Honeywell IC 40 Technical Information

Actuators IC 40

Technical Information · GB
3 Edit i o n 0 7. 1 8
• For complex applications with programmable functions for flexible adjustment to the process, with statistics and fault history to support service personnel
• Position indicator that can be read externally
• Spacious connection chamber for ease of installation

Contents

Actuators IC 40 .....................................1
Contents ............................................2
1 Application ........................................4
1.1 Examples of application ...........................6
1.1.1 Staged control .........................................6
1.1.2 Staged control with three burner capacity levels .....6
1.1.3 Continuous control by three-point step signal........7
1.1.4 Staged control with pre-purge ........................8
1.1.5 Continuous control with defined ignition position ....9
1.1.6 Hot-air compensation ...............................10
1.1.7 Staged control with online adjustment of the
burner capacity ............................................10
2 Certification ......................................11
3 Function ..........................................12
3.1 Operating modes .................................13
3.2 Standard and analogue operating modes ........13
3.3 Closed, low-fire rate, intermediate and open
position ...............................................13
3.4 Running times ....................................14
3.5 Standard operating modes 1–12 ................15
3.5.1 2-point operation....................................15
3.5.2 2-point operation with flame proving period ....... 16
3.5.3 2-stage operation with one or two digital inputs ....17
3.5.4 2-stage operation with two digital inputs...........19
3.5.5 3-point step operation ..............................20
3.5.6 3-stage operation with one or two digital inputs ....21
3.5.7 2-point operation with switchover of the
adjustment angle for the “open” position .................23
3.5.8 2-point operation with input-dependent
adjustment angle for the “open” position .................25
3.5.9 2-point operation with switchover of the running
times .......................................................26
3.5.10 3-point step operation with running time
fractions ....................................................27
3.5.11 3-stage operation with t wo digital inputs .........29
3.5.12 3-point step operation with low position ..........30
3.6 Analogue operating modes 21–27 ..............31
3.6.1 2-point operation.....................................31
3.6.2 2-point operation with switchover of the
adjustment angle for the “open” position .................33
3.6.3 2-point operation with input-dependent
adjustment angle for the “open” position .................35
3.6.4 2-point operation with switchover of the running
times .......................................................36
3.6.5 2-point operation with characteristic curve
switchover I ................................................38
3.6.6 2-point operation with characteristic curve
switchover II ...............................................40
3.6.7 2-stage operation with t wo digital inputs and
variable adjustment angle for the “open” position ........ 42
3.6.8 Emergency closing function ........................43
3.7 Parameters....................................... 44
3.7.1 Parameter sets.......................................45
3.7.2 Factor y default parameters...........................47
3.8 Inputs ............................................ 48
3.8.1 Digital................................................48
3.8.2 Analogue ............................................48
3.9 Outputs .......................................... 50
3.10 Manual mode....................................51
3.10.1 Direct position preset ...............................51
3.10.2 Simulate inputs .....................................51
3.11 Statistics.........................................52
3.11.1 Counters ...........................................52
3.11.2 Measured values...................................52
3.11.3 Resetting statistics ................................ 52
3.11.4 Resetting a signal ..................................52
3.12 Connection diagram.............................53
3.13 Display ...........................................54
3.13.1 During operation ...................................54
3.13.2 Warnings and faults................................54
3.14 Relay outputs RO 1 and RO 2 function..........56
IC 40 · Edition 07.18 2
= To be continued
4 Replacement possibilities for actuators ..........57
4.1 GT 31 is to be replaced with IC 40 ................57
4.2 M 5/M 6 is to be replaced with IC 40 .............58
5 Selection ........................................ 59
5.1 Selection table ....................................59
5.2 Type code .........................................59
6 Project planning information .................... 60
6.1 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.1.1 Cable selection ......................................60
6.1.2 Digital inputs ........................................60
6.1.3 Feedback signalling ..................................61
6.2 Feedback potentiometer .........................62
6.3 Installation........................................62
6.4 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
7 Accessories ...................................... 64
7.1 Heat deflectors ....................................64
7.2 “Single application” attachment set...............64
7.3 BCSoft.............................................65
7.3.1 Opto-adapter PCO 200 ..............................65
7.4 Cable gland with pressure equalization element .65
8 Technical data ................................... 66
8.1 Running times and torques.......................67
8.2 Dimensions ...................................... 68
8.2.1 IC 40.................................................68
9 Maintenance cycles ............................. 69
10 Glossary ........................................ 70
10.1 Start fuel flow rate ...............................70
10.2 Positions .........................................70
10.3 Adjustment angle for the “open” position .......70
11 Legend ..........................................71
Feedback ...........................................72
Contact.............................................72
IC 40 · Edition 07.18 3
Application

1 Application

Actuator IC 40 is designed for all applications that re­quire precise, controlled rotary movement between 0° and 90°. It can be mounted directly onto the butterfly valves BVG, BVGF, BVA, BVAF, BVH, BVHS or linear flow control VFC in order to control the gas and air flow rates on gas burners.
Actuators and butterfly valves or linear flow control VFC can also be delivered ready assembled as butter­fly valves with actuator IBG, IBGF, IBA, IBAF, IBH, IBHS or linear flow control IFC, see Technical Information Butterfly valves BVG, BVA, BVH..., IB..., and Linear flow controls VFC, IFC.
IBG (IC 40 + BVG) IFC (IC 40 + VFC)
An optional integrated feedback potentiometer offers the option of monitoring the current position of the ac­tuator. This checking function can be used in automa­tion processes.
The IC 40 can be used on continuously-controlled
burners and on stage-controlled burners.
Settings on the actuator IC 40 can be made using a PC with the programming software BCSoft. All the relevant settings for the process are made using the software via an optical interface. Various operating modes, which may be modified, are stored in the unit. In addition, the control type (two-point step signal, three-point step signal or continuous control), running times, adjust­ment angles and intermediate positions can be pro­grammed.
The actuator can also be controlled “by hand” using the
software.
Once set, all the parameters can be saved on the PC and copied from there into other actuators, thus saving time during the commissioning process.
Service technicians can call up statistical data using BCSoft, such as hours of operation, actuating cycles and a fault history. Some values can also be set to zero, for example to record data over a specific period of time.
IC 40 · Edition 07.18 4
Application
Roller hearth kiln in the ceramics industry
Forging furnace
IC 40 · Edition 07.18 5
Application

1.1 Examples of application

1.1.1 Staged control

VAG + VAS 1
Two-
point
step
For processes that require a homogeneous tempera­ture distribution in the furnace. The actuator IC 40 is controlled by a two-point controller and operates in On/Off or High/Low intermittent mode. The actuator closes when the voltage supply is interrupted. The run­ning time can be infinitely adjusted between 5 and 25 seconds.
M
IC 40 + BVA BVA

Staged control with three burner capacity levels

1.1.2
VAG + VAS 1
PLC
M
IC 40 + BVA BVA
For processes that require a homogeneous tempera­ture distribution in the furnace and three burner capac­ity levels. The actuator IC 40 is controlled by a program­mable logic controller and works in High/Medium/Low or High/Medium/Low/Off intermittent mode. This al­lows the ignition stage to be started. The optional pres­sure switch provides fail-safe monitoring of the maxi­mum pilot air volume. The actuator running time can be infinitely adjusted between 5 and 50 (75) seconds.
IC 40 · Edition 07.18 6
Application
VAGVAS
4 DI 1
IC 40
VAG

1.1.3 Continuous control by three-point step signal

The actuator IC 40 is controlled by the three-point step
controller 3PS and moves the butterfly valve BVA to the ignition position. The burner starts.
L1, N, PE
3PS
P
PLC
Once the burner is operating, the operation signalling contact of the burner control unit BCU 460 closes. The BCU issues the controller enable signal to the tempera­ture controller. The butterfly valve opens or closes be­tween the low-fire and high-fire rate positions depend-
5 3
12
V1
4
µC
9
BCU 460
18 19
16 17
ing on the capacity demand of the burner. When the three-point step signal is disconnected, the butterfly valve stops at its current position.
If both inputs on the IC 40 (DI 1 and DI 2) are activated after the burner has been shut down, the butterfly valve closes further than the low-fire rate position (see Op­erating mode 12, 3-point step operation with low posi­tion).
µC
M
DI 2 7
BIO/ BIC
DI 1 DI 2 IC 40 position Valve position
Off Off Idle/Stop Idle On Off Open to high position Open to high-fire rate Off On Close to middle position Close to low-fire rate On On low Valve closes further
BVA
IC 40 · Edition 07.18 7
Application
VAGVAS
VAG
L1, N, PE
PLC
P
22
A
23
5 3
12 26
V1
DI 1 DI 2
4 7
4
µC
9
P
BCU 460..L

1.1.4 Staged control with pre-purge

The central control system starts the pre-purge. Input
DI 2 is activated via the air valve output of the BCU and the butterfly valve BVA is set to the pre-purge position.
In the event of a temperature demand, the burner con­trol unit BCU activates input DI 1 via the valve output
V1 and moves the butterfly valve to the ignition position
(precondition: the IC 40 must have reached the ignition position on the instant of ignition). The burner starts.
To activate the high-fire rate, DI 2 is actuated via the air
18 19
16 17
valve output on terminal 26 of the BCU.
The butterfly valve moves cyclically between the high-
fire rate position and the low-fire rate position (see Operating mode 11, 2-stage operation with two digital inputs).
DI 1/ V1 DI 2/air valve IC 4 position Valve position
BIO/ BIC
Off Off closed Closed On Off low Ignition position/low-fire rate On On middle High-fire rate Off On high Pre-purge
IC 40
M
BVA
IC 40 · Edition 07.18 8
Application
VAGVAS
VAG
P
22
5 3
12 26
V1
DI 1 DI 2
IN
18
4 7
IC 40
mA
µC
M
L1, N, PE
PLC
µC
4
9
P
BCU 460..L
1.1.5
Continuous control with defined ignition position
The central control system starts the pre-purge. Input
DI 2 is activated via the air valve output of the BCU and the butterfly valve BVA is set to the pre-purge position.
In the event of a temperature demand, the burner con­trol unit BCU activates input DI 1 via the valve output
V1 and moves the butterfly valve to the ignition position
(precondition: the IC 40 must have reached the ignition position on the instant of ignition). The burner starts.
The BCU activates DI 2 via the air valve output. This
18 19
16 17
enables the analogue input IN on the actuator IC 40. Depending on the capacity demand of the temperature controller, the butterfly valve BVA moves steplessly to the position between the low-fire rate and the high-fire rate as specified by the analogue input IN (see Operat­ing mode 27, 2-stage operation with two digital inputs and variable adjustment angle for the open position).
BIO/ BIC
DI 1/ V1 DI 2/air valve IC 40 position Valve position
Off Off closed Closed On Off low Ignition position/low-fire rate On On analogue chart 1 In acc. with chart 1 Off On high Pre-purge/high-fire rate
BVA
IC 40 · Edition 07.18 9
Application

1.1.6 Hot-air compensation

VAG +VAS 1
VAS
GIK
WPS
Two
M
IC 40 + BVH
point
For processes in which preheated combustion air at a temperature of up to 450°C must be controlled. In this example, the actuator IC 40 is controlled by a two-point controller to adjust the burner capacity. It runs in High/ Low intermittent mode. The running time can be ad­justed between 5 and 25 seconds.
Staged control with online adjustment of the burner
1.1.7 capacity
VAG +VAS 1
VAS
4–20 mA
PLC
M
IC 40 + BVA BVA
For processes that require a homogeneous tempera­ture distribution and high temperature accuracy in the furnace.
If only a low heat output is required, for example to maintain the temperature in the furnace, the burner can continue to be operated in intermittent mode. The ad­justment angle of the valve is reduced via the analogue input (4–20 mA) of the actuator and the burner capac­ity is therefore lowered. This ensures uniform tempera­ture distribution even with a low heat output.
This function of the actuator IC 40 can also be used in
the ceramics industry to correct the lambda value or for temperature compensation purposes in hot-air applica­tions.
IC 40 · Edition 07.18 10
Certification
2 Certification
Certificates–see Docuthek.
EU certified
Meets the requirements of the
– Low Voltage Directive (2014/35/EU)
– EMC Directive (2014/30/EU)
Standards:
– EN 60730214
Eurasian Customs Union
The product IC 40 meets the technical specifications of
the Eurasian Customs Union.
ANSI/CSA approved
Directive on the restriction of the use of hazardous substances (RoHS) in China
Scan of the Disclosure Table China RoHS2 – see certifi­cates at www.docuthek.com
UL listed
Underwriters Laboratories–UL 607301 “Automatic Electrical Controls for Household and Similar Use”, UL 60730214 “Automatic Electrical Controls for Household and Similar Use; Part 2: Particular Require­ments for Electric Actuators”, File No. E4436.
American National Standards Institute/Canadian Standards Association–ANSI/UL 429 and CSA C22.2. Class number: C322102, Class number: C322182 www.csagroup.org.
IC 40 · Edition 07.18 11
Function

3 Function

The actuator IC 40 moves the butter fly valve towards 0°
or 90°. There are 4 possible positions which the actua­tor can approach in steps. Any intermediate position is possible in continuous three-point step mode. Option­ally, the actuator can also approach any intermediate position via an additional current input.
The slow flashing blue LED indicates that the motor of
actuator IC 40 is moving. The position indicator on the housing indicates the opening angle. Further visualiza­tion and operation are performed on a PC using the BCSoft software.
BCSoft
The sequence of opening and closing is programmed
using the BCSoft software and can be adapted indi­vidually to any application.
All settings for the actuator IC 40 are made using BCSoft. Commissioning and calibration of the “closed” position are performed conveniently using the software.
BCSoft offers the option of moving and adjusting the butterfly valve in Manual mode via the actuator, see page 51 (Manual mode).
A detailed manual is available for the BCSoft PC soft­ware:
ww w.docuthek.com  Home  Elster Thermal Solu- tions Products  03 Valves and butterfly valves  Actuators IC BCSoft (D, GB)
IC 40 · Edition 07.18 12
Function

3.1 Operating modes

The operating mode is responsible for the setting prop-
erties of the IC 40.
The running times and dwell positions of the actuator
are stored in the various operating modes but can be reprogrammed at any time using BCSoft (if mounted on butterfly valve BV..).
The actuator operates in continuous and intermittent
mode with various adjustment angles for the “open” position. The adjustment angles for the “open” position indicate the approached position of the actuator in the case of intermittent operation. They can be changed in BCSoft.
The corresponding operating modes are displayed in
BCSoft as flowcharts by way of example to visualize the opening/closing behaviour of the actuator.

3.2 Standard and analogue operating modes

In the standard operating modes, two digital inputs (DI 1 and DI 2) of the actuator are pre-assigned at the works as universal inputs. If a voltage of 24 V DC or
100–230 V AC is applied to the input, this is recog-
nized as “On” signal (positive logic). It is not necessary to set or readjust the voltage magnitude or voltage type.
In the analogue operating modes, an additional input (IN) is assigned for the actuator. If an actuator IC 40..A with 4–20 mA analogue input is connected (option), further operating modes are available in addition to the
standard operating modes. The actuator can approach corresponding intermediate positions via a current sig­nal to the additional input, see page 49 (Priority and running time in operating modes 1–10).
3.3
Closed, low-fire rate, intermediate and open
position
Depending on the set operating mode, there are 4 posi­tions which the actuator can approach: Closed = 0° = 0%, Low = low-fire rate position, Middle = intermediate position, High = open position.
The positions not used by the operating mode are
barred.
The “closed position” is always the calibrated zero posi-
tion of the device and cannot be readjusted. The other positions can be defined on site.
IC 40 · Edition 07.18 13
Function
Basically, the following parameter limits must be noted.
Ascending sequence of positions: 0% = closed –> low –> middle –> high 100%
The “high position” must not be selected less than 10 %.
If the positions have been changed in the software, BCSoft checks the new values for compliance with the limits and adapts the positions.

3.4 Running times

Up to 6 running times (t1 to t6), each between 0 and max. 25.5 seconds, can be set dependent on the oper­ating mode.
A minimum running time is required for each change in position.
Minimum actuator running time t
t
4.5 s x change in position%
=
min
100 %
Times which are too short are automatically corrected
by the IC 40 to the minimum possible value. If the ac­tuator is to operate as fast as possible, a time of 0 sec­onds can be preset.
In the case of position changes < 16.2%, the maximum running time is reduced from 25.5 s percentage-wise.
min
:
The IC 40 corrects the time to the maximum possible
value.
After they have been entered, the valid parameters are automatically read out and displayed in BCSoft.
We recommend switching to Manual mode when com­missioning in order to establish the right positions and running times for the application, see page 51 (Manual mode).
Outputs
In addition to feedback signals, it is also possible to assign freely adjustable position ranges to the two out­puts, RO 1 and RO 2, see page 50 (Outputs).
Statistics
The statistical data stored in the unit, such as faults
which have occurred, various counter readings and measured values, are displayed and read out in BCSoft, see page 52 (Statistics).
Emergency closing function
A pre-tensioned spiral spring moves the drive shaft with valve disc to the closed position in the event of faults or if the continuous supply voltage is interrupted, within the closing time < 1 s, see page 43 (Emergency clos­ing function).
IC 40 · Edition 07.18 14
Function
t
1
high
low
closed
DI 1
Operating mode 1

3.5 Standard operating modes 1 – 12

General description, see page 13 (Operating modes).

3.5.1 2-point operation

Operating mode 1
In idle state (DI 1 with no signal), the actuator is in “low” position (“low” position may also be 0° = “closed” posi­tion).
If a signal is applied to digital input DI 1, the actua­tor moves to “high” position within running time t When the signal at digital input DI 1 drops, the actuator moves back to “low” position within running time t2.
.
1
t
2
t [s]
t [s]
DI 1 Position
Off low/closed On high
If the signal at digital input DI 1 is deactivated before
“high” position is reached, the actuator moves directly to “low” position within the percentage time of t2.
The actuator operates in high/low (high/closed) inter-
mittent mode.
Possible parameter sets for this operating mode: P68017, P68018 and P68019, see page 45 (Param­eter sets).
IC 40 · Edition 07.18 15
Function
t
1
t
2
t
3
high
middle
low
closed
DI 1
Operating mode 2
3.5.2 2-point operation with flame proving period
Operating mode 2
In idle state (DI 1 with no signal), the actuator is in “low” position (“low” position may also be 0° = “closed” posi­tion).
If digital input DI 1 is activated, the actuator moves to
“middle” position within running time t
After waiting time t
, the actuator automatically moves
2
.
1
further to “high” position within running time t3.
As the voltage at digital input DI 1 drops, the actuator closes to “low” position within running time t
.
4
t4
t [s]
t [s]
DI 1 Position
Off low/closed On high
If the signal at digital input DI 1 is deactivated before
“high” position is reached, the actuator moves directly to “low” position within the percentage time of t4.
The actuator operates in high/middle/low (high/mid-
dle/closed) intermittent mode.
On burners which must ignite during opening of the butterfly valve, waiting time t
is appropriate for flame
2
proving.
Possible parameter set for this operating mode: P 68021, see page 45 (Parameter sets).
IC 40 · Edition 07.18 16
Function
t
1
t
2
high
middle
low
closed
DI 1 DI 2
Operating mode 3

3.5.3 2-stage operation with one or two digital inputs

Operating mode 3
In idle state (DI 1 and DI 2 with no signal), the actua­tor is in “low” position (“low” position may also be 0° =
“closed” position).
Control via two digital inputs
If digital input DI 2 is activated, the actuator moves from “low” position to “middle” position within running time t
.
1
If, in addition, digital input DI 1 is activated, the actuator approaches “high” position within running time t
.
2
When the signal at DI 1 drops, the actuator moves back to “middle” position within running time t
and closes
3
the control element to “low” position within running
t
3
t4
t
1
t
2
t [s]
t [s]
time t
if the signal is also disconnected from DI 2.
4
The actuator operates in high/middle/low (high/mid-
dle/closed) intermittent mode.
DI 1 DI 2 Position
Off Off low/closed On Off high (DI 1 has priority) Off On middle On On high
In this operating mode, digital input DI 1 has priority and its signal always leads to opening of the actuator to
“high” position.
IC 40 · Edition 07.18 17
t [s]
t
t
Function
high
middle
low
closed
DI 1 DI 2
Operating mode 3
This may prove to be practical in order to purge a fur-
nace or kiln via DI 1 (independently of DI 2), for instance. It is then possible to operate with both inputs in high/ middle/low intermittent mode.
Possible parameter sets for this operating mode: P 68015, P68016, see page.45 (Parameter sets).
Control via one digital input
If digital input DI 1 is activated (DI 2 with no signal), the actuator moves to “high” position. The running times t
1
and t2 run directly in succession.
Likewise, the actuator closes within the successive run­ning times t
and t4 if signal DI 1 drops. The “middle”
3
position serves as an interpolation point and can be freely programmed.
1
2
t [s]
Owing to the two successive running times, the open­ing characteristic of the butterfly valve can be changed. For example, the characteristic of the air circuit can be adapted to that of the gas circuit.
Running times up to 51 s (2 x 25.5 s) are possible in this operating mode. If the signal at digital input DI 1 is de­activated before “high” position is reached, the actuator moves directly to “low” position within the percentage times of t
and t4.
3
The actuator operates in high/low (high/closed) inter-
mittent mode.
DI 1 DI 2 Position
Off Off low/closed On Off high
IC 40 · Edition 07.18 18
Function
t
1
t
2
high
middle
low
closed
DI 1 DI 2
Operating mode 4

3.5.4 2-stage operation with two digital inputs

Operating mode 4
The function corresponds to operating mode 3 with dif-
ferent priority of the digital inputs.
Digital input DI 2 has priority over DI 1. This means that a signal at DI 1 has no effect unless a signal is also ap­plied to DI 2.
t
3
t
4
t [s]
t [s]
DI 1 DI 2 Position
Off Off low/closed On Off low/closed (DI 2 has priority) Off On middle On On high
Possible parameter set for this operating mode: P 68022, see page 45 (Parameter sets).
IC 40 · Edition 07.18 19
Function
Operating mode 5
high
low
closed
DI 1 DI 2
t
1
t
2

3.5.5 3-point step operation

Operating mode 5
If only digital input DI 1 is active, the actuator opens. If only digital input DI 2 is active, the actuator closes.
If neither of the digital inputs or both digital inputs are active simultaneously, the actuator stops in its position.
This means that it can be stopped in any position.
The actuator operates in continuous mode and is con-
trolled via a 3-point step signal. The setting function is limited by the “low” and “high” positions (“low” position may also be 0° = “closed” position).
The opening speed is preset via the time t
for the entire
1
“low” to “high” setting travel. Accordingly, the closing
speed is set with t2 for the entire “high” to “low” setting travel.
t [s]
t [s]
Possible parameter sets for this operating mode: P68012, P68013, P68014, see page 45 (Parameter sets).
DI 1 DI 2 Reaction
Off Off Idle/Stop
On Off
Off On Close to “low” position (“closed” position) at min.
On On Idle/Stop
Open to “high” position at max.
This method of control is frequently used on furnaces
and kilns in the sector of ceramics, steel and aluminium.
IC 40 · Edition 07.18 20
Function
t
1
t
2
t
3
high
middle
low
closed
DI 1 DI 2
Operating mode 6

3.5.6 3-stage operation with one or two digital inputs

Operating mode 6
Each of the 4 circuit combinations resulting from DI 1 and DI 2 determines precisely one actuator position:
DI 1 DI 2 Position
Off Off closed On Off low Off On middle On On high
Each signal change results in a new position setpoint for the actuator. If the signals overlap (see t2), the actu­ator moves towards “high”. If the signals do not overlap (see t5), the actuator moves towards “closed”.
t
4
t
5
t
6
t [s]
t [s]
Various modes of operation can be implemented with this operating mode.
Control via one digital input
DI 2 with no signal:
The actuator operates in low/closed intermittent mode
via digital input DI 1.
DI 1 with no signal:
The actuator operates in middle/low intermittent mode
via digital input DI 2.
IC 40 · Edition 07.18 21
Function
t
1
t
2
t
3
high
middle
low
closed
DI 1 DI 2
Operating mode 6
DI 1 with continuous signal, for instance resulting from inversion of the logic, see page 48 (Switching logic):
The actuator operates in high/low (high/closed) inter-
mittent mode via digital input DI 2 with two successive running times up to 51 s (2 x 25.5 s).
DI 1 and DI 2 are connected in parallel:
The actuator operates with one signal in high/closed
intermittent mode with three successive running times up to 76.5 s (3 x 25.5 s).
With three successive running times via interpolation points, it is possible to change the opening character­istic of the butterfly valve. For example, the character­istic of the air circuit can be adapted to that of the gas circuit.
t
4
t
5
t
6
t [s]
t [s]
Control via two digital inputs
If all possible combinations of the two inputs are used, for instance by a PLC control system, it is possible to implement high/middle/low/closed intermittent mode (3 stages plus the “closed” position).
Possible parameter set for this operating mode: P 68001, see page 45 (Parameter sets).
IC 40 · Edition 07.18 22
Loading...
+ 50 hidden pages