Honeywell HZ432 User Manual 2

HZ432 TrueZONE
69-2198-01
Zone Panel Professional Installation Guide
Installation Guide
M24797
13.42 (341)
1.86 (47)
8 (203)
TABLE OF CONTENTS
Specifications ................................................................................................................................. ii
Accessories .................................................................................................................................... 1
Mounting .........................................................................................................................................2
Wiring ..............................................................................................................................................3
Heat Pump ......................................................................................................................................6
Dual Fuel .........................................................................................................................................8
Basic Configuration ..................................................................................................................... 10
Advanced Configuration .............................................................................................................. 12
Operation ...................................................................................................................................... 13
Checkout ...................................................................................................................................... 13
Warranty ....................................................................................................................................... 14
SPECIFICATIONS
Input Ratings:
Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more.
Current Draw:
Zone Panel: 8.5 VA max. All VA specifications at 24 VAC.
Wiring:
18- or 20-gauge solid (not stranded) wire.
Humidity Ratings:
5% to 90% RH non-condensing.
Temperature Ratings:
Shipping: -20° to 150°F (-29° to 66°C) Operating: -40° to 165°F (-40° to 74°C)
Dimensions:
See below.
Emissions:
Complies with FCC Class B, part 15 requirements.
For assistance with this product please visit http://yourhome.honeywell.com
or call Honeywell Zoning Hotline toll-free at 1-800-828-8367
Need Help?
Fig. 1. HZ432 TrueZONE panel dimensions in in. (mm).
Read and save these instructions.
® U.S. Registered Trademark. Patents pending.
Copyright © 2008 Honeywell International Inc. All rights reserved.
HZ432 TrueZONE
ACCESSORIES
Table 1. Recommended Thermostats.
System Non-
Programmable
Single­Stage
Multi­Stage
Heat­Pump
Wire­less
Note: All versions of the model numbers listed above
will work with the applications they're listed for.
* This thermostat cannot control two stages of fossil
fuel when in emergency heat mode.
Type Honeywell
Zone Spring-open/
Zone Power-open/
Bypass Static pres-
TH5110D, TH3110D, T87N
TH5220D TH8320U, TH8321U,
TH5220D (2H/1C only) TH3210D (2H/1C only) TH5320U* (Up to 3H/2C)
TH5320R TH6320R
Table 2. Recommended Dampers.
Damper
power-closed
power-closed
sure regulat­ing damper
Programmable
TH8110U, TH6110D, TH4110D
TH6220D, YTH9421C
TH8320U (Up to 3H/2C) TH8321U (Up to 3H/2C) TH6320U* (Up to 3H/2C) TH6220D (2H/1C only) TH4210D (2H/1C only) YTH9421C
Round Rectangular
ARD ZD
MARD/ RRD
SPRD SPRD
For recommended dampers call the Honeywell Zoning Hotline at 1-800-828-8367.
Table 3. Maximum Dampers.*
Ambient Temp. Maximum Damper VA per Zone
100°F (38°C) 28.8
160°F (71°C) 16.8
* Use an SDCR (Slave Damper Control Relay) for addi-
tional dampers.
Maximum dampers per panel is limited by transformer
size.
Ensure transformer is large enough to power the panel
(10 VA) and dampers.
Table 4. Accessories.
Accessory Description
40 VA transformer* AT140A1042*
75 VA transformer AT175A1008
Discharge Air Temperature Sensor *
Wired Outdoor Air Temperature Sensor
Wireless Outdoor Air Temperature Sensor
Wireless Adapter THM4000R1000
TAZ-4 TotalZone® Add-A-ZoneTM
SDCR Slave Damper Control
Wireless Remote Control REM5000R1001
* Included in HZ432K kit.
DATS C7735A1000*
C7089U1006 (hard wired)
C7089R1013 (wireless)
Control Panel
Relay
1 69-2198—01
Installation Guide
SUPPLY
DUCT
DATS
(AT LEAST 3 FT
FROM PLENUM)
DATS
(ALTERNATE
LOCATION)
TrueZONE PANEL
MOUNTED ON
RETURN DUCT
TrueZONE PANEL
MOUNTED ON WALL
ZD SERIES
ZONE DAMPERS
SPRD BYPASS
DAMPER
FURNACE OR
AIR CONDITIONER
M24738
M24807
MOUNTING
Mount the HZ432 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or cold-
1
air return. NOTE: The HZ432 TrueZONE panel can be mounted in
any orientation; level it for appearance only.
Please refer to TrueZONE Panel Frequently Asked Questions form 50-9694 for operating details.
Fig. 2
2
Separate the zone panel cover from the base, and use the base as a template to drill mounting holes. Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).
Use two screws for attaching to a stud or roof truss, or four screws for duct or drywall/plaster installations.
Fig. 3
69-2198—01 2
HZ432 TrueZONE
M24743
M24808
Rc
R C
W
W2
Y
Y2
G
M1 M4 M6
R C
W1/E
W2 W3
Y1 Y2
G
O/B
L
ZONE 4
DAMPER
THERMOSTAT
M24920
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
ZONE 3
DAMPER
M1 M4 M6 R
ZONE 1
DAMPER
RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED
M4 OPEN
M6 CLOSED
M1 COMMON
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
ZONE 2
DAMPER
WIRING
CAUTION: Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. Wire entire panel before applying transformer power.
Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional sys­tems, refer to this page. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9.
Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring diagrams to wire the zone panel to the thermostats and dampers.
Install thermostats using instructions provided with thermostats.
3
Connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To release wire, press the button on top of the terminal.
Fig. 5
4
Fig. 4
The HZ432 offers many innovations for wire management and organization: wires can be run behind the panel, through wire channels on its sides, and must be attached to a wiring anchor with a cable tie.
Install dampers using instructions provided with dampers. Connect dampers to zone panel.
NOTE: Multiple dampers can be wired in parallel.
3 69-2198—01
Fig. 6
Installation Guide
C7735A1000
M24804
DATS DATS
SENSOR
DEDICATED
TRANSFORMER
R
C
M24806
R C
POWER
L1 (HOT)
L2
RH RC
W1/E
W2 W3
Y1 Y2
G O B
DS/BK
M24809
HVAC
FAN RELAY
24 VOLT TRANS.
G
Y
Y2
C
R
W
COMPRESSOR
RELAY
W2
EQUIPMENT
M28193
A B C D
WIRELESS
ADAPTER
WIRELESS
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
M28207
OT OT
SENSORS
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
WIRING
5
6
7
Connect DATS as shown.
Fig. 7
Connect outdoor air temperature sensor as shown. Required for dual fuel systems; optional for other multistage systems.
Fig. 8
Connect equipment as shown.
The DS/BK terminal is used with a variable-speed fan. Connect the DS, BK, ODD, or DHUM terminal on the HVAC equipment to this terminal. When 1 zone is calling (or 25% on systems with more than 4 zones) this termi­nal will be de-energized of 24 VAC. This reduces blower speed on most variable speed blowers.
69-2198—01 4
8
9
Fig. 9
If using any wireless device, connect the ABCD terminals for the wireless interface module.
Fig. 10
Connect transformer as shown.
Fig. 11
HZ432 TrueZONE
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCY
HEAT
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B
L
RH RC
W1/E
W2 W3
Y1 Y2
G O B
DS/BK
HOME
CONFIG
CHECK OUT
ADJUST SETTING
M4 OPEN
M6 CLOSED
M1 COMMON
M28196
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
DEDICATED
TRANSFORMER
R
C
L1 (HOT)
L2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
M1 M4 M6
R C
W1/E
W2 W3
Y1 Y2
G
O/B
L
DATS DATS
OT OT
AZ1 AZ2
ZONE 4
DAMPER
THERMOSTATEQUIPMENT
POWERSENSORS ACCESSORIES
ZONE 2
DAMPER
THERMOSTATZONE 1
DAMPER
THERMOSTAT ZONE 3
DAMPER
THERMOSTAT
R C
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
A B C D
WIRELESS
ADAPTER
WIRELESS
HVAC
FAN RELAY
24 VOLT TRANS.
G
Y
Y2
C
R
W
COMPRESSOR
RELAY
W2
Rc
R C
W
W2
Y
Y2
G
Rc R C W W2 Y Y2 G
Rc R C W W2 Y Y2 G
Rc R C W W2 Y Y2 G
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
CONVENTIONAL
The following diagram is an overall view of wiring for a conventional system as depicted in steps 3–9.
Fig. 12. Zone panel wiring—conventional.
5 69-2198—01
Installation Guide
1
2
1
2
1
2
3
3
1
2
1
2
Rc R C E AUX Y
G O/B L
Rc R C E AUX Y
G O/B L
Rc
R C E
AUX
Y
G
O/B
L
Rc R C E AUX Y
G O/B
L
ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.
FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR COOL CHANGEOVER VALVES, AND ATTACH B FOR HEAT CHANGEOVER VALVES.
IF EQUIPMENT DOES NOT HAVE SEPARATE E AND W2 TERMINALS, JUMPER E TO W2 ON PANEL AND WIRE TO E.
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCY
HEAT
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B
L
RH RC
W1/E
W2 W3
Y1 Y2
G O B
DS/BK
HOME
CONFIG
CHECK OUT
ADJUST SETTING
M4 OPEN
M6 CLOSED
M1 COMMON
M24794
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
DEDICATED
TRANSFORMER
R
C
L1 (HOT)
L2
AIR
HANDLER
FAN RELAY
EM. HEAT
AUX. HEAT
HEAT PUMP
G
Y
24 VOLT TRANS.
C
R
Y
E
C
R
W2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
M1 M4 M6
R C
W1/E
W2 W3
Y1 Y2
G
O/B
L
DATS DATS
OT OT
AZ1 AZ2
ZONE 4
DAMPER
THERMOSTATEQUIPMENT
POWERSENSORS
A B C D
ACCESSORIES
ZONE 2
DAMPER
THERMOSTATZONE 1
DAMPER
THERMOSTAT ZONE 3
DAMPER
THERMOSTAT
R C
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
WIRELESS
ADAPTER
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
REVERSING
VALVE
WIRELESS
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
HEAT PUMP
Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat.
NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by heat pump thermostats. The diagram below shows a heat pump thermostat used with a heat pump system.
Fig. 13. Zone panel wiring—heat pump, 2-heat/1-cool with electric auxiliary heat.
69-2198—01 6
Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat.
1
2
1
2
1
2
1
2
1
2
Rc R C E AUX Y Y2 G O/B L
Rc R C E AUX Y Y2 G O/B L
Rc
R C
E
AUX
Y
Y2
G
O/B
L
Rc R C E AUX Y Y2 G O/B
L
ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.
FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR COOL CHANGEOVER VALVES, AND ATTACH B FOR HEAT CHANGEOVER VALVES.
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
HZ432
HEAT 1 HEAT 2
HEAT 3 COOL 1 COOL 2 PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCY
HEAT
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B
L
RH RC
W1/E
W2 W3
Y1 Y2
G O B
DS/BK
HOME
CONFIG
CHECK OUT
ADJUST SETTING
M4 OPEN
M6 CLOSED
M1 COMMON
M24795
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
DEDICATED
TRANSFORMER
R
C
L1 (HOT)
L2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
M1 M4 M6
R C
W1/E
W2 W3
Y1 Y2
G
O/B
L
DATS DATS
OT OT
AZ1 AZ2
ZONE 4
DAMPER
THERMOSTATEQUIPMENT
POWERSENSORS ACCESSORIES
ZONE 2
DAMPER
THERMOSTATZONE 1
DAMPER
THERMOSTAT ZONE 3
DAMPER
THERMOSTAT
R C
3
3
IF EQUIPMENT DOES NOT HAVE SEPARATE E AND W2 TERMINALS, JUMPER E TO W2 ON PANEL AND WIRE TO E.
AIR
HANDLER
FAN RELAY
EM. HEAT
AUX. HEAT
G
Y2
Y
24 VOLT TRANS.
C
R
E
W3
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
HEAT PUMP
Y
C
R
REVERSING
VALVE
Y2
A B C D
WIRELESS
ADAPTER
WIRELESS
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
Fig. 14. Zone panel wiring—heat pump, 3-heat/2-cool with electric stage 3 heat.
HZ432 TrueZONE
HEAT PUMP
7 69-2198—01
Installation Guide
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCY
HEAT
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B
L
RH RC
W1/E
W2 W3
Y1 Y2
G O B
DS/BK
HOME
CONFIG
CHECK OUT
ADJUST SETTING
M4 OPEN
M6 CLOSED
M1 COMMON
M24796
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
DEDICATED
TRANSFORMER
R
C
L1 (HOT)
L2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
M1 M4 M6
R C
W1/E
W2 W3
Y1 Y2
G
O/B
L
DATS DATS
OT OT
AZ1 AZ2
ZONE 4
DAMPER
THERMOSTATEQUIPMENT
POWERSENSORS ACCESSORIES
ZONE 2
DAMPER
THERMOSTATZONE 1
DAMPER
THERMOSTAT ZONE 3
DAMPER
THERMOSTAT
R C
FURNACE
FAN RELAY
G
Y
24 VOLT TRANS.
C
R
W
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
A B C D
WIRELESS
ADAPTER
WIRELESS
Rc
R C E
AUX
Y
Y2
G
O/B
L
Rc R C E AUX Y Y2 G O/B L
Rc R C E AUX Y Y2 G O/B L
Rc R C E AUX Y Y2 G O/B L
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
HEAT PUMP
Y
C
R
REVERSING
VALVE
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
DUAL FUEL
Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump.
Fig. 15. Zone panel wiring—dual fuel: single-stage furnace and single-stage heat pump.
69-2198—01 8
HZ432 TrueZONE
HZ432
HEAT 1 HEAT 2
HEAT 3 COOL 1 COOL 2 PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCY
HEAT
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B
L
RH RC
W1/E
W2 W3
Y1 Y2
G O B
DS/BK
HOME
CONFIG
CHECK OUT
ADJUST SETTING
M4 OPEN
M6 CLOSED
M1 COMMON
M24793
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
DEDICATED
TRANSFORMER
R
C
L1 (HOT)
L2
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
M1 M4 M6
R C
W1/E
W2 W3
Y1 Y2
G
O/B
L
DATS DATS
OT OT
AZ1 AZ2
ZONE 4
DAMPER
THERMOSTATEQUIPMENT
POWERSENSORS ACCESSORIES
ZONE 2
DAMPER
THERMOSTATZONE 1
DAMPER
THERMOSTAT ZONE 3
DAMPER
THERMOSTAT
R C
FURNACE
FAN RELAY
G
Y2
Y
24 VOLT TRANS.
C
R
W
C7089U1006
OUTDOOR
TEMPERATURE
SENSOR
C7735A1000
DATS
HEAT 1
HEAT 2
W2
HEAT PUMP
Y
C
R
REVERSING
VALVE
Y2
A B C D
WIRELESS
ADAPTER
WIRELESS
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
Rc
R C
E
AUX
Y
Y2
G
O/B
L
Rc R C E AUX Y Y2 G O/B L
Rc R C E AUX Y Y2 G O/B L
Rc R C E AUX Y Y2 G O/B L
RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
DUAL FUEL
Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump.
Fig. 16. Zone panel wiring—dual fuel: two-stage furnace and two-stage heat pump.
9 69-2198—01
Installation Guide
HOMEWIRELESS
MODE
BACK NEXT
CONFIG
CHECK OUT
ADJUST SETTING
M24799
HOME
MODE
BACK NEXT
CONFIG
CHECK OUT
ADJUST SETTING
M24810
WIRELESS
CONFIGURATION
To enter Configuration:
Press the Mode button (the Config LED will
1
2
3
light up).
Use the Back and Next buttons to navigate through the configuration menus. Pressing Next enters the selected option for that menu item and advances to the next menu. Adjust settings up or down by pressing the Adjust Setting button.
The flow chart below illustrates basic zone panel configuration. For additional configuration, see Advanced Configuration on page 12. The label on the inside cover of the HZ432 Zone Panel also con­tains configuration information.
Fig. 17
69-2198—01 10
Fig. 18
4
HOME
MODE
BACK NEXT
CONFIG
CHECK OUT
ADJUST SETTING
M28194
WIRELESS
Press the Mode button until the Wireless LED lights up. The TrueZONE must be configured for wireless devices to select Wireless mode.
Press Next to add devices. While the display alternates the Press Connect and
Exit screens, push the Connect button(s) on the wire­less device(s).
-OR­Follow the instructions that came with the wireless
device(s). Press Next to exit.
HZ432 TrueZONE
CONNECT WIRELESS DEVICES
Fig. 19
5
If using more than 4 zones, use the TAZ-4 Add-A-ZoneTM Control Panel. Follow instructions with the TAZ-4 for installation (form 69-1366).
Note: If using a wireless device, a maximum of 4 zones may be configured.
11 69-2198—01
Installation Guide
ADVANCED CONFIGURATION
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 10 for instructions on using these buttons.
Table 5. Advanced Configuration.
Menu Name Menu Title (LCD
Heat Fan HEAT FAN
Stage 2 Timer STAGE 2 TIMER [5 MIN] > – < [60 MIN]
Stage 3 Timer STAGE 3 TIMER [5 MIN] > – < [60 MIN]
Purge Timer PURGE TIME [2] 3.5 5 MIN 2.0 minutes Number of minutes panel will purge following
Purge Fan FAN IN PURGE [HVAC] PANEL Fan control by HVAC Fan controlled by HVAC or panel during purge.
Purge Dampers PURGE DAMPERS [UNCHANGD] OPEN Dampers Unchanged Damper position unchanged or all dampers
Auto Changeover Delay CHANGEOVER
DATS Enabled DISCHARGE
DATS High Limit DAT HIGH LIMIT [110 F] > – < [180 F]
DATS Low Limit DAT LOW LIMIT [30 F] > – < [60 F]
Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES] Enabled Allow panel to downstage multistage equip-
Dual Fuel Changeover DUALFUEL
Dual Fuel Mstage Changeover Time OT Temp Enabled OT SENSOR [NO] YES Disabled Enables or disables outdoor temperature
Multistage OT Temp Lockout
OT Balance Temperature (Dual Fuel)
OT Trip point for multi­stage lockout
LCD Contrast Adjust LCD CONTRAST [1] > – < [10]
Save Changes SAVE CHANGES? [NO] YES Disabled Saves or rejects the configuration settings.
Reload Defaults RELOAD
top line)
CONTROL
DELAY
SENSOR
CHGOVR
CHANGEOVER DELAY
MSTG OT LOCKOUT
OT BALANCE TEMP
OT LOCKOUT TEMP
DEFAULTS?
Menu Options (LCD bottom line; defaults in bold) [HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or turned
HVAC [PANEL] Fan control by Panel
[5 MIN] >
[5 MIN] >
2 [3.5] 5 MIN 3.5 minutes 2 3.5 [5] MIN 5.0 minutes
HVAC [PANEL] Fan control by Panel
UNCHANGD [OPEN] Dampers All Open [15] 20 30 MIN 15 minutes auto changeover timer Number of minutes to delay auto changeover 15 [20] 30 MIN 20 minutes auto changeover timer 15 20 [30] MIN 30 minutes auto changeover timer [NO] YES Disabled Enables or disables DATS. If Disabled, the NO [YES] Enabled
< [160 F] >
< [40 F] >
[NO] YES Disabled [OT] MULTISTG Dual Fuel Changeover by OT Temp Allow panel to changeover from heat pump to OT [MULTISTG] Dual Fuel Changeover by OT Temp +
[15 MIN] >< [180 MIN] [30 MIN] >
NO [YES] Enabled
[NO] YES Disabled When outdoor temperature is above OT NO [YES] Enabled
[0 F] > – < [50 F]
< [30 F] >
[0 F] > – < [50 F]
< [50 F] >
< [5] >
NO [YES] Enabled [NO] YES Disabled Restores the panel's default configuration set- NO [YES] Enabled
Menu option description Notes:
5 minutes–60 minutes Number of minutes to delay before engaging
5 minutes–60 minutes Number of minutes to delay before engaging
110 deg F–180 deg F High temperature limit.
30 deg F–60 deg F Low temperature limit.
multistage call
Sets fossil fuel changeover delay time.
0 deg F–50 deg F Selects the temperature at which a dual fuel
0 deg F–50 deg F The temp that locks out second or third stage
Contrast value 1–10 Sets LCD display contrast for ease of viewing.
on by panel in call for heat.
second stage.
third stage.
call for heat or cool.
open during purge.
when one zone is calling for heat and another is calling for cooling.
Multistage DATS Inhibit setting is Disabled.
ment when near DATS high or low limit.
fossil fuel based on outdoor temperature, or allow second stage call to changeover panel to fossil fuel for a minimum of one hour when outdoor temperature is above OT balance tem­perature setting. Sets number of minutes to delay fossil fuel when calling for second stage heat.
sensor. If Disabled, the Multistage OT Temp Lockout setting is Disabled.
Lockout temperature, locks out second or third stage (only for conventional and heat pump configurations).
configuration will change from heat pump to fossil fuel.
(only for conventional and heat pump configu­rations, not dual fuel systems).
Lowest contrast is 1, highest contrast is 10.
tings.
69-2198—01 12
The HZ432 TrueZONE panel contains an LED display that communicates system and
M24798
HZ432
HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCY
HEAT
zone status. The LEDs indicate the following information.
Much of this information, as well as configuration information, is listed on the label on the inside of the HZ432 cover. For users who prefer French or Spanish labels, they are provided in form 69-2198FS. Cut them out and attach them to the inside of the HZ432 cover.
Table 6. LED Operation.
LED Description
HEAT 1 Solid when in heat stage 1. Blinking when DATS high limit mode has been
reached.
HEAT 2, 3 Solid when in heat stage 2, 3. Blinking when stage 2, 3 locked out due to
DATS or OT.
COOL 1 Solid when in cool stage 1. Blinking when DATS low limit mode has been
reached.
COOL 2 Solid when in cool stage 2. Blinking when stage 2 locked out due to DATS.
PURGE Solid when in purge (at power-up and after a call for heat or cool).
Blinking when the DATS sensor has failed, or the wires are shorted or open. Will blink for 3 minutes at power-up if DATS is not present.
FAN Solid with a call for fan.
EM HEAT Solid when in emergency heat mode. This light does not indicate a call for
heat. Emergency heat will only run when both HEAT and EM HEAT are lit.
ZONE 1, 2, 3, 4
Solid green when open or opening. Solid red when closed or closing. Blinking amber when there is a damper or thermostat short circuit (circuit breaker trip).
HZ432 TrueZONE
OPERATION
Fig. 20
CHECKOUT
To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on page 10 for instructions on using these buttons.
Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation. Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or
cool and viewing the active wires as displayed on the LCD screen.
Table 7. Checkout.
Checkout Step Line 1 display Line 2 Display Notes:
1. Display shows OT OT SENSOR VAL current OT temp (dynamic) All zone dampers open, all other relays OFF.
2. Display shows DATS DAT SENSOR VAL current DATS (dynamic)
3. Heat stages test TEST HEAT [OFF] 1 2 3 Heat turns on (fan also turns on if configured for
4. EM Heat stages test TEST EMERG HEAT [OFF] 1 2 Emergency heat turns on (fan also turns on).
5. Cool stages test TEST COOL [OFF] 1 2 Cooling turns on (fan also turns on).
6. Fan Test TEST FAN [OFF] ON Fan cycles on and off.
7. Damper 1 test TEST Z1 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
8. Damper 2 test TEST Z2 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
9. Damper 3 test TEST Z3 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
10. Damper 4 test TEST Z4 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
11. View Tstat1 inputs ZONE1 STAT INPTS Displays active Tstat1 terminals or displays wire-
12. View Tstat2 inputs ZONE2 STAT INPTS Displays active Tstat2 terminals or displays wire-
13. View Tstat3 inputs ZONE3 STAT INPTS Displays active Tstat3 terminals or displays wire-
14. View Tstat4 inputs ZONE4 STAT INPTS Displays active Tstat4 terminals or displays wire-
15. Exit checkout mode? EXIT CHECKOUT? (NEXT = EXIT)
16. Exiting checkout mode EXITING CHECKOUT
less thermostat operation
less thermostat operation
less thermostat operation
less thermostat operation
fan on in heat).
Tests thermostat connection with HVAC off.
Tests thermostat connection with HVAC off.
Tests thermostat connection with HVAC off.
Tests thermostat connection with HVAC off.
13 69-2198—01
WARRANTY
Honeywell warrants the products in this catalog (except those parts designated on Honeywell’s price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPROTM, FocusPRO®, PRO 4000, PRO 3000, LineVoltTM PRO, Digital RoundTM, and Modern RoundTM (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date of installation. CommercialPRO, PRO 2000 and PRO 1000 thermostats: twenty-four (24) months from date of installation. All other Honeywell thermostats and thermo­stats with a date code of 0452 or earlier: twelve (12) months from date of installation, unless specified otherwise. Honeywell Air Cleaners, Humidifiers, Ventilators, Ultraviolet Treatment and Zoning Products with a date code of 0501 or later, excluding replacement maintenance parts: sixty (60) months from date of installation. All other Honeywell indoor air quality and zoning products with a date code of 0452 or earlier: twenty-four (24) months from date of installation, unless specified other­wise. Variable frequency drive devices (VFD) and accessories: new products for thirty-six (36) months and factory refurbished drives for twelve (12) months from date of installation when start-up and commissioning is performed by Honeywell VFD Authorized and trained personnel. All VFD warranty return products must have prior authorization (Form No. 87-0284) and be returned only to the VFD Service Center in Chattanooga, TN. MS, MN and Fact Acting 2-position Direct Coupled Actuators: sixty (60) months from date of installation. The warranty period for all other products is twelve (12) months from date of installation.
If a product is defective due to workmanship or materials, is removed within the applicable warranty period, and is returned to Honeywell in accordance with the pro­cedure described below, Honeywell will, at its option, either repair, replace or credit the customer for the purchase price of the product, in accordance with the proce­dure described below. This warranty extends only to persons or organizations who purchase products in this catalog for resale.
The expressed warranty above constitutes the entire warranty of Honeywell with respect to the products in this catalog and IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL HONEYWELL BE RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
cust omer.honeywel l.com
® U.S. Registered Trademark. © 2008 Honeywell International Inc. Patents pending 69-2198— 01 M.S. 02-08
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...