Honeywell He220, He260 Installation Instruction

Page 1
INSTALLATION INSTRUCTIONS
HE220, HE260 Humidifier

WELCOME

To the comfortable world of humidified air. When you use

APPLICATION

INSTALLATION

Preparing for the Installation

Required Accessories (Included)
Required Tools
your Honeywell humidifier, you notice that your skin is not as dry, and that your scratchy throat and irritated nasal passages that aggravate allergies and asthma are steadily improving.
You have also taken the first step in reducing the you create when you walk on your carpet and then touch your TV, computer, metal door knob or your pet. Your furniture and woodwork are also benefitting from the difference that humidified air makes.
Congratulations! You have just made a great investment in improving the comfort of your home.
This installation kit contains all the parts necessary to install your new Honeywell HE220 or HE260 Humidifier.
zapping
Be sure to identify all the required (Table 1) accessories (included) and make sure the appropriate tools are available before beginning the installation.
Table 1. Required Accessories.
Quantity Accessory
6 ft (1.85M) Bypass ducting including:
20 ft (6.2m) 18 gauge, two-strand thermostat wire
20 ft (6.2m) 1/4 in. (6.35 mm) OD feed water tubing
10 ft (3.1m) 1/2 in (12.7 mm) ID drain tubing
1 bag Connecting and mounting hardware:
1 Plug-in transformer
1 Sail switch
6 in. (155 mm) diameter flexible duct Starter collar Summer shut-off damper Duct tape
Wire nuts (4) No. 8 sheet metal screws (18) Drain tube clamps (2 sizes) Feed tube mounting clamps (6) Brass inserts (2) Plastic compression rings (2)
Tools required for installation include:
• Tin snip.
• Screwdriver.
• Adjustable or open-end wrench.
• Drill, punch or awl.
•Level.
® U.S. Registered Trademark Copyright © 2001 Honeywell • •All Rights Reserved
69- 1570
Page 2
HE220, HE260 HUMIDIFIER INSTALLATION KIT
Determining Best Location for Humidifier
Selecting Water Supply Location
Locating Closest Floor Drain
Selecting Location for Sail Switch
Selecting Location for Humidistat
Locating Closest 120V Electrical Outlet
INSTALLING HUMIDIFIER
• Select a location for the humidifier on the supply (warm air stream) or the return plenum. See Fig. 1.
• Select a location for the bypass on the opposite plenum. The sidewalls of the humidifier are interchangeable to allow bypass duct mounting on either side of the humidifier.
• Select a location that cannot damage the air conditioner A-coil during installation.
• Select a location where the 6 ft (1.86m) of 6 in. (155 mm) duct provided is adequate to connect the humidifier to the bypass. — Do not locate the humidifier or bypass on a fur-
nace body.
— Allow adequate clearance in front of and above
the humidifier so you can easily remove the cover to perform routine maintenance.
— Mount humidifier at least 3 in. (78 mm) above the
furnace body to allow adequate space for the solenoid valve and drain line.
— Mount humidifier in a conditioned space to pre-
vent freezing.
HORIZONTAL
HIGHBOY
DOWN
FLO
LOWBOY
M12248C
Fig. 1. Typical humidifier installation locations.
• Select a location for the sail switch in the cold air return duct where the sail is in the direct path of an unrestricted air stream. — Sail switch detects when furnace fan is operating.
• Select a location where the air duct is at least 12 in. (305 mm) deep and 8 in. (203 mm) wide to allow operation of the sail without affecting the smooth flow of air in the duct. — Airflow at the location can be vertical (up or
down) or horizontal.
IMPORTANT
Mounting the S688 in warm air supply duct can reduce the sail life.
Mount the switch at least 6 in. (152 mm) upstream from an elbow or junction, and at least 15 in. (381 mm) downstream from an elbow or junction. Locate the switch on the opposite side of the duct from the air entrance. (See Fig. 1-3 in S688 Installation Instructions.)
• Select a location for the humidistat on the return plenum or on the wall in the living space. — Mounting on the return plenum is the easiest
installation for the control wiring circuit. For return duct mounting, the humidistat should be mounted upstream from the humidifier or bypass so that it is properly sensing the relative humidity of the living space. Locate the control at least 8 in. (203 mm) upstream from the humidifier in the return air duct. (See Fig 2.)
ALTERNATE LOCATION
RETURN AIR
6 in. (152 mm) MINIMUM
BEST LOCATION
RETURN AIR DUCT
15 in. (381 mm) MINIMUM
RETURN AIR
M12831
• Use either hard or soft water in the humidifier and either hot or cold water. The water flow rate, with the humidifier running, is 3.5 gal/hr (13 liters/hr) to flush the pad and provide moisture for evaporation.
• Make sure that the 20 ft (6.2m) of feed water tubing provided is adequate to connect the water supply (saddle valve) with the humidifier solenoid valve.
• Select location with access to a floor drain to provide drainage for air conditioner condensation and humidifier drainage.
• If you do not have a drain available, we recommend that you install the Honeywell Whole House Drum or Disk Humidifier.
• Make sure that the 10 ft (3.1m) of drain tubing is adequate to reach from the humidifier drain connection to the floor drain.
69-1570 2
Fig. 2. Selecting duct location for humidistat.
• Select location with access to an outlet. If not available, contact an electrician to have one installed. Make sure that the 20 ft (6.2m) of thermostat wire is adequate to reach from the humidifier solenoid, to the sail switch, to the humidistat, to the plug-in transformer in the outlet.
WARNING
Hazardous Voltage. Can cause personal injury or equipment damage.
Do not cut or drill into any air conditioning or electrical accessory.
Page 3
HE220, HE260 HUMIDIFIER INSTALLATION KIT
CAUTION
Sharp Edges Installation Hazard. Can cause personal injury.
Wear gloves and safety glasses.
Turn off power to the air handing system at the cir-
1.
cuit breaker. Draw a level line on the plenum in the location
2.
chosen for the humidifier. (Leveling assures opti­mal humidifier performance.) Locate the template in the Humidifier Installation
3.
Instructions. Tape the template in position and trace around the
4.
template. Remove the template and carefully cut the rectan-
5.
gular opening. Disassemble the humidifier; remove the cover and
6.
take out the humidifier pad assembly. See Fig. 3.
NOTE: Sidewalls are interchangeable for either left or
right bypass installation. To change direction, remove the screws holding each sidewall, reverse sidewall locations, and reinstall the screws.
WATER FEED NOZZLE
HUMIDIFIER PAD ASSEMBLY
FRAME
HUMIDIFIER HOUSING
COVER
SIDEWALL
WATER FEED TUBE
SHEET METAL SCREWS (4)
LEVEL
DUCT
OPENING
TO AIR DUCT
PLASTIC TABS (2)
DRAIN TUBING
Fig. 4. Installing humidifier on duct.
Use the 6 in. (155 mm) starter collar as a template
9.
to mark the opening for the bypass. Carefully cut the opening for a 6 in.(155 mm)
10.
starter collar. See Fig. 5. Use a drill, punch or awl to start the cut in the middle of the circle. Cut in an outward spiral to assist in controlling the cut.
6 IN. ROUND TEMPLATE
STARTING HOLE
M20171
BY-PASS SIDEWALL
Fig. 3. Disassembling humidifier.
Make sure the humidifier housing is level, then
7.
position it in the opening so the plastic tabs are in place on the ing. Use pliers, as necessary, to flatten cut edges. See Fig. 4. Secure the humidifier housing to the opening at the
8.
top and bottom using sheet metal screws.
lower sheet metal edge
of the open-
M12304A
Fig. 5. Cutting bypass opening.
Assemble the summer shutoff damper into the
11.
starter collar. Verify that the damper rotates freely between the open and closed positions. Make sure handle will be accessible. Mark the damper closed position as summer and the open position as win­ter. See Fig. 6.
3 69-1570
M20172
Page 4
HE220, HE260 HUMIDIFIER INSTALLATION KIT

CONNECTING PLUMBING

M20175
SCREW DRIVER
WATER LINE
SUMMER
WINTER
M20173
Fig. 6. Installing the starter collar.
Remove liner to expose foam adhesive. Position
12.
starter collar over opening. Using sheet metal screws, connect starter collar to
13.
the duct and bypass duct from humidifier to starter collar. Be sure to secure the collar to the duct with sheet metal screws. See Fig. 7.
Use hot or cold water and either hard or softened water in the humidifier.
Shut off the water.
1.
CAUTION
Chemical Hazard. Can cause personal injury or equipment damage.
Do not use any line connected to an air conditioner. Do not use gas line.
Use the self-piercing saddle valve (included) to tap
2.
into the water supply line at the location selected. See Fig. 8. If tapping into galvanized pipe, drain line and pre-drill 3/16 in. tap for saddle valve.
NOTE: The saddle valve is not designed to regulate
water flow. The valve is either open or closed.
IMPORTANT
To prevent debris from clogging the solenoid in­line filter, be sure to install the saddle valve han­dle pointing toward the ceiling.
M20174
Fig. 7. Connecting bypass ducting.
IMPORTANT
To avoid sagging and stress on humidifier, add support if ducting is longer than 4 ft (1.25m).
Seal the duct connections with duct tape.
14.
Reinstall the humidifier pad assembly in the humid-
15.
ifier housing.
IMPORTANT
Be sure to reconnect the water feed tube and ensure that the tube is not pinched or kinked.
Hinge the cover in place and secure with the
16.
thumbscrew located at the bottom of the cover.
69-1570 4
Fig. 8. Installing saddle valve.
Use 1/4 in. (6 mm) OD tubing and connect saddle
3.
valve to inlet side of the solenoid valve (see Fig. 9). a. Place brass compression nut over tubing. b. Install brass insert into end of tubing. c. Slide the plastic compression ring over the
tubing. (Discard copper compression ring pro­vided with valve.)
NOTE: To prevent leaking, use plastic (Delrin) sleeve
rings with plastic tubing. Use copper sleeve rings only with copper tubing.
d. Insert the tubing into the solenoid valve fitting
and support the valve while tightening the com­pression nut.
NOTE: Do not over-tighten the compression nut. Mod-
erate tightness prevents leaking.
e. Repeat steps a. through d. for saddle valve fit-
ting.
f. Secure tubing with clamps provided.
Page 5

Installing Sail Switch

Adapting Switch to Air Flow Direction
BRASS COMPRESSION NUT
PLASTIC COMPRESSION RING
BRASS INSERT
M20176
Fig. 9. Installing feed tubing.
Connect a 1/2 in. (13 mm) drain tube to the humid-
4.
ifier drain fitting and run to the floor drain (see Fig.
10). a. Slide the drain clamp over the tubing. b. Push the tubing over the drain nipple on the
humidifier.
c. Hand-tighten the clamp around the tubing to
secure the humidifier drain.
d. Fasten the drain tubing (can use duct tape)
along the route to prevent movement and ensure downward slope for correct drainage.
NOTE: Cut tubing to correct length so the tubing termi-
nates at the drain.
HE220, HE260 HUMIDIFIER INSTALLATION KIT
IMPORTANT:
Do not use the sail switch with both springs attached. Be sure to select air flow direction and remove spring(s) not required for installation.
UP
M3014
Fig. 11. Adapting sail switch to air flow direction or
Vertical
place that is attached to the bracket marked Down. Remove the spring that is attached to the bracket marked Up.
Vertical
that is attached to the bracket marked Up. Remove the spring that is attached to the bracket marked Down.
Horizontal air flow:
mounting position.
downward
upward
air flow:
Leave the spring in
air flow:
Leave the spring in place
Remove both springs.
M20177
Fig. 10. Installing drain tubing.
The S688A Sail Switch is provided with two counterbalancing springs in place as shown in Fig 11. These springs offset the effect of gravity for air flow direction.
Mount the template (provided with the sail switch)
1.
at the desired location.
NOTE: Be sure the arrow (indicating air flow) points in
the correct direction.
a. For horizontal mounting,
sion shown on the template.
b. For vertical mounting,
sion.
Cut the hole indicated on the template in the duct-
2.
work. Center punch the screw holes indicated and drill
3.
out with a 1/8 in. (13 mm) drill. Attach the sail to the switch as shown in Fig 12.
4.
5 69-1570
level
plumb
the long dimen-
the long dimen-
Page 6
HE220, HE260 HUMIDIFIER INSTALLATION KIT

INSTALLING HUMIDISTAT

Mounting Duct

WIRING

– LOOSEN SETSCREW – INSERT SAIL – TIGHTEN SETSCREW
SAIL
M20181
Position the base on the duct with the arrow up.
5.
Secure the base to the duct using the four
6.
1 in. (25 mm) mounting screws provided with humi­distat. Connect the low-voltage wires to the leads and
7.
replace the H8908 case. See Fig. 14.
NOTE: For wall mounting instructions, see the H8908
Installation Instructions.
HUMIDISTAT BASE REAR OF HUMIDISTAT
Fig. 12. Attaching sail to switch.
Press together the sides of the wire loop. Insert the
5.
sail into the duct. (When in the Off position, the sail should point into the direction of airflow as shown in Fig.13.)
AIRFLOW
M20178
Fig. 13. Inserting sail switch in direction of airflow.
Secure the switch by using the sheet metal screws
6.
provided. After wiring, snap on the cover.
7.
Apply the template to the duct location chosen for
1.
the humidistat. Make sure the template is level before drilling the holes. Refer to the template (provided with the H8909
2.
Humidistat Installation Instructions) to drill the con­trol assembly opening and mounting holes for the H8908. Remove the H8908 case from the base.
3.
Position the foam gasket on the H8908 base.
4.
WIRE SLOT
HUMIDISTAT WIRES
M20179
Fig. 14. Humidistat base and rear view.
CAUTION
Hazardous Voltage. Can cause personal injury or equipment damage.
Disconnect power supply before installing or servicing equipment.
IMPORTANT
All wiring must comply with applicable local code, ordinances and regulations.
Wire the humidifier solenoid valve, sail switch, humidistat and transformer.See Fig. 15
HUMIDISTAT
Y T
I D
I M U
H R O
O D T U
O
G N
I T T E S
E R U
T A R E P
M E T
% 5
1 C
¡
0 3
­F
¡ 0 2
-
% 0
2 C
¡
5 2
­F
¡ 0 1
-
% 5
2 C
¡
0 2
­F
¡ 0
% 0 3
C
¡ 0 1
­F
¡ 0 1 +
% 5 3
C
¡ 5
­F
¡
l
0 2
o
+
r t
n o C
y t
i d
i m
u H
% 0 4
C
¡ 0 r e v
O F
¡ 0 2 r
e v O
é t
i d
i m
u h
' d r
u e
t a
l u
g é R
WHITE
SAIL
SWITCH
M20180
TRANSFORMER
HUMIDIFIER
SOLENOID
VALVE
BLACK
BLACK
Fig. 15. Wiring the controls.
BLACK
WHITE
69-1570 6
Page 7
Run the two-strand thermostat wire from the

TESTING HUMIDIFIER OPERATION

Checklist

1.
humidifier to the transformer, from the transformer to the humidistat, and from the humidistat to the sail switch. Cut lengths of thermostat wire to reach between
2.
components, leaving adequate wire at both ends for connections.
NOTE: Transformer, humidistat and sail switch can be
wired in any order.
At the humidifier, connect the black and white con-
3.
ductors to the two black humidifer wires. At the transformer, connect both black conductors
4.
to the two transformer terminals. Use a wire nut to connect together the two white conductors. At the humidistat, connect both black conductors to
5.
the two humidistat terminals. Use a wire nut to con­nect together the two white conductors. At the sail switch, connect the black and white con-
6.
ductors to the Com and NO sail switch terminals (NC terminal is not used).
HE220, HE260 HUMIDIFIER INSTALLATION KIT
Humidifier is level.
Starter collar is secured with sheet metal screws.
Summer shut-off damper is open (in winter position).
Control wiring was reviewed using circuit diagram.
Transformer is plugged in.
Feed line has no kinks.
Drain line slopes continuously down and ends at floor
drain. Water hose inside humidifier is connected to
PerfectFlow™ water distribution tray.
After installation use the following steps to check the humidifier operation:
Turn on the power and the water supply
1.
Turn the H8908 Humidity Control to On and turn on
2.
the heat by setting the thermostat to 10ºF (6ºC) above room temperature.
IMPORTANT
The furnace blower must be on in to activate the humidifier.
Make sure that water is flowing out of the drain
3.
hose. If water does not flow, see Troubleshooting Your Humidifier section. Check for leaks.
4.
Reset the thermostat and H8908 Humidity Control
5.
to a comfortable setting for automatic operation.
7 69-1570
Page 8
HE220, HE260 HUMIDIFIER INSTALLATION KIT

TROUBLESHOOTING YOUR HUMIDIFIER (TABLE 2)

Table 2. Troubleshooting Humidifier.
Problem What to look for What to do
Water leakage Leaking joints Shut off water.
Tighten connections.
Brass tubing inserts Verify that brass tubing inserts are used.
Saddle valve leaking Verify rubber pad is installed on saddle valve.
No water to drain.
Electrical
Humidistat Turn humidistat up and down and listen for contact to
Verify control circuit wiring. Check all connections.
click.
Transformer Verify that outlet has power.
Sail switch Remove sail cover; turn on furnace fan and listen for
Solenoid After verifying other wiring components, turn on
Plumbing
Saddle valve Verify that needle pierced water line and then back
Humidifier Remove cover and verify that water flows into
faint click. Verify that sail can move freely in duct; check sail switch instructions to trim sail, if necessary.
furnace fan, turn humidistat up and down, and listen for solenoid to click.
Verify plumbing connections. Check for kinks.
out needle to open valve.
distribution tray.
Drain tubing Verify no obstructions.
Air leakage Check duct joints Seal with duct tape.
Home and Building Control Home and Building Control
Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
69-1570 G.H. 09-01 www.honeywell.com/yourhome
M1V 4Z9
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...