• Single-stage, multi-stage, conventional, or heat pump heat/cool HVAC equipment up to 3 stages of heat and 2
stages of cool;
• Dual-fuel systems with up to 2 heat pump stages and 2 fossil fuel stages;
• 2, 3, or 4 zones and is expandable to 32 zones using wired thermostats with the TotalZone® Add-A-Zone™
panel;
• 2, 3, or 4 zones with wireless thermostats when used with the wireless adaptor.
Please refer to TrueZONE Panel Frequently Asked Questions form 50-9694 for operating details, or see
http://customer.honeywell.com
ACCESSORIES
Table 1. Recommended Thermostats.
System Non-
Programmable
Programmable
SingleStage
MultiStage
HeatPump
Wireless
TH5110D, TH3110D,
T87N
TH8110U, TH6110D,
TH4110D
TH5220DTH8320U, TH8321U,
TH6220D, YTH9421C
TH5220D (2H/1C
only)
TH3210D (2H/1C
only)
TH5320U* (Up to
3H/2C)
TH5320RTH6320R
†
TH8320U (Up to 3H/2C)
TH8321U (Up to 3H/2C)
TH6320U* (Up to 3H/2C)
TH6220D (2H/1C only)
TH4210D (2H/1C only)
YTH9421C
Note: All versions of the model numbers listed above
will work with the applications they're listed for.
* This thermostat cannot control two stages of fossil
fuel when in emergency heat mode.
†
For RedLINK™ wireless devices, a THM4000 is
required. For more than 4 zones, see page 11.
Table 2. Recommended Dampers.
TypeActuationRoundRectangular
Residential
ZoneSpring-open/
power-closed
ZonePower-open/
power-closed
ARD
(6 VA)
RRD
(2 VA)
ZD (6 VA)
Bypass BarometricSPRDSPRD
Commercial
ZonePower-open/
power-closed
Bypass Power-open/
power-closed
MARD
(2 VA)
MARD
(2 VA)
with
D2 or D3 with
ML6161A2009 (2 VA)
D2 with
ML6161B2024* (2 VA)
and SPC
SPC
* Or equivalent damper and actuator.
Table 3. Maximum Dampers.*
Ambient Temp.Maximum Damper VA per Zone
100°F (38°C)28.8
160°F ( 71°C)16.8
* Use an SDCR (Slave Damper Control Relay) for addi-
tional dampers to surpass the maximum damper VA
per zone.
Maximum dampers per panel is limited by transformer
size.
Ensure transformer is large enough to power the
panel, thermostats, wireless adapter module, and
dampers.
Table 4. Accessories.
AccessoryDescription
40 VA transformer*AT140A1042
75 VA transformerAT175A1008
Discharge Air Temperature
C7735A1000
Sensor (DATS)*
TAZ-4TotalZone® Add-A-ZoneTM
Control Panel
SDCR**Slave Damper Control
Relay
Portable Comfort
REM5000R1001
Control***
Wireless Adapter***THM4000R1000
Wired Outdoor Air
Temperature Sensor
‡
Wireless Outdoor Air
Temperature Sensor***
RedLINK Internet
C7089U1006 (hard wired)
C7089R1013 (wireless)
‡
THM6000R1002**
Gateway***
* Included in HZ432K kit.
** Use an SDCR (Slave Damper Control Relay) to add
additional dampers to a zone to surpass the maximum Damper VA rating per Zone.
*** For RedLINK™ wireless devices, a THM4000 is
required.
‡
A wired or wireless outdoor sensor is required for
Dual Fuel applications.
1 69-2198—03
Page 4
Installation Guide
L
MOUNTING
1
2
Mount the HZ432 TrueZONE panel near the HVAC
equipment; locate it on a wall, stud, roof truss, or cold-
SPRD BYPASS
DAMPER
ZD SERIES
ZONE DAMPERS
air return.
NOTE: The HZ432 TrueZONE panel can be mounted in
any orientation; level it for appearance only.
DATS
(ALTERNATE
LOCATION)
TrueZONE PANEL
MOUNTED ON
RETURN DUCT
DATS
(AT LEAST 3 FT
FROM PLENUM)
FURNACE OR
AIR CONDITIONER
SUPPLY
DUCT
TrueZONE PANEL
MOUNTED ON WAL
M24738
Fig. 2
Separate the zone panel cover from the base, and use the base as a template to drill mounting holes.
Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).
Fig. 3
Use two screws for attaching to a stud or roof truss, or
four screws for duct or drywall/plaster installations.
M24807
69-2198—03 2
Page 5
HZ432 TrueZONE
WIRING
CAUTION: Voltage Hazard.
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
Wire entire panel before applying transformer power.
Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional systems, see page 5. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9.
Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring diagrams to wire
the zone panel to the thermostats and dampers.
Install thermostats using instructions provided with thermostats.
M1
M4
M6
ZONE 4
DAMPER
R
C
W1/E
W2
W3
THERMOSTAT
Y1
Y2
G
O/B
L
M24808
3
If using wired thermostats, connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and
push wire into terminal. To release wire, press the button on top of
the terminal.
W2
Rc
R
C
W
Y
Y2
G
M24743
Fig. 5
4
The HZ432 offers many innovations for wire management and organization: wires can be run
behind the panel, through wire channels on its sides, and must be attached to a wiring anchor
with a cable tie.
Install dampers using instructions provided with dampers.
Connect dampers to zone panel.
NOTE: Multiple dampers can be wired in parallel.
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
M1 COMMON
DAMPER
ZONE 3
DAMPER
ZONE 1
M1
M4
M6
R
M4 OPEN
M6 CLOSED
RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED
Fig. 4
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
DAMPER
ZONE 2
M24920
Fig. 6
3 69-2198—03
Page 6
Installation Guide
L1
WIRING
5
6
7
Connect DATS as shown.
Connect outdoor air temperature sensor as shown.
Required for dual fuel systems; optional for other
multistage systems. If using the C7089R1013 wireless
outdoor sensor and THM4000R wireless adapter on
2- to 4-zone systems, see page 11.
Connect equipment as shown here
or on pages 5–9.
HVAC
24 VOLT TRANS.
C
FAN RELAY
COMPRESSOR
RELAY
W2
Y2
Y
DATS
DATS
SENSOR
C7735A1000
M24804
Fig. 7
OT
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
OT
SENSORS
M28207
Fig. 8
For oil heat with a separate transformer for cooling,
remove this jumper.
For other systems, leave jumper in place and wire to
R
W
G
W1/E
EQUIPMENT
DS/B
W2
W3
RH
RC
HVAC R terminal with 18 gauge solid copper wire.
The DS/BK terminal is used with a variable-speed fan.
Y1
Y2
G
O
B
K
If the HVAC equipment has DS, BK, ODD, or DHUM terminals, wire that terminal to the DS/BK terminal. When
greater than 25% of zones are calling for cooling, this
terminal will be energized and the fan will operate at normal speed. When 1 zone or fewer than 25% of zones are
M24809
calling for cooling, the terminal will be de-energized and
the fan will run at a reduced rate, which will reduce the
amount of air that needs to be bypassed. This reduces
Fig. 9
blower speed on most variable speed blowers. Refer to
HVAC equipment manufacturer instructions.
8
When a wireless thermostat, Portable Comfort Control, wireless outdoor air temperature sensor, or other RedLINK™ wireless
device is used on systems up to four zones, wire the THM4000
Wireless Adapter Module to the ABCD terminals on the zone panel.
WIRELESS SETUP
CONNECTED
THM4000R
POWER
CONNECT
A
B
C
D
WIRELESS
M28193
For systems with more than 4 zones, see page 11.
WIRELESS
ADAPTER
Fig. 10
CAUTION : Do not wire the A-B-C-D terminals of the THM5320R Wireless Equipment Interface Module
to the A-B-C-D terminals on the HZ322 zone control panel. Doing so will damage the components.
(HOT)
9
Connect a dedicated transformer as shown.
R
L2
C
DEDICATED
TRANSFORMER
POWER
R
C
M24806
Fig. 11
69-2198—03 4
Page 7
HZ432 TrueZONE
CONVENTIONAL
The following diagram is an overall view of wiring for a conventional system as depicted in steps 3–9.
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
HVAC
24 VOLT TRANS.
C
R
W
W2
FAN RELAY
G
Y2
Y
COMPRESSOR
RELAY
THM4000R
POWER
WIRELESS SETUP
CONNECTED
CONNECT
L1
(HOT)
L2
TRANSFORMER
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
Rc
R
C
W
W2
Y
Y2
G
R
C
DEDICATED
M1
M4
M6
ZONE 4
DAMPER
R
C
W1/E
W2
W3
THERMOSTATEQUIPMENTPOWERSENSORSACCESSORIES
Y1
Y2
G
O/B
RH
RC
W1/E
W2
W3
Y1
Y2
DS/BK
AZ1
AZ2
OT
OT
DATS
DATS
WIRELESS
M1 COMMON
M4 OPEN
DAMPER
M1
M4
M6
THERMOSTATZONE 3
R
C
W1/E
W2
W3
Y1
Y2
G
L
1
G
O
B
R
C
A
B
C
D
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT
EMERGENCY
2
HZ432
HEAT
HOME
CONFIG
CHECK OUT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
DAMPER
ZONE 2
THERMOSTATZONE 1
DAMPER
THERMOSTAT
M6 CLOSED
Rc
R
C
W
W2
Y
Y2
G
Rc
R
C
W
W2
Y
Y2
G
Rc
R
C
W
W2
Y
Y2
G
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ADJUST SETTING
WIRELESS
ADAPTER
1
FOR OIL HEAT WITH A SEPARAT E TRANSFORMER FOR COOLING, REMOVE JUMPER.
ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R
2
WIRELESS EIM TO THESE TERMINALS.
M28196A
Fig. 12. Zone panel wiring—conventional.
5 69-2198—03
Page 8
Installation Guide
HEAT PUMP
Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat.
NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by
heat pump thermostats or by pressing the Emergency Heat button on the zone panel. The diagram below shows a
heat pump thermostat used with a heat pump system.
ARD OR ZD DAMPER
SPRING-OPEN
AIR
HANDLER
24 VOLT TRANS.
C
EM. HEAT
AUX. HEAT
W2
FAN RELAY
HEAT PUMP
C
REVERSING
VALV E
THM4000R
POWER
WIRELESS SETUP
CONNECTED
CONNECT
POWER-CLOSED
Rc
R
C
E
AUX
1
Y
G
O/B
2
L
R
E
G
Y
R
Y
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
L1
(HOT)
R
L2
C
DEDICATED
TRANSFORMER
M1
M4
M6
ZONE 4
DAMPER
R
C
W1/E
W2
W3
THERMOSTATEQUIPMENTPOWERSENSORS
Y1
Y2
G
O/B
RH
RC
W1/E
W2
W3
Y1
Y2
DS/BK
AZ1
AZ2
ACCESSORIES
OT
OT
DATS
DATS
A
B
C
D
WIRELESS
M1 COMMON
M4 OPEN
DAMPER
M1
M4
M6
THERMOSTATZONE 3
R
C
W1/E
W2
W3
Y1
Y2
G
L
3
G
O
B
R
C
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT
EMERGENCY
HZ432
ZONE 1
ZONE 2
ZONE 3
ZONE 4
HEAT
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
DAMPER
ZONE 2
THERMOSTATZONE 1
DAMPER
THERMOSTAT
4
HOME
CONFIG
CHECK OUT
M6 CLOSED
Rc
R
C
E
AUX
Y
G
O/B
L
Rc
R
C
E
AUX
Y
G
O/B
L
Rc
R
C
E
AUX
Y
G
O/B
L
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
1
2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
2
WIRELESS
ADAPTER
1
ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.
2
FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, AT TACH O FOR
COOL CHANGEOVER VALVES OR ATTACH B FOR HEAT CHANGEOVER VALVES.
IF EQUIPMENT DOES NOT HAVE SEPARATE E AND AUXILIARY TERMINALS, JUMPER
3
E TO W2 ON PANEL AND WIRE TO E.
ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R
4
WIRELESS EIM TO THESE TERMINALS.
ADJUST SETTING
Fig. 13. Zone panel wiring—heat pump, 2-heat/1-cool with electric auxiliary heat.
69-2198—03 6
M24794B
Page 9
Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat.
ARD OR ZD DAMPER
SPRING-OPEN
AIR
HANDLER
24 VOLT TRANS.
C
R
EM. HEAT
E
AUX. HEAT
W3
FAN RELAY
G
Y2
Y
HEAT PUMP
C
R
Y2
REVERSING
VALV E
THM4000R
POWER
WIRELESS SETUP
CONNECTED
CONNECT
POWER-CLOSED
Rc
R
C
E
AUX
1
Y
Y2
G
O/B
2
L
Y
TRANSFORMER
C7089U1006
OUTDOOR
TEMPERATURE
C7735A1000
L1
(HOT)
L2
DEDICATED
SENSOR
DATS
M1
M4
M6
ZONE 4
DAMPER
R
C
W1/E
W2
W3
THERMOSTATEQUIPMENTPOWERSENSORSACCESSORIES
Y1
Y2
G
O/B
L
RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
R
C
DS/BK
DATS
DATS
WIRELESS
AZ1
AZ2
R
C
OT
OT
A
B
C
D
3
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT
4
HZ432
EMERGENCY
HEAT
HOME
CONFIG
CHECK OUT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
DAMPER
THERMOSTATZONE 3
DAMPER
ZONE 2
THERMOSTATZONE 1
DAMPER
THERMOSTAT
M1 COMMON
M4 OPEN
M6 CLOSED
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
HZ432 TrueZONE
HEAT PUMP
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
1
2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
2
WIRELESS
ADAPTER
1
ALTERNATIVELY LABELED W3 ON SOME THERMOSTATS.
FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, AT TACH O FOR
2
COOL CHANGEOVER VALVES OR ATTACH B FOR HEAT CHANGEOVER VALVES.
IF EQUIPMENT DOES NOT HAVE SEPARATE E AND AUXILIARY TERMINALS, JUMPER
3
E TO W3 ON PANEL AND WIRE TO E.
ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R
4
WIRELESS EIM TO THESE TERMINALS.
ADJUST SETTING
M24795B
Fig. 14. Zone panel wiring—heat pump, 3-heat/2-cool with electric stage 3 heat.
7 69-2198—03
Page 10
Installation Guide
DUAL FUEL
Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump.
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
FURNACE
24 VOLT TRANS.
C
R
W
FAN RELAY
G
Y
HEAT PUMP
C
R
Y
REVERSING
VALV E
THM4000R
POWER
WIRELESS SETUP
CONNECTED
CONNECT
WIRELESS
ADAPTER
1
TRANSFORMER
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
L1
(HOT)
L2
DEDICATED
M1 COMMON
M4 OPEN
M1
M4
M6
ZONE 4
DAMPER
R
C
W1/E
W2
W3
THERMOSTATEQUIPMENTPOWERSENSORSACCESSORIES
Y1
Y2
G
O/B
L
RH
RC
W1/E
W2
W3
Y1
Y2
G
O
R
C
DS/BK
DATS
DATS
WIRELESS
AZ1
AZ2
B
R
C
OT
OT
A
B
C
D
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
EM HEAT
2
FAN
HZ432
EMERGENCY
HEAT
HOME
CONFIG
CHECK OUT
ADJUST SETTING
ZONE 1
ZONE 2
ZONE 3
ZONE 4
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
DAMPER
THERMOSTATZONE 3
DAMPER
ZONE 2
THERMOSTATZONE 1
DAMPER
THERMOSTAT
M6 CLOSED
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
1
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
ARD OR ZD DAMPER
1
SPRING-OPEN
POWER-CLOSED
FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, AT TACH O FOR
1
COOL CHANGEOVER VALVES OR ATTACH B FOR HEAT CHANGEOVER VALVES.
ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R
2
WIRELESS EIM TO THESE TERMINALS.
Fig. 15. Zone panel wiring—dual fuel: single-stage furnace and single-stage heat pump.
69-2198—03 8
M24796B
Page 11
HZ432 TrueZONE
DUAL FUEL
Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump.
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
FURNACE
24 VOLT TRANS.
C
R
HEAT 1
W
HEAT 2
W2
FAN RELAY
G
Y2
Y
HEAT PUMP
C
Y2
REVERSING
VALV E
THM4000R
POWER
WIRELESS SETUP
CONNECTED
CONNECT
R
Y
Rc
R
C
E
AUX
1
Y
Y2
G
O/B
L
L1
(HOT)
L2
DEDICATED
TRANSFORMER
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
M1 COMMON
M4 OPEN
M1
M4
M6
ZONE 4
DAMPER
R
C
W1/E
W2
W3
THERMOSTATEQUIPMENTPOWERSENSORSACCESSORIES
Y1
Y2
G
O/B
L
RH
RC
W1/E
W2
W3
Y1
Y2
G
DS/BK
O
B
HZ432
R
R
C
C
AZ1
AZ2
OT
OT
DATS
DATS
A
B
C
D
WIRELESS
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT
EMERGENCY
2
ADJUST SETTING
HEAT
HOME
CONFIG
CHECK OUT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
DAMPER
THERMOSTATZONE 3
DAMPER
ZONE 2
THERMOSTATZONE 1
DAMPER
THERMOSTAT
M6 CLOSED
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
Rc
R
C
E
AUX
Y
Y2
G
O/B
L
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
1
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
1
WIRELESS
ADAPTER
1
ALTERNATIVELY LABELED W3 ON SOME THERMOSTATS.
ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY. NEVER WIRE A THM5320R
2
WIRELESS EIM TO THESE TERMINALS.
M24793A
Fig. 16. Zone panel wiring—dual fuel: two-stage furnace and two-stage heat pump.
9 69-2198—03
Page 12
Installation Guide
CONFIGURATION
To enter Configuration:
1
2
3
Press the Mode button (the Config LED will
light up).
Use the Back and Next buttons to navigate
through the configuration settings. Scroll
HOMEWIRELESS
CONFIG
CHECK OUT
BACKNEXT
ADJUST SETTING
MODE
WIRELESS
BACKNEXT
HOME
CONFIG
CHECK OUT
ADJUST SETTING
MODE
through the selection choices by using the
"Adjust Setting" Left and Right arrow buttons. Pressing Next enters the selected
M24799
Fig. 17
M24810
option for that menu item and advances to
the next menu.
The flow chart below illustrates basic zone panel configuration. For additional configuration, see
Advanced Configuration on page 12. The label on the inside cover of the HZ432 Zone Panel also contains configuration information.
Fig. 18
CONVENTIONAL
COOL STAGES
0 [1] 2
SYSTEM TYPE
[CONV] HEATPUMP
HEATPUMP
DUAL FUEL OPER
[NO] YES
COMPRESSOR STAGES
[1] 2
1
OPTIONS: 1, 2, 3, 4,
4+ADDZONE
ASKS THIS FOR EVERY ZONE.
“RF” MEANS
“WIRELESS
THERMOSTAT”
C7089U1006 WIRED OUTDOOR SENSOR, OR C7089R1013 WIRELESS OUTDOOR SENSOR AND THM4000R1000 WIRELESS
1
ADAPTOR REQUIRED IF DUAL FUEL OPERATION IS SET TO YES.
SET TO “YES” IF WIRELESS (RADIO FREQUENCY) THERMOSTATS AND THM4000R ADAPTOR ARE USED. SET TO “NO” IF THE THM5320R
2
IS USED AS DESCRIBED ON PAGE 11 .
CANNOT USE TAZ-4 ADD-A-ZONE WITH THE HZ432 IF RF ENABLED IS SET TO “YES”. SYSTEM IS LIMITED TO 4 ZONES WHEN THM4000
3
WIRELESS ADAPTER IS USED.
4
SHOWN IF COMPRESSR STAGES, HEAT STAGES, OR DFUEL HT STAGES IS SET TO 2, OR AUX HT ENABLED IS SET TO “YES”
SHOWN ON NON DUAL FUEL HEAT-PUMPS IF COMPRESSR STAGES IS SET TO 2 AND AUX HT ENABLED IS SET TO “YES”,
5
OR ON CONVENTIONAL APPLICATIONS IF HEAT STAGES IS SET TO 3.
HEAT STAGES
0 [1] 2 3
“RF ENABLED” MEANS
“WIRELESS ENABLED.”
ZONES INSTALLED
3
ZONE 1 TSTAT TYPE
[4]
[RF] WIRED
DUAL FUEL OPERATION = NO
RF ENABLED
[YES] NO
YES
WIRED
RF
STAGE 2 CONTROL
4
STAGE 3 CONTROL
5
ADVANCED CONFIG
SAVE CHANGES
[OFF]
[OFF]
[NO] YES
[NO] YES
DUAL FUEL OPERATION = YES
AUX HT ENABLED
[YES] NO
2
NO
ZONES INSTALLED
ZONE 1 TSTAT TYPE
[4]
[HTPUMP-O]
OPTIONS: TSTAT, TIMER, % ZONES, OFF
OPTIONS: TSTAT, TIMER, % ZONES, OFF
“YES” PERMITS VIEWING AND CHANGING
THE ADVANCED CONFIGURATION OPTIONS.
SHOWN IF CHANGES WERE MADE.
SELECT “YES” THEN PRESS “NEXT” TO SAVE.
DFUEL HT STAGES
[1] 2
OPTIONS: 1, 2, 3, 4, 4+ADDZONE
ASKS THIS FOR EVERY WIRED ZONE.
OPTIONS: HTPUMP-O FOR HEAT PUMP
THERMOSTAT USING O FOR CHANGEOVER,
HTPUMP-B FOR HEAT PUMP THERMOSTAT S
USING B FOR CHANGEOVER AND
CONVENTIONAL FOR CONVENTIONAL,
NON-HEAT PUMP THERMOSTAT S
M24812B
69-2198—03 10
Page 13
HZ432 TrueZONE
CONNECT WIRELESS DEVICES
4
5
If connecting wireless devices, press the Mode button until the Wireless LED lights up. The TrueZONE
must be configured for wireless devices to select
Wireless mode.
Press Next to add devices.
While the display alternates the Press Connect and
Exit screens, push the Connect button(s) on the wireless device(s).
-ORFollow the instructions that came with the wireless
device(s).
Press Next to exit.
If using more than 4 zones, use the TAZ-4 Add-A-ZoneTM
Control Panel. Follow instructions with the TAZ-4 for
installation (form 69-1366).
Note: If using wireless thermostats, a maximum of 4
zones may be configured when using the THM4000 wireless adpater.
For applications requiring more than 4 zones using wireless thermostats, wire a THM5320R Wireless Equipment
Interface Module to the thermostat terminals of each
zone on the zone panel, and configure the panel for wired
thermostats. Note that no THM4000R Wireless Adapter is
used in this more than 4 zone setup.
WIRELESS
BACKNEXT
HOME
CONFIG
CHECK OUT
ADJUST SETTING
MODE
Fig. 19
M28194
CAUTION
Do not wire the A-B-C-D terminals of the THM5320R to
the A-B-C-D terminals of the HZ432 zone control panel.
Doing so will damage the components.
11 69-2198—03
Page 14
Installation Guide
ADVANCED CONFIGURATION
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page
10 for instructions on using these buttons. Options/information displayed will vary by system type, control type,
number of zones, and other settings.
Table 5. Advanced Configuration.
Menu NameMenu Title (LCD
Heat FanHEAT FAN
Stage 2 TimerSTAGE 2 TIMER
Stage 3 TimerSTAGE 3 TIMER
Purge TimerPURGE TIME
Purge FanFAN IN PURGE
Purge DampersPURGE DAMPERS
Auto Changeover Delay CHANGEOVER
DATS EnabledDISCHARGE
DATS High LimitDAT HIGH LIMIT [110 F] > – < [180 F]
DATS Low LimitDAT LOW LIMIT [30 F] > – < [60 F]
Multistage DATS Inhibit DAT MSTG INHIBIT
Dual Fuel Changeover DUALFUEL
Dual Fuel Mstage
Changeover Time
OT Temp EnabledOT SENSOR
Multistage OT Temp
Lockout
OT Balance
Temperature (Dual Fuel)
OT Trip point for multistage lockout
LCD Contrast AdjustLCD CONTRAST [1] > – < [10]
Save ChangesSAVE CHANGES?
top line)
CONTROL
DELAY
SENSOR
CHGOVR
CHANGEOVER
DELAY
MSTG OT
LOCKOUT
OT BALANCE
TEMP
OT LOCKOUT
TEMP
Menu Options (LCD bottom
line; defaults in bold)
[HVAC] PANEL
UNCHANGD [OPEN]Dampers All Open
[15] 20 30 MIN15 minutes auto changeover timerNumber of minutes to delay auto changeover
15 [20] 30 MIN
15 20 [30] MIN30 minutes auto changeover timer
[NO] YESDisabledEnables or disables DATS. If Disabled, the
NO [YES]Enabled
< [160 F] >
< [40 F] >
NO [YES]
[NO] YESDisabled
[OT] MULTISTG
OT [MULTISTG]Dual Fuel Changeover by OT Temp +
[15 MIN] > – < [180 MIN]
[30 MIN] >
[NO] YES
NO [YES]Enabled
[NO] YES
NO [YES]Enabled
[0 F] > – < [50 F]
< [30 F] >
[0 F] > – < [50 F]
< [50 F] >
< [5] >
[NO] YES
NO [YES]Enabled
Menu option descriptionNotes:
Fan control by HVACIn heat mode, fan controlled by HVAC or turned
5 minutes–60 minutesNumber of minutes to delay before engaging
5 minutes–60 minutesNumber of minutes to delay before engaging
2.0 minutesNumber of minutes panel will purge following
Fan control by HVACFan controlled by HVAC or panel during purge.
Dampers UnchangedDamper position unchanged or all dampers
20 minutes auto changeover timer
110 deg F–180 deg FHigh temperature limit.
30 deg F–60 deg FLow temperature limit.
EnabledAllow panel to downstage multistage equip-
Dual Fuel Changeover by OT TempAllow panel to changeover from heat pump to
multistage call
Sets fossil fuel changeover delay
time.
DisabledEnables or disables outdoor temperature
DisabledWhen outdoor temperature is above OT
0 deg F–50 deg FSelects the temperature at which a dual fuel
0 deg F–50 deg FThe temp that locks out second or third stage
Contrast value 1–10Sets LCD display contrast for ease of viewing.
DisabledSaves or rejects the configuration settings.
on by panel in call for heat.
second stage.
third stage.
call for heat or cool.
open during purge.
when one zone is calling for heat and another
is calling for cooling.
Multistage DATS Inhibit setting is Disabled.
ment when near DATS high or low limit.
fossil fuel based on outdoor temperature, or
allow second stage call to changeover panel
to fossil fuel for a minimum of one hour when
outdoor temperature is above OT balance temperature setting. Multistage changeover is only
available on dual fuel applications configured
for 2 heat pump stages.
Sets number of minutes to delay fossil fuel
when calling for second stage heat.
sensor. If Disabled, the Multistage OT Temp
Lockout setting is Disabled.
Lockout temperature, locks out second and
third stage (only for conventional and heat
pump configurations), not dual fuel configurations.
configuration will change from heat pump to
fossil fuel.
(only for conventional and heat pump configurations, not dual fuel systems).
Lowest contrast is 1, highest contrast is 10.
69-2198—03 12
Page 15
The HZ432 TrueZONE panel contains an LED display that communicates system and
zone status. The LEDs indicate the following information.
Much of this information, as well as configuration information, is listed on the label
on the inside of the HZ432 cover. For users who prefer French or Spanish labels,
they are provided in form 69-2198FS. Cut them out and attach them to the inside of
the HZ432 cover.
HZ432 TrueZONE
OPERATION
HZ432
Table 6. LED Operation.
LEDDescription
HEAT 1Solid when in heat stage 1. Blinking when DATS high limit mode has been
reached.
HEAT 2, 3Solid when in heat stage 2, 3. Blinking when stage 2, 3 locked out due to
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
DATS or OT.
COOL 1Solid when in cool stage 1. Blinking when DATS low limit mode has been
reached.
EMERGENCY
HEAT
COOL 2Solid when in cool stage 2. Blinking when stage 2 locked out due to DATS.
PURGESolid when in purge (at power-up and after a call for heat or cool).
Blinking when the DATS sensor has failed, or the wires are shorted or
Fig. 20
M24798
open. Will blink for 3 minutes at power-up if DATS is not present.
FANSolid with a call for fan.
EM HEATSolid when in emergency heat mode. This light does not indicate a call for
heat. Emergency heat will only run when both HEAT and EM HEAT are lit.
ZONE 1, 2,
3, 4
Solid green when open or opening. Solid red when closed or closing.
Blinking amber when the VA draw of the dampers exceeds the specified
VA, or if there is a short circuit on the damper or thermostat wiring, causing that zone's breaker to trip.
CHECKOUT
To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the
Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on
page 10 for instructions on using these buttons.
Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation of the
equipment and dampers. These steps energize the equipment and damper terminals.
Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or
cool and viewing the active wires as displayed on the LCD screen. This is a useful way to troubleshoot which thermostat terminals are actually energized on each zone.
Table 7. Checkout.
Checkout StepLine 1 displayLine 2 DisplayNotes:
1. Display shows OTOT SENSOR VALcurrent OT temp (dynamic)All zone dampers open, all other relays OFF.
Honeywell warrants the products in this catalog (except those parts designated on Honeywell’s price lists as not covered by this warranty) to be free from defects due
to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPROTM, FocusPRO®, PRO
4000, PRO 3000, LineVoltTM PRO, Digital RoundTM, and Modern RoundTM (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date of
installation. CommercialPRO, PRO 2000 and PRO 1000 thermostats: twenty-four (24) months from date of installation. All other Honeywell thermostats and thermostats with a date code of 0452 or earlier: twelve (12) months from date of installation, unless specified otherwise. Honeywell Air Cleaners, Humidifiers, Ventilators,
Ultraviolet Treatment and Zoning Products with a date code of 0501 or later, excluding replacement maintenance parts: sixty (60) months from date of installation. All
other Honeywell indoor air quality and zoning products with a date code of 0452 or earlier: twenty-four (24) months from date of installation, unless specified otherwise. Variable frequency drive devices (VFD) and accessories: new products for thirty-six (36) months and factory refurbished drives for twelve (12) months from date
of installation when start-up and commissioning is performed by Honeywell VFD Authorized and trained personnel. All VFD warranty return products must have prior
authorization (Form No. 87-0284) and be returned only to the VFD Service Center in Chattanooga, TN. MS, MN and Fact Acting 2-position Direct Coupled Actuators:
sixty (60) months from date of installation. The warranty period for all other products is twelve (12) months from date of installation.
If a product is defective due to workmanship or materials, is removed within the applicable warranty period, and is returned to Honeywell in accordance with the procedure described below, Honeywell will, at its option, either repair, replace or credit the customer for the purchase price of the product, in accordance with the procedure described below. This warranty extends only to persons or organizations who purchase products in this catalog for resale.
The expressed warranty above constitutes the entire warranty of Honeywell with respect to the products in this catalog and IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL
HONEYWELL BE RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.