Sleeves (Optional)
Ferrite sleeves are not normally required with the panel.
In difficult EMC environments, or where non-preferred
cables are used, optional ferrite sleeves should be fitted
to both the loop and sounder wiring. the ferrite sleeves
(A) are to be fitted over the conductor(s) of each cable and NOT over the screen of the cable, which should pass
outside of the sleeve. They should be fitted as close as
possible to the entry point of the cable, i.e. as near as
possible to the screen termination (B) to the metal cable
gland (C). The sleeve should be held in place using a
cable tie (D).
The ferrite sleeves are available for purchase from
NOTIFIER’s distributors (PN: 538-143).
Installation Guide - Cabling
3.4MICC Cables
MICC cables must be fitted with metal cable glands (use
Type A2 glands) to ensure good earthing continuity and
correct termination. In particular, the mains cable requires
that the cable gland (A) is fitted with an earth tail kit (B).
The earth tail kit must be connected, using an insulated
wire (C), to the panel safety earth connection (D) at the
mains termination block (E). The bare mains wiring from
the MICC cable must be suitably-insulated (F) and
terminated in accordance with the appropriate local wiring
regulations.
January 2010
22997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
4Commissioning
4.1Introduction
This section describes how to bring the ID50 Series Panel
into an operational state (commissioning) ready for
configuration. To commission this series of panels follow
the steps detailed below. Information on how to configure
the panel is given in Section 5, Configuration.
1 Check that the panel is installed and assembled
correctly, refer to Section 4.2, Preliminary Checks.
Before connecting the mains power to the panel, check
that:
a. All PCBs are correctly fitted.
b. All internal wiring is correctly connected.
c. The loop wiring and external sounder circuits have
NOT, at this stage, been connected to the PCB.
d. Check that there are no more than 10 CLIP device
addresses on a mixed-protocol loop. Be aware that
some modules, e.g. M720, M721 use more than one
loop address - the first device address taken up is
OPAL while the others are CLIP, so an M721 module
uses one OPAL and two CLIP addresses.
e. The appropriate end-of-line devices are connected to
the sounder outputs. For backwards compatibility, the
default is set for 6k8 resistor end-of-line devices.
However, an option is provided to select diode endof-line devices to meet the requirements of EN54-13,
which requires the ability to monitor for partial-open
and partial-short circuit faults. A diode is provided for
each sounder circuit should this option be selected.
Commissioning
f. The 150R termination resistors are connected to the
first and the last panels on the RS485
Communications Link.
23997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
4.3Internal Checks
When all PCBs have been installed and all cabling has
been successfully checked, the following jumper links
allow the implementation of panel software or
configuration updates, as described below.
4.3.1Jumper Link Options
Software Upgrade (J4)
The Software Upgrade Jumper in conjunction with the
Upgrade kit is used to upgrade the panel operating
software. To enable the panel upgrade, fit a link to J4
and connect the appropriate cable. The link J4 must be
removed on completion of the upgrade (see 997-415,ID50 Series Panel - Upgrading Instructions). This
jumper is situated to the right of the Digital/ÜE terminal
block (TB8).
DISABLEDUNLOCKED
J9
J9
LOCKED
J4
J4
ENABLED
Commissioning
Configuration Lock (J9)
The Configuration Lock Jumper is used to lock and unlock
the system configuration. If the link is fitted the system
configuration is locked and changes will NOT be allowed.
If the link is removed system configuration is possible.
The panel can only be configured with the Configuration
Lock (J9) in the unlocked position. The jumper is situated
to the left of the Digital / ÜE terminal block (TB8).
January 2010
24997-263-000-11, Issue 11
ID50 Series Panel - Installation, Commissioning & Configuration Manual
Earth Fault Monitoring (J19)
Earth fault monitoring should be enabled during normal
EN54-2 : 8.2.4c.
Earth Fault Monitoring
is required.
operation; this is the default condition and is indicated by
a fitted jumper link on J19 to the right of the CFG Outputs
C and D terminal block (TB3). To disable the earth fault
monitoring, remove the link.
J19
DO NOT remove link if
there is an existing earth
fault. If link is removed,
ensure it is fitted before
replacing front cover.
J19
ENABLEDDISABLED
The presence of an earth fault is indicated by a yellow
Earth Fault and general Fault LED.
Warning: If an earth fault already exists, DO NOT attempt
to connect additional equipment likely to cause
earth faults as damage may result, i.e. inhibiting
the monitoring will not protect the equipment.
Note: Direct connection of a VDU etc. to the RS232 serial
port D-type plug connector PL5, will result in an
earth fault and potential damage to the connecting
equipment. This fault can be removed by use of
an isolated RS232 link or by (temporarily) disabling
the earth leakage detection. Wait at least one
minute after disabling the earth fault monitoring
circuit before plugging into PL5.
4.4External Wiring Checks
The following sections describe the procedures for
checking and connecting the external wiring:
a. See Section 4.4.1, Loop Wiring*,
b. See Section 4.4.2, RS485 Communications Link,
c. See Section 4.4.3, DC Auxiliary Output,
d. See Section 4.4.4, Sounder Circuit Outputs A and B,
e. See Section 4.4.5, CFG Outputs C and D,
f. See Section 4.4.6, -VE Outputs, and
g. See Section 4.4.7, Digital / ÜE Inputs.
*Notifier has a PC-based Loop Diagnostic Tool (LDT).
This tool is easy to use and its purpose is to reduce
the amount time spent resolving cable and wiring
termination faults. Contact Notifier Technical Support
for details.
Commissioning
25997-263-000-11, Issue 11
January 2010
ID50 Series Panel - Installation, Commissioning & Configuration Manual
The loop wiring MUST
be disconnected from
the panel during this
procedure
OPAL Protocol Devices
Most OPAL devices have internal isolators.
With OPAL-compatible bases the isolator is
connected across terminals +2 and +4 on
the positive loop leg. OPAL devices will
work satisfactorily on B501 bases except
the internal isolator, when fitted, cannot
be operated.
4.4.1Loop Wiring
Typical connections of analogue addressable loop pair
to a loop are shown below.
Checks Before Connection
To check the Loop wiring:
1 For CLIP devices link out any isolators on the Loop
by temporarily shorting terminals 2 and 4 on each
isolator. For OPAL protocol-compatible sensor bases
(B501 AP) remove the device from the base. These
bases have +leg terminals (+2 OUT and +4 IN) that
connect automatically when the sensor is removed.
Check Appendix 1 of this manual or the LBC for OPAL
device types fitted with internal isolators.
2 These tests should then be carried out using a low-
voltage multimeter. Check the continuity of each leg
of the loop and measure the end-to-end resistance.
Verify that the total loop resistance (sum of both legs)
is less than 40 ohms. Typically, this will allow a
maximum loop length of 2,000m of screened 1.5mm
cable.
2
Commissioning
4k7
18k
Monitor used
(see Note a)
LOOP INLOOP OUTLOOP OUTLOOP OUTLOOP INLOOP IN
as input
A
See Note c
Isolator
(see Note b)
M500KAC/
M700KAC
Note: The cable capacitance should be less than 0.5μF.
3 Connect the meter in ‘normal’ polarity (+ve to loop +ve
and -ve to loop -ve). The meter should initially read low
resistance but this should increase as the capacitor in
each of the loop devices charges. If the meter indicates
the presence of a forward-biased diode then it is
probable that one or more of the loop devices is
connected in reversed polarity or the wiring is crossed.
4 If reversed device(s) are indicated in step 3, they may
be located by successive halving of the loop (if the
site layout makes this difficult, the affected section of
the loop can be identified from the panel fault
messages after the system has been configured and
the links in the isolators removed - CLIP devices only).
Notes:
a. A = Normally open switch
- closes under an alarm
28V Supply
Output
Module
See Note c
47k
Supervised
Load
condition.
b. To comply with the
requirements of EN54,
isolators should be fitted
between a maximum of
32 loop devices. For the
ID50 Series Panel, do not
place more than 25 loop
devices between isolators
(20 if FET isolators are
used).
See Note c
B501/B501 AP
+
Loop Start
-
January 2010
c. Refer to device
instruction sheet for
wiring terminations.
Loop Finish
+
26997-263-000-11, Issue 11
Loading...
+ 95 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.