Honeywell HR200 User Manual

M29857
68-0171-12
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems
PRODUCT DATA
Included In thIs VentIlatIon system Box
*
e
STARTED
GETTING
MOUNTING PLUMBING WIRING APPENDICESDUCTING
*
Wire cutter/stripper 18-gauge wire (up to 5 conductor) Standard screwdriver Insulated 6-inch round duct Non-insulated 6-inch round duct Two 6-inch weather hoods Two 6-inch starter collars 1/2-inch I.D. drain hose Airflow balancing kit Foil tape
F1 F3
OPTIONAL CONTROLS SOLD SEPARATELY
e
F1
F2
F3
F4
F5
F2
F4 F5
HR150/200 or ER150/200 Perfect
Window™ Fresh Air Ventilation System
Owner’s Manual Hanging straps * T-fitting * 2 drain spouts VisionPRO IAQ control TrueIAQ Dehumidistat H8908
Digital fan timer W8150 ventilation control
Not with “C” models.
*
Perfect Window Fresh Air Ventilation Systems
GETTING STARTED
Safety Definitions and Precautions . . . . . . . . . . . . . . 2
Application ................................. 3
Features .................................. 3
Planning the Installation . . . . . . . . . . . . . . . . . . . . . . 4
Sizing .................................. 5
Mounting Position and Location. . . . . . . . . . . . . . . . . 6
Balancing Airflow ............................ 9
MOUNTING
Installation ................................ 10
Suspended from Floor Joists .................. 10
PLUMBING
Installing Drain Line and P-Trap . . . . . . . . . . . . . . . 11
STARTED
GETTING
MOUNTING PLUMBING WIRING APPENDICESDUCTING
WIRING
Heat Recovery Ventilator (HRV) and
Energy Recovery Ventilator (ERV) Connections . . . 12
Digital Fan Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
DUCTING
Airflow Balancing ........................... 16
Balancing Procedure ........................ 16
APPENDICES
Startup and Checkout . . . . . . . . . . . . . . . . . . . . . . . 17
Cleaning Filters and Core .................. 17
Inspecting Exterior Hoods . . . . . . . . . . . . . . . . . 17
Troublshooting ............................. 18
Parts List ................................. 20
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
NEED HELP? For assistance with this product please visit http://yourhome.honeywell.com
?
or call Honeywell Customer Care toll-free at 1-800-468-1502.
Read and save these instructions.
® U.S. Registered Trademark. Patents pending. Copyright © 2009 Honeywell International Inc. All rights reserved.
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
1
GETTING
STARTED
Safety Definitions and Precautions
Safety Definitions
These safety terms identify information you must read.
CAUTION: Indicates a hazardous situation which, if not avoided, could cause bodily injury
or property damage.
WARNING: Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Safety Precautions
Make sure you read and understand the following safety and/or property hazards before installing,
using, or working with the Perfect Window™ Fresh Air Ventilation System:
All ducting to the outdoors must be terminated above anticipated snow lines and be fitted with a •
weather cap that incorporates bird screening.
CAUTION: Electrical shock hazard.
Can cause personal injury or equipment damage.
Disconnect power supply to prevent electrical shock or equipment damage.
CAUTION: Electrical Shock Hazard.
Can cause personal injury.
Be sure ventilator is correctly grounded. Confirm polarity of power line switched with safety (disconnect)
switch when cleaning or servicing unit.
CAUTION: Electrical Hazard.
Can cause equipment damage
Disconnect HRV/ERV from power source before connecting or disconnecting digital fan timer or other
device to HRV/ERV high-speed override terminals.
2
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
Application
The HR150B and HR200B Perfect Window™ Fresh Air Ventilation Systems provide proper levels of ventilation
with energy savings by transferring heat between the exhaust and fresh air streams.
The ER150B and ER200B Perfect Window™ Fresh Air Ventilation Systems provide proper levels of ventilation
with energy savings by transferring heat and moisture between the exhaust and fresh air streams.
The ER150C and ER200C Perfect Window™ Fresh Air Ventilation Systems are specifically designed for
installations in unconditioned spaces such as attics and garages in regions where the outdoor temperature does
not drop below freezing.
Features
Remotely control two-speed fan.•
Integral balancing dampers for quick installation.•
Provides ventilation that helps contractors meet ASHRAE 62.•
Automatic, economical built-in frost control available for operation to design temperatures of -40°F (-40°C).•
HR150 and HR200 models have an easy-to-clean aluminum cross-flow core.•
ER150 and ER200 models have an advanced energy heat and moisture recovery fixed core.•
Washable energy transfer core.•
Includes vibration isolation hardware and duct collars.•
Insulated cabinet made of rugged steel.•
Permanent (washable) prefilters.•
Quiet operation.•
Digital fan timer option on all models.•
Advanced ventilation algorithms available on VisionPRO IAQ, TrueIAQ and W8150 controls.•
Interlock the ERV/HRV to an air handler or furnace blower.•
Dehumidistat operation deactivated in summer.•
STARTED
GETTING
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
3
GETTING
STALE AIR FROM INSIDE
DEFROST PORT
FRESH AIR TO INSIDE
FRESH AIR FROM OUTSIDE
STALE AIR TO OUTSIDE
M29739
BALANCING DAMPER
FILTERS
FILTERS (2)
DRAIN
M29853
MOTOR
BLOWERS
FRESH AIR FROM OUTSIDE
DEFROST PORT
DRAIN PANS
BALANCING DAMPER
BALANCING DAMPER
CORE
STALE AIR FROM INSIDE
FRESH AIR TO INSIDE
STALE AIR TO OUTSIDE
FRESH AIR TO INSIDE
FRESH AIR
FROM OUTSIDE
M29861
MOTOR
MOTOR
STALE AIR
FROM HOUSE
ENERGY TRANSFER CORE
BALANCING
DAMPER
CORE
STALE AIR
TO OUTSIDE
BALANCING
DAMPER
FILTERS (2)
STARTED
Planning the Installation
Failure to comply with these requirements will result in voided warranty, improper installation, and
service callbacks.
The Fresh Air Ventilation System is designed to
supply fresh air and exhaust stale air. The system
draws fresh outdoor air through the ventilator for
distribution throughout the house.
Heat Recovery Ventilator
Stale air is exhausted through the ventilator and to
the outdoors. Heat is transferred from one airstream
to the other as the air passes through the opposite
Duct connections and airflow (HR150B/HR200B).Fig. 1.
sides of the heat transfer core. See Fig. 1.
Energy Recovery Ventilator
Stale air is exhausted through the ventilator and to
the outdoors. Heat and moisture is transferred from
one airstream to the other as the air passes through
the opposite sides of the energy transfer core.
See Fig. 2 and 3.
4
Duct connections and airflow (ER150C/ER200C).Fig. 2.
Duct connections and airflow (ER150B/ER200B).Fig. 3.
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
Sizing
ASHRAE 62.2
There are several methods that can provide
satisfactory results for sizing a ventilator to provide
adequate ventilation for a home. There is a new
residential ventilation standard, ASHRAE 62.2, that
suggests the following:
7.5 CFM per person (count people as 1 per •
bedroom plus 1) plus 1 CFM per 100 sq. ft.
Example:
2200 sq. ft. house with 4 bedrooms
= (7.5 CFM x (4 bedrooms + 1)) + (1 CFM x (2200 sq. ft. / 100))
= (7.5 x 5) + (2200 / 100)
= 37.5 + 22
= 59.5 CFM
In this case 60 CFM continuous would provide
satisfactory ventilation for this home.
ASHRAE 62.1
Some regions still use the previous standard, ASHRAE
62.1, as the code for ventilation in their region.
The ASHRAE Standard 62.1 Ventilation for Acceptable
Indoor Air Quality suggests the following:
Option 1: Fresh Air Ventilation System provides
continuous fresh air supply of 93 cfm, and intermittent
capacity for bathrooms of 150 cfm. A separate 100
cfm exhaust fan is used for the range hood.
Supply air flow required = 93 cfm
Exhaust air flow required = 150 cfm
Any Honeywell ventilation unit provides suitable
ventilation capacity. See Fig. 22.
Option 2: Fresh Air Ventilation System provides
continuous 93 cfm fresh air supply, 150 cfm
intermittent exhaust capacity for bathrooms and
continuous 50 cfm kitchen ventilation.
Supply air flow required = 93 cfm
Exhaust air flow required = 200 cfm
Honeywell HR200/ER200 have the exhaust capacity
required to meet the ventilation needs of this
application. See Fig. 22.
STARTED
GETTING
.35 air changes per hour (ach) but not less than 15 •
cfm per person for living areas = house size (sq ft)
x ceiling height (ft) / 60 (min) x.35 (ach)
Example:
= 2000 sq ft x 8 ft / 60 min x .35 ach = 93 cfm
50 cfm intermittent or 20 cfm continuous capacity •
for bathrooms
Example:
50 cfm intermittent x 3 bathrooms = 150 cfm
20 cfm continuous x 3 bathrooms = 60 cfm
100 cfm intermittent or 25 cfm continuous capacity •
for kitchens
Example:
100 cfm intermittent x 1 kitchen = 100 cfm
25 cfm continuous x 1 kitchen = 25 cfm
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
5
GETTING
INSULATED FLEX DUCT
COLLAR ON VENTILATOR
SEAL INTERIOR LINING OF FLEX DUCT TO INSIDE COLLAR
SEAL OUTER LINING OF FLEX DUCT TO OUTER COLLAR
M6557
STARTED
Mounting Position and Location
The HR150/ER150 and HR200/ER200 can be
suspended from exposed ceiling joists, ceiling surface
or floor mounted. (Level ventilator so drains function
correctly.)
NOTE: ER150C and ER200C are specifically designed
for installations in unconditioned spaces such as
attics and garages in regions where the outdoor
temperature does not drop below freezing. (These
units are not equipped with drain kits.)
Locate fresh air intake 6 ft (2m) or more from stale •
air exhaust to prevent exhaust air from re-entering.
Locate ventilator where length of ducting required •
is minimal.
Install HR150/ER150 and HR200/ER200 in a
conditioned space using these guidelines:
Pipe drain line (ER150C and ER200C do not have •
drain kits) from the ventilator to a drain.
Use an existing electrical outlet with appropriate •
current rating (or install one) close to ventilator
power cord.
Allow space for drain line by placing the ventilator •
at least 10 in. (254 mm) off the floor.
For access and removal of ventilator core, allow at •
least 25 in. (635 mm) of open space in front of unit.
Ducting
Ducting between the ventilator and the outdoors must
be insulated and have a continuous air vapor barrier.
See Fig. 4.
IMPORTANT
All ducting to the outdoors must be terminated above
anticipated snow lines and be fitted with a weather cap
that incorporates bird screening.
Sealing insulated duct terminations.Fig. 4.
6
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
Design and installation of ductwork must be according to standard HVAC practice to deliver required quantities
COLD AIR RETURN
EXHAUST AIR FROM VARIOUS PARTS OF HOME (BATHROOMS IF REQUIRED; KITCHENS IF REQUIRED; ROOMS WITHOUT OPERABLE WINDOWS,
A
ND POTENTIALLY BASEMENTS).
FORCED AIR FURNACE
COMBUSTION OR ELECTRIC
M6549D
RETURN AIR
OUTDOORS
NOTES:
1.
2.
3.
4.
FURNACE BLOWER NEED NOT OPERATE TO PROVIDE GOOD AIR DISTRIBUTION/QUALITY WITH THIS SYSTEM.
IF FURNACE BLOWER OPERATION IS REQUIRED TO HELP DISTRIBUTE SUPPLY AIR: RUN CONTINUOUSLY OR INTERLINK ELECTRICALLY (LOW VOLTAGE).
NO SEPARATION REQUIREMENTS ARE NECESSARY BETWEEN DIRECT CONNECTION POINT AND FURNACE.
WEATHER-HOOD ARRANGEMENT IS FOR DRAWING ONLY. 6 FT (2m) MINIMUM SEPARATION REQUIRED, 18 IN. (0.46m) ABOVE GRADE MINIMUM.
of fresh air to temperature-controlled space and exhaust equivalent quantities of room air to the outside.
Keep intake and exhaust duct runs as short as possible with few bends or elbows.
Keep duct sizes as large as possible throughout the installation.•
Use a 6 in. diameter round duct for all connections to and from the ventilator.•
Separate outside intake and exhaust vents by at least 6 ft (2m).•
NOTES: Do not locate the fresh air vent where it blows directly onto occupants or the thermostat.
Do not locate the fresh air intake close to known sources of pollutants such as automobile exhaust, a
dryer vent or chimney smoke.
Ducting the supply outlet and/or the exhaust inlet of the ventilator to the return air plenum of the air handler •
is an excellent way to distribute fresh air and exhaust stale air from all parts of the house, while reducing
installation costs. When choosing this method, balance the ventilator when the air handler is running and
interlock the ventilator so that it can run only when the air handler runs. See Fig. 6. An alternate method is to
balance the ventilator when the air handler is not running and let the ventilator run whether the air handler is
running or not, see Fig. 5. An independent installation is shown in Fig. 7.
NOTE: When the home is occupied, continuous operation of the ventilator is recommended. When the furnace air handler
operates, fresh air is distributed through the heating/air conditioning supply registers. When the air handler is off,
fresh air is delivered through both supplies and returns.
STARTED
GETTING
An electrical interlock or an automatically powered damper must be used to prevent unwanted entry of •
outside air if the ventilator is turned off while the furnace air handler continues to operate.
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
Direct connection of supply air stream to furnace cold air return for HRV/ERV.Fig. 5.
7
Loading...
+ 19 hidden pages