AAAAAAAA MODEL CODE
B FACTORY:
T FOR TAOYUAN,
W FOR WUJIANG
C LAST DIGIT OF YEAR
DD WEEK: FROM 1 52
EEEE WEEKLY QUANTITY:
BEGIN EACH WEEK WITH “0001”
DATE CODE YYWW
YY LAST 2 DIGITS OF YEAR
WW 2 DIGIT WEEK
ENCLOSURE TYPE
DESCRIPTION
CERTIFICATIONS
HONEYWELL SERIAL
COUNTRY OF ORIGIN
Receiving and Inspection
After receiving the VFD, please check for the following:
1. Please inspect the unit after unpacking to assure it was not damaged during shipment.
2. Make sure that the part number printed on the package corresponds with the part number indicated on the nameplate
3. Make sure that the voltage for the wiring lie within the range as indicated on the nameplate.
4. Please install the VFD according to this manual.
5. Before applying the power, please make sure that all the devices, including power, motor, control board and digital keypad,
are connected correctly.
6. When wiring the VFD, please make sure that the wiring of input terminals “R/L1, S/L2, T/L3” and output terminals “U/T1, F/
T2, W/T3” are correct to prevent drive damage.
7. When power is applied, select the language and set the parameter groups via the digital keypad.
8. After applying the power, please trial run with the low speed and then increase the speed gradually to the desired speed.
Nameplate Information
Model Name
63-4528—042
NOMINAL HORSEPOWER
0007 0.75 HORSE POWER
0010 1 HORSE POWER
0100 10 HORSE POWER
Fig. 1. Nameplate Information.
HCRD A 0100 A 1 000T
PRODUCT FAMILY
HCRD CORE DRIVE
HCRB CORE BYPASS
NOMINAL VOLTAGE
A 208/230 VAC DRIVE ALONE,
208 VAC BYPASS
B 230 VAC BYPASS
C 480 VAC
D 575 VAC
Fig. 2. Model Name.
OPTIONS
000T DRIVE ONLY WITH
TEXT DISPLAY
3000T DRIVE WITH BYPASS
3 CONTRACTOR
ENCLOSURE TYPE
1 NEMA 1
2 NEMA 12
3 NEMA 3R
FRAME SIZE
A, B, C, D, E -- SEE
DIMENSIONAL TABLE
M33232
Product Serial Number
CHAPTER 1: INTRODUCTION
XXXXXXXXXXXXXXXX
MODEL
CODE
FACTORY
T: TAOYUAN
W: WUJIANG
YEAR
LAST NUMBER
OF THE YEAR
0:2010
Fig. 3. Product Serial Number.
Table 1. Dimensions for Frames A, B, C in mm [inch].
208/230Vac460VacHP Weight
HCRDA0010A1000T HCRDC0010A1000T12.8A130
HCRDA0020A1000T HCRDC0020A1000T22.8
HCRDA0030A1000T HCRDC0030A1000T32.8
HCRDA0050A1000T HCRDC0050A1000T52.8
HCRDA0075A1000T HCRDC0075A1000T 7.52.8
HCRDA0100A1000T 102.8
HCRDA0100B1000T
HCRDA0150B1000T HCRDC0150B1000T 154.6
HCRDA0200B1000T HCRDC0200B1000T 205.6
HCRDC0250B1000T 25
HCRDA0250C1000T2510.5C250
HCRDA0300C1000T HCRDC0300C1000T 30 10.5/8.7
HCRDA0400C1000T HCRDC0400C1000T 40 10.5/8.7
HCRDC0500C1000T 509.4
D1*: Flange mounting Unit: mm [inch]
104.6B190
FrameWHDW1H1
(kg.)
[5.12]
[7.48]
[9.84]
WEEK NO.
01-52
250
[9.84]
320
[12.60]
400
[15.75]
170
[6.69]
190
[7.48]
210
[8.27]
QUANTITY
QUANTITY OF
ONE WEEK
116
173
231
236
[9.29]
303
[11.93]
381
[15.00]
[4.57]
[6.81]
[9.09]
M33233
D1*S1
45.8
[1.80]
77.9
[3.07]
92.9
[3.66]
6.2
[.24]
8.5
[0.33]
8.5
[0.33]
φ1φ2φ3
22.2
34
[.87]
[1.34]
22.2
22.2
34
[1.34]
34
[1.34]
[0.87]
[0.87]
28
[1.1]
28
[1.10]
50
[1.97]
363-4528—04
CHAPTER 1: INTRODUCTION
SEE DETAIL A
DETAIL A (MOUNTING HOLE)
DETAIL B (MOUNTING HOLE)
SEE DETAIL B
D
D1
W1
W
H1
H
S1
S1
2
3
1
1
3
M31495
CORE
SEE DETAIL B
CORE
FRAME A
Fig. 4. Frame A: Units in mm (inches). See also Table 1.
63-4528—044
FRAME B
M31496
SEE DETAIL A
SEE DETAIL B
DETAIL A (MOUNTING HOLE)
DETAIL B (MOUNTING HOLE)
S1
S1
D
D1
W
W1
H1
H
1
1
3
3
1
2
CORE
CORE
CHAPTER 1: INTRODUCTION
Fig. 5. Frame B: Units in mm (inches). See also Table 1.
563-4528—04
CHAPTER 1: INTRODUCTION
M31497
SEE DETAIL A
SEE DETAIL B
DETAIL A (MOUNTING HOLE)
DETAIL B (MOUNTING HOLE)
S1
S1
W1
W
D1
D
H1
H
1
3
2
1
1
1
3
CORE
ORE
FRAME C
208/230Vac460VacHP Weight
HCRDA0500D1000T
HCRDA0600D1000T HCRDC0600D1000T 6035.5
HCRDC0750D1000T 7535.5
HCRDC1000D1000T 100 35.5/
HCRDC1250D1000T 125 35.5/
HCRDA0750E1000T
HCRDA1000E1000T
HCRDA1250E1000T
*D1 Flange mounting
Fig. 6. Frame C: Units in mm (inches). See also Table 1.
Table 2.
50 35.5D330
75 45.7
100 46.2
125 54.7
Dimensions for Frames D and Ein mm [inches].
Frame WHDW1H1H2H3D1*D2S1S2
(Kg.)
40.5
40.5
E370
[12.99]
[14.57]
[27.10]
[28.18]
688.3
715.8
275
[10.83]
300
[11.81]
285
[11.22]
335
[13.19
550
[21.65]
589
[23.19]
525
[20.67]
560
[22.05]
492
[19.37]
528
[20.80]
107.2
[4.22]
143
[5.63]
16
[0.63]
18
[0.71]
11
[0.43]
13
[0.51]
18
[0.71]
18
[0.71]
φ1φ2φ3
76.2
34
[3.00]
[1.34]
22
34
[0.87]
[1.34]
22
[0.87]
92
[3.62]
63-4528—046
FRAME D
SEE DETAIL A
SEE DETAIL B
W1
W
D1
D
H1
H
DETAIL B
(MOUNTING HOLE)
DETAIL A
(MOUNTING HOLE)
S1
S1
1
1
3
3
2
2
M31498
CORE
ORE
CHAPTER 1: INTRODUCTION
Fig. 7. Frame D: Units in mm (inches). See also Table 2.
763-4528—04
CHAPTER 1: INTRODUCTION
SEE DETAIL A
SEE DETAIL B
DETAIL B
(MOUNTING HOLE)
DETAIL A
(MOUNTING HOLE)
S3
D2
S1
S2
D1
D
W1
W
H1
H2
H3
H
M31499
1
1
2
2
2
2
3
3
CORE
COR
FRAME E
Fig. 8. Frame E: Units in mm (inches). See also Table 2.
63-4528—048
Fig. 9. Keypad Dimensions in mm (inches).
VFD-Cx
F1F2
F3
F4
ESC
MENU
AUTO
HAND
STOP
RESET
FWD
REV
FWD
ENTER
ERR
COMM
RUN
RUN
M33223
72 (2-53/64)
116
(4-9/16)
15
(19/32)
CHAPTER 1: INTRODUCTION
963-4528—04
CHAPTER 1: INTRODUCTION
63-4528—0410
CHAPTER 2: INSTALLATION
AA
A
A
A
A
B
B
A
A
B
A
A
C
A
A
B
A
A
D
A
A
B
A
A
2B
A
A
B
A
A
D
A
A
B
A
A
A
A
D
B
B
A
A
B
A
D
Ta *
B
A
A
C
B
B
A
A
C
B
50 mm
Ta
50 mm
Ta
50 mm
Ta
50 mm
Ta
A
A
D
Ta *
A
FRAME A, B, C
MULTIPLE DRIVES: INDEPENDENT
INSTALLATION IN HORIZONTAL
FRAME D, E
MULTIPLE DRIVES: INDEPENDENT
INSTALLATION IN HORIZONTAL
INSTALL A BARRIER BETWEEN THE
DRIVES
FRAME A, B, C
MULTIPLE DRIVES: INDEPENDENT
INSTALLATION
TA: FRAME A~E
IT IS SUGGESTED TO INSTALL A
BARRIER BETWEEN THE DRIVES.
ADJUST THE SIZE OF THE BARRIER TILL
THE TEMPERATURE OF THE FAN ON THE
INFLOW SIDE IS LOWER THAN THE
OPERATION TEMPERATURE.
(REFER TO THE RIGHT FIGURE)
OPERATION TEMPERATURE IS THE
TEMPERATURE MEASURED 50MM AWAY
FROM THE INFLOW SIDE OF THE FAN.
MINIMUM MOUNTING CLEARANCE
FRAME
A~C
A (mm/in) B (mm/in) C (mm/in)
D (mm/in)
D~E
60/1.2
100/3.3
30/0.6
50/1.7
10/0.2
0
0
A
B
B
A
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTERNVERTER
NVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
NOTE:
THE MOUNTING CLEARANCES SHOWN IN THE LEFT FIGURE ARE NOT FOR INSTALLING THE DRIVE IN A
CONFINED SPACE (SUCH AS CABINET OR ELECTRIC BOX). WHEN INSTALLING IN A CONFINED SPACE,
BESIDES THESE SAME MINIMUM MOUNTING CLEARANCES, IT NEEDS TO HAVE THE VENTILATION
EQUIPMENT OR AIR CONDITIONER TO KEEP THE SURROUNDING TEMPERATURE LOWER THAN THE
OPERATION TEMPERATURE.
THE FOLLOWING TABLE SHOWS HEAT DISSIPATION AND THE REQUIRED AIR VOLUME WHEN INSTALLING
A SINGLE DRIVE IN A CONFINED SPACE. WHEN INSTALLING MULTIPLE DRIVES, THE REQUIRED AIR
VOLUME SHALL BE MULTIPLIED BY THE NUMBER OF DRIVES.
REFER TO THE CHART (AIR FLOW RATE FOR COOLING) FOR VENTILATION EQUIPMENT DESIGN AND
SELECTION.
REFER TO THE CHART (POWER DISSIPATION) FOR AIR CONDITIONER DESIGN AND SELECTION.
IT IS THE MINIMUM DISTANCE REQUIRED FOR FRAME A~D. IF DRIVES ARE INSTALLED CLOSER THAN
THE MINIMUM MOUNTING CLEARANCE, THE FAN MAY NOT FUNCTION PROPERLY.
(BLUE ARROW) INFLOW
(FRAME A-E)
SINGLE DRIVE: INDEPENDENT INSTALLATION
(RED ARROW) OUTFLOW
(FRAME A-C)
PARALLEL MOUNTING IN HORIZONTAL
M31500A
The appearances shown in the following figures are for reference only.
The required airflow shown in chart is for installing single drive in a confined space.
When installing the multiple drives, the required air volume should be the required air volume for single drive multiplied by the
number of the drives.
Heat dissipation for each model is calculated by rated voltage, current and default carrier at full load, full speed, and maximum
ambient temperature
1363-4528—04
CHAPTER 2: INSTALLATION
63-4528—0414
CHAPTER 3: UNPACKING
M33234
M33235
M33236
M33237
The VFD should be kept in the shipping carton or crate before installation. In order to retain the warranty coverage, the VFD should
be stored properly when it is not to be used for an extended period of time.
The frame size D and size E VFDs are packed in crates. Follow the instructions below for unpacking.
Frame D
Crate (HCRDXXXXXD1000T)
1. Loosen all the screws on the four iron plates at the four
bottom corners of the crate. Four screws are on each of
the iron plates.
3. Loosen the 10 screws on the pallet, then remove the
wooden plate.
2. Remove the crate cover, EPEs, rubber and manual.
4. Lift the drive by hooking the lifting holes. It is now ready
for installation.
1563-4528-04
CHAPTER 3: UNPACKING
M33239
Using the lifting hook
1. The arrows show the position of lifting holes.2. Make sure the lifting hook properly goes through the
lifting hole, as shown on the far right below.
3. Ensure that the angle between the lifting holes and lifting
device is within the specification as shown below.
M33228
63-4528-0416
Frame E
M33234
M33241
M33242
M33243
Crate (HCRDXXXXXD1000T)
CHAPTER 3: UNPACKING
1. Loosen all the screws on the four iron plates at the four
bottom corners of the crate. Four screws are on each of
the iron plates.
2. Remove the crate cover, EPEs, rubber and manual.
3. Loosen the 10 screws on the pallet, then remove the
wooden plate.
4. Lift the drive by hooking the lifting holes. It is now ready
for installation.
1763-4528-04
CHAPTER 3: UNPACKING
M33245
E
M33239
Using the lifting hook
1. The arrows show the position of lifting holes.2. Make sure the lifting hook properly goes through the
lifting hole, as shown on the far right below.
3. Ensure that the angle between the lifting hole and lifting
device is within the specification as shown below.
63-4528-0418
CHAPTER 4: WIRING
R(L1)
S(L2)
T(L3)
FWD
R(L1)
S(L2)
T(L3)
NFB
U(T1)
V(T2)
W(T3)
MOTOR
JUMPER
DC CHOKE
(OPTIONAL)
BREAKING RESISTOR
(OPTIONAL)
IM
3~
REV
MI1
FWD/STOP
REV/STOP
3 PHASE POWER IS PROVIDED
FUSE/NO FUSE BREAKER
FACTORY SETTING:
PNP SOURCE
PRESET SPD 1
PRESET SPD 2
PRESET SPD3
PRESET SPD 4
EXT F
A
ULT
FAULT RESET
NA
NA
MI3
MI2
MI4
MI5
MI6
MI7
MI8
MULTI FUNCTION
OUTPUT TERMINALS
RA1
RB1
RC1
RA2
RC2
RA3
RC3
250VAC/6A
30VDC/6A
30VDC/5A
MULTI FUNCTION OUTPUT
FREQUENCY TERMINALS
250VAC/5A
MULTI FUNCTION OUTPUT
FREQUENCY TERMINALS
250VAC/5A
30VDC/5A
DCM
SCM
S1
DIGITAL SIGNAL COMMON TERMINAL WHILE
USING INTERNAL POWER TO RUN SINK MODE
FACTORY
SETTING
POWER REMOVAL SAFETY FUNCTION
FOR EMERGENCY STOP
DIGITAL SIGNAL COMMON TERMINAL
+10V/20mA
0~10V/0~20mA
0 20mA/0~10V
ANALOG SIGNAL
COMMON TERMINAL
3
2
1
5KΩ
MAIN CIRCUIT (POWER)
TERMINALS
CONTROL
TERMINALS
SHIELDED
LEADS &
CABLES
+10V
AVI1
ACI
AVI2
ACM
AFM1
ACM
AFM2
ANALOG MULTI-FUNCTION
OUTPUT TERMINAL
0~10V/0~20mA
ANALOG SIGNAL
COMMON TERMINAL
ANALOG MULTI-FUNCTION
OUTPUT TERMINAL
0~10V/0~20mA
MI: MULTIFUNCTION INPUT
AVI: ANALOGUE VOLTAGE INPUT
ACI: ANALOGUE CURRENT INPUT
+24V
63-4528—0420
Fig. 2. Wiring Diagram for Frames D and E.
CHAPTER 4: WIRING
M33246
DCM
COM
M1
M2
M8
+24V
+24V
+24V
+24V
DCM
COM
INTER NAL CIRCUIT
INTER NAL CIRCUIT
INTER NAL CIRCUIT
INTER NAL CIRCUIT
DCM
COM
SINK MODE
WITH EXTERNAL POWER
SOURCE MODE
WITH EXTERNAL POWER
SINK MODE
WITH INTERNAL POWER
(+24 VD C)
SOURCE MODE
WITH INTERNAL POWER
(+24 VD C)
EXTERNAL POWER +24V
EXTERNAL POWER +24V
DCM
COM
2
M1
M2
M8
M1
M2
M8
M1
M2
M8
4
3
1
M33247
Fig. 3. Sink (NPN)/Source (PNP) Mode.
Option number 2 Source Mode is most frequently used for Honeywell VFDs.
Fig. 4. Frame E, remove terminal r and terminal s before using DC-Link.
(As circled in dotted line, uninstall the gray section and properly store cable r and cable s.
Cable r and cable s are not available in optional accessories; do not throw them away.)
2163-4528—04
CHAPTER 4: WIRING
63-4528—0422
CHAPTER 5: MAIN CIRCUIT TERMINAL
U(T1)
V(T2)
W(T3)
MOTOR
IM
3~
3-PHASE POWER IS PROVIDED
R(L1)
S(L2)
T(L3)
R(L1)
S(L2)
T(L3)
NFB
FUSE/NO FUSE BREAKER
+1/DC+
-/DC+
M33249
U(T1)
V(T2)
W(T3)
MOTOR
IM
3~
3-PHASE POWER IS PROVIDED
R(L1)
S(L2)
T(L3)
R(L1)
S(L2)
T(L3)
NFB
FUSE/NO FUSE BREAKER
+1/DC+
-/DC+
r
s
R
S
M33250
3-PHASE POWER IS PROVIDED
JUMPER
FUSE/NO FUSE BREAKER
NFB
R(L1)
S(L2)
T(L3)
DC CHOKE
(OPTIONAL)
R(L1)
S(L2)
T(L3)
BREAKING RESISTOR
(OPTIONAL)
U(T1)
V(T2)
W(T3)
Fig. 1. Main Circuit Terminal of Frame A~C.
Fig. 2. Main Circuit Terminal of Frame D.
MOTOR
IM
3~
M33248
R/L1, S/L2, T/L3AC line input terminals 3-phase
U/T1, V/T2, W/T3VFD output terminals for connecting 3-phase induction motor
Fig. 3. Main Circuit Terminal of Frame E.
Table 1. Control Connections
TerminalsDescriptions
+1, +2
Applicable to frame A~C
Connections for DC reactor to improve the power factor. One needs to remove the jumper for installation.
Applicable to frame D~E
Connections for brake unit
+1/DC+, -/DC-
(for 230V models: 22kW, built-in brake unit)
(for 460V models: 30kW, built-in brake unit)
Common DC Bus
When connecting DC+ and DC-, please follow the required wired gauge in Honeywell VFD CORE user
manual.
2363-4528-04
CHAPTER 5: MAIN CIRCUIT TERMINAL
BRAKE RESISTOR
(OPTIONAL)
M33252
B1
B2
+
–
BRAKE RESISTOR
(OPTIONAL)
BRAKE UNIT
(OPTIONAL)
BR
B1, B2Connections for brake resistor (optional)
Grounding connection, please comply with local regulations.
Main power terminals
• Do not connect 3-phase model to one-phase power. It is unnecessary to consider phase-sequence
for these terminals R/L1, S/L2 and T/L3.
• It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off power
quickly and reduce malfunction when activating the protection function of the VFD. Both ends of the
MC should have an R-C surge absorber.
• Securely fasten the main circuit terminals to prevent sparks which can be made by the loose screws
due to vibration.
• Use voltage and current within the specification.
• When using a general GFCI (Ground Fault Circuit Interrupter), select a current sensor with
sensitivity of 200mA or above and not less than 0.1-second operation time to avoid nuisance
tripping.
• Use shield wire or tube for the power wiring and ground the two ends of the shield wire or tube.
• Do NOT stop the VFD by cutting the power. Stop the VFD using RUN/STOP command via control
terminals or keypad. If you must stop the VFD by turning the power OFF. Do not do so more than
once per hour.
Table 1. Control Connections
Output terminals for main circuit
• When installing a load filter at the output side of terminals U/T1, V/T2, W/T3 of the VFD, please use
inductance filter. Do not use phase-compensation capacitors or L-C (Inductance-Capacitance) or RC (Resistance-Capacitance), unless approved by Honeywell.
• DO NOT connect phase-compensation capacitors or surge absorbers at the output terminals of the
VFD.
• Recommended using an inverter duty-rated motor.
Terminals for connecting DC reactor, external brake resistor, external brake resistor and DC
circuit
• These are the terminals used to connect the DC reactor to improve the power factor. For the factory
setting, it connects the short-circuit object. Please remove this short-circuit object before connecting
to the DC reactor.
DC REACTOR (OPTIONAL)
+1
+2
M33251
• Connect a brake resistor or brake unit in applications with frequent deceleration ramps, short
deceleration time, insufficient brake torque or requiring increased brake torque.
• The external brake resistor should connect to the terminals (B1, B2) of the VFD.
• For those models without built-in brake resistor, connect external brake unit and brake resistor (both
of them are optional) to increase brake torque.
• When the terminals +1, +2 and - are not used, leave the terminals open.
• DO NOT connect [+1, -], [+2, -], [+1/DC+, -/DC-] or brake resistor directly to prevent drive damage.
(B) 8kg-cm [6.94Ib-in.] (0.78Nm) (As shown in Fig. 1 above)
Wiring precautions:
• Reserve a bare wire strip of 5mm and properly install the wire into the terminal; tighten the installation with a slotted
screwdriver. If the wire is stripped, sort the wire before installation into the terminal.
• Use a flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
• In the Fig. 1 above, the factory setting for S1-SCM is short circuit. The factory setting for +24V-COM is short circuit and SINK
mode (NPN); please refer to Chapter 4 Wiring for more detail.
+24VDigital control signal common (Source)+24V±5% 200mA
COMDigital control signal common (Sink)Common for multi-function input terminals
FWD-DCM:
FWDForward-Stop command
REVReverse-Stop command
MI1
~
MI8
DCMDigital frequency signal common
Multi-function input 1~8
ON Æ forward running
OFF Æ deceleration to stop
REV-DCM:
ON Æ reverse running
OFF Æ deceleration to stop
Refer to parameters 02-01~02-08 to program the multi-function inputs
MI1~MI8.
ON: the activation current is 6.5mA 11Vdc
OFF: leakage current tolerance is 10μA 11Vdc
NOTE: Wire size of analog control signals: 18 AWG (0.75 mm2) with shielded wire
Analog input terminals (AVI 1, ACI, AVI 2, ACM)
• Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible [less than 20
meters (65.6168 feet)] with proper grounding. If the noise is inductive, connecting the shield to terminal ACM can bring
improvement.
• This way of using contacts in a circuit should be able to process weak signals at the bifurcated contacts. Do not use contacts
to control the terminal ACM.
• If the analog input signals are affected by noise from the VFD, connect a capacitor and ferrite core as indicated in the following
diagram.
AVI1/ACI/AVI2
C
ACM
FERRITE CORE
M33266
NOTE: The value of the capacitor is 0.1~0.01uF; if there is no noise issue, the capacitor is not necessary.
Digital inputs (FWD, REV, MI1~MI8, COM)
• When using contacts or switches to control the digital inputs, use high quality components to avoid contact bounce.
Remove the Terminal Block
1. Loosen the screws using a screwdriver (see figure below).
M33267
63-4528—0432
CHAPTER 6: CONTROL CIRCUIT TERMINAL
M33268
2. Remove the control board by pulling it out for a distance 6~8 cm (see 1 in the figure below) then lift the control board
upward (see 2 in the figure below).
3363-4528—04
CHAPTER 6: CONTROL CIRCUIT TERMINAL
63-4528—0434
CHAPTER 7: OPTIONAL COMPONENTS
The components listed in this chapter are optional (not built-in) and available for purchase. Installing additional components to
your drive would substantially improve its performance. Please select applicable components according to your need and contact
Honeywell local distributors or Honeywell customer services for product availability.
List of Optional Components:
• All Brake Resistors and Brake Units Used in VFD
• Non-fuse Circuit Breaker
• Fuse (Specification Chart)
• Digital Keypad
• Panel Mounting Kit
• Conduit Box Kit
• Fan Kit
• Flange Mounting Kit
• IFD6530: USB/RS-485 Communication Interface
3563-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
Brake Resistors and Brake Units Used in VFDs
Table 1. 230V & 460V
Applicable
Motors
Braking
HPkW
10.75 0.5
21.5 0.5
32.2 1.0
53.7 1.5
7.55.52.5
107.53.7
15115.1
20157.5
251810.2
302212.2
403014.9
503720.320152
604525.120222
755530.520222
1007537.220223
1259050.820224
10.75 0.5
21.5 0.5
32.2 1.0
53.7 1.5
54 2.5
7.55.52.7
107.53.7
15115.1
20157.5
251810.2
302212.2
403014.9
503720.3
Tor que
(kg-m)***
Brake Unit
VFDB Unit
10% ED
Resistor
Value Spec.
for Each
VFD
80W 200Ω
80W 200Ω
200W 91Ω
300W 70Ω
400W 40Ω
1000W 20Ω
1000W 20Ω
1500W 13Ω
2000W 8.6Ω
2000W 8.6Ω
3000W 6.6Ω
4000W 5.1Ω
4800W 3.9Ω
6000W 3.3Ω
7200W 2.6Ω
9600W 2Ω
80W 750Ω
80W 750Ω
200W 360Ω
300W 250Ω
400W 150Ω
1000W 75Ω
1000W 75Ω
1000W 75Ω
1500W 43Ω
2000W 32Ω
2000W 32Ω
3000W 26Ω
4000W 16Ω
*
Braking Resistor Series for
Each Brake Unit
Part #****
BR080W20011.963.362.3
BR080W20011.963.362.3
BR200W09114.247.583.0
BR300W07015.438.0103.8
BR400W04019.519.0207.6
BR1K0W02011914.6269.9
BR1K0W02011914.6269.9
BR1K5W01312913.62810.6
BR1K0W4P322 series448.34617.5
BR1K0W4P322 series448.34617.5
BR1K5W3P322 series585.86625.1
BR1K0W5P122 series754.88030.4
BR1K2W3P922 series973.212045.6
BR1K5W3P322 series1183.212045.6
BR1K2W3P922 series1452.118068.4
BR1K2W3P922 series1901.624091.2
BR080W75011190 4 3
BR080W7501119043
BR200W36012.1126.764.6
BR300W25013108.675.3
BR400W15015.184.496.8
BR1K0W075110.254.31410.6
BR1K0W075110.254.31410.6
BR1K0W075110.247.51612.2
BR1K5W043117.642.21813.7
BR1K0W01622 series2426.22922
BR1K0W01622 series24233325.1
BR1K5W01322 series29233325.1
BR1K0W0164
Unit Connection
230V
460V
2 parallel,
2 series
Max. Braking Torque**
Tota l
Braking
Current
47.514.15441
Min.
Resistor
Val ue (Ω)
Max. Total
Braking
Current (A)
Peak
Power
(kW)
63-4528—0436
CHAPTER 7: OPTIONAL COMPONENTS
CYCLE TIME
BRAKE TIME
T
100%
T0
ED% T1/T0 X 100
M33296
Table 1. 230V & 460V
Applicable
10% ED
*
Max. Braking Torque**
Motors
Resistor
Value Spec.
for Each
VFD
4800W 15Ω
6000W 13Ω
8000W 10.2Ω
9600W 7.5Ω
HPkW
Braking
Tor que
(kg-m)***
Brake Unit
VFDB Unit
604525.140451
755530.540451
1007537.240302
1259050.840452
*
The longest operation time for 10% ED is 10 sec. (on: 10 sec.; off: 90 sec.)
**
See Brake Performance Curve below for the relation between Running Time, ED(%) vs Braking Current.
***
The calculation of the maximum braking torque is based on a 4-pole motor (1800rpm)
****
For the heat dissipation, a resistor of 400W or lower should be fixed to the frame and keep the surface below 250° C (400° F).
As for a resistor of 1000W and above, the surface temperature should be kept below 600
Braking Resistor Series for
Each Brake Unit
Part #****
BR1K2W0154
BR1K5W0134
Unit Connection
2 parallel,
2 series
2 parallel,
2 series
Tota l
Braking
Current
Min.
Resistor
Val ue (Ω)
Max. Total
Braking
Current (A)
5012.76045.6
5912.76045.6
BR1K0W5P144 series769.58060.8
BR1K2W0154
2 parallel,
2 series
1006.312091.2
° C. If the temperature is over the
resistor’s temperature limit, it will be necessary to add heat dissipating system or increase resistor’s power
Peak
Power
(kW)
NOTE:
1. Definition for Brake Usage ED%
Explanation: The definition of the brake usage ED (%) is for assurance of enough time for the brake unit and brake resistor
to dissipate away heat generated by braking. When the brake resistor heats up, the resistance would increase with temperature, and brake torque would decrease accordingly. Recommended cycle time is one minute.
For safety concern, install an overload relay (O.L) between the brake unit and the brake resistor together with the magnetic
contactor (MC) prior to the drive to protect the drive from abnormal functions. The purpose of installing the thermal overload relay is to protect the brake resistor from damages due to frequent brakes, or caused by brake unit’s continuous
conductions resulted from unusual high input voltage. Under such circumstance, turn off the power to prevent damaging the
brake resistor.
R/L1
S/L2
T/L3
THERMAL
OVERLOAD
RELAY OR
TEMPERATURE
SWITCH
NFB
O. L.
12WHEN USING THE VFD WITH DC REACTOR, PLEASE REFER TO WIRING DIAGRAM IN THE VFD
USER MANUAL FOR THE WIRING OF TERMINAL
DO NOT WIRE TERMINAL
MC
MC
SA
SURGE
ABSORBER
R/L1
S/L2
T/L3
-
(N) TO THE NEUTRAL POINT OF POWER SYSTEM.
VFD
SERIES
U/T1
V/T2
W/T3
1
+ (P)
-
(N)
E.F.
DCM
+ (P)
-
(N)
2
RA
RC
+(P) OF BRAKING UNIT.
IM
MOTOR
VFDB
BRAKING
B1
B2
THERMAL
OVERLOAD
RELAY
O. L.
BRAKING
BR
RESISTOR
TEMPERATURE
SWITCH
M33297
3763-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
60
40
30
20
10
8
3
2
4
6
1
0.8
0.6
0.4
0.3
0.8 11.5 234 5 68
1015
79
XLN (A)
M33298
MULTIPLE OF CURRENT
TRIPPING
SECONDS
2. If damage to the drive or other equipment is due to the fact that the brake resistors and brake modules in use are not provided by Honeywell, the warranty will be void.
3. Consider the safety of the environment when installing the brake resistors. If the minimum resistance value is to be utilized,
consult Honeywell Technical Support for the calculation of Watt figures.
4. When using more than 2 brake units, equivalent resistor value of parallel brake unit can’t be less than the value in the column “Minimum Equivalent Resistor Value for Each VFD” (the right-most column in the table). Read the wiring information in
the user manual of the brake unit thoroughly prior to operation
5. This chart is for normal usage; if the VFD will be applied for frequent braking, it is recommended to increase the watts by
2~3 times.
6. Thermal Relay:
Thermal relay selection is based on its overload capability. A standard braking capacity for VFD CORE is 10%ED (Tripping
time=10s). The figure below is an example of 460V, 110kw VFD. It requires the thermal relay to take 260% overload capacity in 10s (Host starting) and the braking current is 126A. In this case, user should select a rated 50A thermal relay. The
property of each thermal relay may vary among different manufacturer, please read carefully specification provided by the
manufacturer.
63-4528—0438
CHAPTER 7: OPTIONAL COMPONENTS
Non-fuse Circuit Breaker
To comply with UL standard: Per UL 508, paragraph 45.8.4, part a:
The rated current of the breaker shall be 2~4 times of the maximum rated input current of VFD.
3-phase 230V3-phase 460V
ModelRecommended non-
fuse breaker (A)
HCRDA0010A1000T15HCRDC0010A1000T5
HCRDA0020A1000T20HCRDC0020A1000T10
HCRDA0030A1000T30HCRDC0030A1000T15
HCRDA0050A1000T40HCRDC0050A1000T20
HCRDA0075A1000T50HCRDC0075A1000T30
HCRDA0100B1000T60HCRDC0100A1000T40
HCRDA0150B1000T100HCRDC0150B1000T50
HCRDA0200B1000T125HCRDC0200B1000T60
HCRDA0250C1000T150HCRDC0250B1000T75
HCRDA0300C1000T200HCRDC0300C1000T100
HCRDA0400C1000T225HCRDC0400C1000T125
HCRDA0500D1000T250HCRDC0500C1000T150
HCRDA0600D1000T300HCRDC0600D1000T175
HCRDA0750E1000T400HCRDC0750D1000T250
HCRDA1000E1000T450HCRDC1000D1000T300
HCRDA1250E1000T600HCRDC1250D1000T300
ModelRecommended non-
fuse breaker (A)
Fuse (Specification Chart)
Fuses with specification smaller than the data in the following table are allowed.
Model 230V
HCRDA0010A1000T6.43.915JJN-15
HCRDA0020A1000T9.66.420JJN-20
HCRDA0030A1000T151230JJN-30
HCRDA0050A1000T221640JJN-40
HCRDA0075A1000T252050JJN-50
HCRDA0100B1000T352860JJN-60
HCRDA0150B1000T5036100JJN-100
HCRDA0200B1000T6552125JJN-125
HCRDA0250C1000T8372150JJN-150
HCRDA0300C1000T10083200JJN-200
HCRDA0400C1000T11699225JJN-225
HCRDA0500D1000T146124250JJN-250
Normal dutyHeavy dutyI (A)Bussmann P/N
Input Current I(A)Line Fuse
3963-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
HCRDA0600D1000T180143300JJN-300
HCRDA0750E1000T215171400JJN-400
HCRDA1000E1000T276206450JJN-450
HCRDA1250E1000T322245600JJN-600
Model 460V
Normal dutyHeavy dutyI (A)Bussmann P/N
Input current (A)Line Fuse
HCRDC0010A1000T4.33.510JJS-10
HCRDC0020A1000T5.44.310JJS-10
HCRDC0030A1000T7.45.915JJS-15
HCRDC0050A1000T118.720JJS-20
HCRDC0075A1000T1815.530JJS-30
HCRDC0100A1000T201740JJS-40
HCRDC0150B1000T252050JJS-50
HCRDC0200B1000T332660JJS-60
HCRDC0250B1000T393575JJS-75
HCRDC0300C1000T4740100JJS-100
HCRDC0400C1000T5847125JJS-125
HCRDC0500C1000T7663150JJS-150
HCRDC0600D1000T9174175JJS-175
HCRDC0750D1000T110101250JJS-250
HCRDC1000D1000T144114300JJS-300
HCRDC1250D1000T180157300JJS-300
63-4528—0440
Digital Keypad: HCRDKEYPAD/U
MCR33299
A: LED DISPLAY
DISPLAY FREQUENCY, CURRENT,
VOLTAGE, AND ERROR, ETC.
B: STATUS INDICATOR
F: FREQENCY COMMAND
H: OUTPUT FREQUENCY
U: USER DEFINED UNITS
ERR: COMM ERROR INDICATOR
RUN: COMM RUN INDICATOR
C: FUNCTION
(REFER TO THE CHART THAT
FOLLOWS FOR DETAIL
DESCRIPTION)
CORE
F1F2
F3
F4
ESC
MENU
AUTO
HAND
STOP
RESET
FWD
REV
FWD
ENTER
ERR
COMM
RUN
RUN
RUN
STOP
RESET
REV
FWD
ENTER
ESC
MENU
Table 2. Descriptions of Keypad Functions
KeyDescriptions
This is the RUN/START command to the VFD when in Hand/Keypad control only.
CHAPTER 7: OPTIONAL COMPONENTS
It can operate the VFD by the function setting and the RUN LED will be ON.
Stop Command Key. This key has the highest processing priority in any situation. Drive will always STOP
when this button is pressed.
The RESET key can be used to reset the drive after the fault occurs. For those faults that can’t be reset by
the RESET key, see the fault records after pressing MENU key for details.
This key controls the operational direction of the motor. NOT activated out of the box.
Press ENTER and go to the next submenu. If at the parameter level, press enter to modify and press
enter to save changes
ESC key function is to leave current menu and return to the last menu. It is also functioned as a return key
in the sub-menu.
Press menu to return to main menu. See main menu descriptions on following pages.
4163-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
F1
F2
F3
F4
HAND
AUTO
RUN
STOP
RESET
REV
FWD
HAND
AUTO
RIGHT and LEFT arrows to move the cursor with a numeric parameter, or to enter into and out of menus.
UP and DOWN arrows used to change numeric parameter values, or cycle through menu options.
Function Keys - will have different functions at different times as displayed on the screen. Used during
Wizard Mode.
Pressing the HAND key will take the VFD into Hand control, where the user can control the motor
Frequency and START and STOP.
Pressing this key will revert the VFD to remote/Automatic control from a remote speed and start
command source.
Table 2. Descriptions of Keypad Functions
Table 3. Descriptions of LED Functions
LEDDescriptions
Steady ON: operation indicator for the VFD, including DC brake, zero speed, standby, restart after fault
and speed search.
Blinking: VFD is decelerating to stop.
Steady OFF: VFD is not running.
Steady ON: VFD is stopped.
Blinking: VFD is in the standby status.
Steady OFF: VFD running.
Operation Direction LED (green: forward running, red: reverse running).
Blinking: drive is changing the operation direction.
HAND LED: HAND LED is on (HAND mode); HAND LED is off (AUTO mode).
AUTO LED: AUTO LED is on (AUTO mode); AUTO LED is off (HAND mode).
63-4528—0442
CHAPTER 7: OPTIONAL COMPONENTS
VFD-Cx
F1F2
F3
F4
ESC
MENU
AUTO
HAND
STOP
RESET
FWD
REV
FWD
ENTER
ERR
COMM
RUN
RUN
M33223
72 (2-53/64)
116
(4-9/16)
15
(19/32)
Fig. 1. Keypad Dimensions: mm (inches).
4363-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
M33300
M33302
Ø 5 (3/16)
36 (1 27/64)
24 (15/16)
19
(3/4)
22 (7/8)
93
(3-21/32)
57
(2-7/32)
M33303
PANEL
A
B
KEYPAD
Normal cutout dimension
*Deviation: ±0.15mm /±0.0059inch
Cutout dimension (Waterproof level: IP56)
*Deviation: ±0.15mm /±0.0059inch
Panel
thickness1.2mm1.6mm2.0mm
A66.4 [2.614]
B
110.2 [4.339]111.3 [4.382]112.5 [4.429]
Panel
thickness1.2mm1.6mm2.0mm
A66.4 [2.614]
B
110.8 [4.362]
Panel Mounting Kit: HCRDMOUNTKIT/U
For mounting kit model, user can choose wall mounting or embedded mounting, protection level is IP56.
1. Loosen screw 1 and screw 2, then press the right and left
sides to remove the cover, following the directions of the
arrows. Press on top of the digital keypad to properly
remove it. Screw torque: 10~12kg-cm (8.6~10.4in-lbf).
3. Loosen screw 5 and disconnect the fan’s power.
Screw torque: 10~12kg-cm (8.6~10.4in-lbf).
2. Loosen screw 3 and screw 4, then press the tab on the
right and left to remove the cover.
Screw torque: 6~8kg-cm (5.2~6.9in-lbf)
Fig. 2. Panel Cutout Diagram Frame A: Unit in in. (mm)
M33366
CHAPTER 7: OPTIONAL COMPONENTS
M33368
SIDE BRACKET
SIDE BRACKET
SCREW 2
M33369
SIDE BRACKET
SCREW 2
SIDE BRACKET
SCREW 2
Installation of Flange Mouting Kit Type 1
1. Install mounting plate by using 4 screws (M3). Screw torque: 6~8kg-cm (5.21~6.95Ib-in).
SCREWS
SCREWS
M33367
2. Install side bracket using 2 screws on one side (M6). Screw torque:25~30kg-cm (21.7~ 26.Ib-in)』
3. Install side brackets by using screws on the other side (M6). Screw torque:25~30kg-cm (21.7~26 Ib-in)』
5763-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
M33370
SCREW 2
SCREW 2
4. Mount VFD on the frame, using 4 screws (M6) through the side brackets and the plate, then fasten the screws.
Screw torque: 25~30kg-cm (5.21~6.94Ib-in).25~30kg-cm (21.7~26Ib-in)』
63-4528—0458
CHAPTER 7: OPTIONAL COMPONENTS
M33371
SIDE BRACKET
SIDE BRACKET
SCREW 1
KIT 1
M33373
SCREW 1
SCREW 1
Installation of Flange Mounting Kit Type 2
1. Install mounting plate by using 4 screws (M3). Screw torque:25~30kg-cm (21.7~26Ib-in)』
(As shown in the figures below)
2. Install side bracket using 2 screws on one side (M3). Screw torque: 25~30kg-cm (21.7~26Ib-in)』
(As shown in the figures below)
SIDE BRACKET
SIDE BRACKET
SCREW 1
SCREW 1
M33372
3. Mount VFD on the frame, using 4 screws (M6) through the side brackets and the plate, then fasten the screws.
Screw torque: 25~30kg-cm (21.7~26 Ib-in). (As shown in the figures below)
5963-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
M33374
M33375
Side Bracket, 2 each
Side Bracket, 2 each
Screw 1 *4 each ~ M8*P 1.25;
Screw 2*6 each ~ M6*P 1.0;
[6] M6*1.0 OR
[6] Ø17/64 (Ø7)
6-13/16 (173)
7-51/64 (198)
8-29/32 (226)
12-11/16
(322)
13-25/32
(350)
M33376
Frame B
Flange Mounting Kit Frame B
Corresponding models: All Frame B models
Fig. 3. Panel Cutout Diagram Frame B: Unit in in. (mm)
63-4528—0460
CHAPTER 7: OPTIONAL COMPONENTS
M33379
SCREW 2
Installation of Flange Mounting Kit Frame B
1. Install side brackets using the screws provided (M8). Screw torque: 40~45kg-cm (34.7~39.0Ib-in).
(As shown in the following figure)
SCREW 1
SIDE BRACKET
SIDE BRACKET
SIDE BRACKET
SIDE BRACKET
M33378
2. Mount VFD on the frame, using 6 screws (M6) through the side brackets and the plate, then fasten the screws.
Screw torque: 25~30kg-cm (21.7~26Ib-in). (As shown in the following figure)
6163-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
M33374
Side Bracket 2 each
Side Bracket 2 each
Screw 1 *4 pieces ~ M8*P 1.25;
Screw 2*8 pieces ~ M6*P 1.0
[8] M6*1.0 OR
[8] Ø17/64 (Ø7)
M33381
9-3/32 (231)
10-5/32 (258)
11-17/64 (286)
15-53/64
(402)
16-15/16
(430)
Frame C
Flange Mounting Kit Frame C
Corresponding models: All Frame C models
M33380
63-4528—0462
Fig. 4. Panel Cutout Diagram Frame C: Unit in in. (mm)
CHAPTER 7: OPTIONAL COMPONENTS
M33382
SCREW 1
SIDE BRACKET
SIDE BRACKET
SIDE BRACKET
SIDE BRACKET
Installation of Flange Mounting Kit Frame C
1. Install side brackets by tightening 4 of the screw 1 (M8). Screw torque: 50~55kg-cm (43.4~47.7Ib-in).
(As shown in the figures below)
2. Plate installation, place 8 of the screw 2 (M6) through accessories 1 & 2 and the plate, then tighten the screws.
Screw torque: 25~30kg-cm (21.7~26.0Ib-in). (As shown in the figures below)
SCREW 2
M33383
6363-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
Frame D
13-5/16 (338)
11-7/32 (285)
[4] M10*P1.5 OR
[4] Ø7/16 (Ø11)
25/64
(10)
19-15/16
(507)
Fig. 5. Panel Cutout Diagram Frame D: Unit in in. (mm)
63-4528—0464
29/64
(12)
M33384
Frame E
[4] M12*P1.75 OR
[4] Ø33/64 (Ø13)
21-1/4
(540)
13-3/16 (335)
15-1/8 (384)
7/16 (11)
37/64 (15)
M33385
CHAPTER 7: OPTIONAL COMPONENTS
Fig. 6. Panel Cutout Diagram Frame E: Unit in in. (mm)
6563-4528—04
CHAPTER 7: OPTIONAL COMPONENTS
M33386
FIXTURE 2
4
3
2
1
8
7
6
5
M33387
FIXTURE 2
1
2
4
3
M33388
FIXTURE 1
4
3
1
2
5
10
9
8
7
6
M33389
FIXTURE 1
1
2
3
5
4
M33390
FIXTURE 2
1
2
5
6
M33391
FIXTURE 2
(4) M10
FIXTURE 1
Installation of Flange Mounting Kit Frame D & E
1. Remove 8 screws, then remove Fixture 2
(as shown in the following figure).
5. Tighten 4 screws (as shown in the following figure).
Screw torque: 24~26kg-cm (20.8~22.6Ib-in)
2. Remove 10 screws, then remove Fixture 1
(as shown in the figure below.)
3. Tighten 4 screws (as shown in the figure below).
Screw torque: 30~32kg-cm (26.0~27.8Ib-in).
6. Tighten 5 screws (as shown in the figure below).
Screw torque: 24~26kg-cm (20.8~22.6Ib-in).
7. Place 4 screws (M10) through Fixture 1 & 2 and the plate
then fasten the screws (as shown in the following figure).
Screw torque: 200~240kg-cm (173.6~208.3Ib-in).
4. Tighten 5 screws (as shown in the figure below).
Screw torque: 30~32kg-cm (26.0~27.8Ib-in).
3
1
FIXTURE 1
63-4528—0466
2
4
5
M33392
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
M33569
(ALL OPTIONAL)
Select applicable option cards for your drive or contact Honeywell Technical Support for professional advice. To prevent drive
damage during installation, please remove the digital keypad and the cover before wiring. Refer to the instructions below.
Remove Keypad cover
Frame A, B and C: Screw Torque: 8~10Kg-cm [6.9~8.7lb-in.]
M33568
Frame D: Screw Torque: 8~10Kg-cm [6.9~8.7lb-in.]
6763-4528—04
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
M33260
Frame E: Screw Torque: 12~15Kg-cm [10.4~13lb-in.] As shown below, lift the cover then pull to remove it.
63-4528—0468
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
SLOT 3
SLOT 2SLOT 1
M33570
1
2
3
4
1. RJ45 (Socket) for digital keypad HCRDKEYPAD
• Please refer to CH10 Digital Keypad for more details on the
keypad and optional RJ45 extension cable
2. Communication Expansion Cards (Slot 1)
3. I/O & Relay Expansion Card (Slot 3)
4. No Function
TerminalsDescriptions
COM
Common for Multi-function input terminals
Select SINK (NPN) / SOURCE (PNP) in J1 jumper/external power supply
Refer to parameters 02-27~02-30 in Chapter 11 to program the multi-function
inputs MI10~MI13.
MI10~ MI13
I/O Expansion Card
(4 Digital Input and 4
Digital Output)
MO10~MO11
Internal power is applied from terminal E24: +24Vdc±5% 200mA, 5W
External power +24VDC: max. voltage 30VDC, min. voltage 19VDC, 30W
ON: the activation current is 6.5mA
OFF: leakage current tolerance is 10μA
Install MODBUS TCP/IP COMMUNICATION CARD on VFD CORE
1. Switch off the power supply of VFD CORE.
2. Open the front cover of VFD CORE.
3. Place the insulation spacer into the positioning pin at Slot 1 (shown in Figure 3), and aim the two holes on the PCB at the
positioning pin. Press the pin to clip the holes with the PCB (see Figure 4).
4. Screw up at torque 6 ~ 8 kg-cm (5.21 ~ 6.94 in-lbs) after the PCB is clipped with the holes (see Figure 5).
[Fig. 3]
[
Fig. 5]
Communication parameter for VFD CORE to connect to an Ethernet
Before VFD-CORE is linked to an Ethernet, set up the communication parameters shown in the table below. Then Ethernet
master will be able to read/write the frequency characters and control characters from/into VFD-CORE after communication
[
Fig. 4]
parameters are set.
63-4528—0472
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
CORE
Parameters
00-20
00-21
09-30
Functions
Set up source of frequency
command
Set up source of operation
command
Communication decoding
method
Factory setting
(Dec)
Explanation
0Frequency command from keypad
5Operation command from communication card.
0The decoding method for Honeywell VFD
09-75IP configuration 0Static IP(0) / Dynamic IP (DHCP) (1)
Remove Modbus TCP/IP communication card from VFD-CORE
1. Switch off the power supply of VFD CORE.
2. Remove the two screws (see Figure 6).
3. Twist opens the card clip and inserts the slot type screwdriver to the hollow to prize the PCB off the card clip (see Figure 7).
4. Twist opens the other card clip to remove the PCB (see Figure 8).
7363-4528—04
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
M33575
M33576
[Figure 6]
[
Figure 7]
Basic Registers
BR
number
PropertyContentExplanation
#0R
#1R
#2R
#11R/W
#13R/W
M33577
[
Figure 8]
Model nameSet up by the system; read only. The model code of MODBUS TCP/IP
COMMUNICATION CARD=H’0203
Firmware
version
Release date of
the version
Modbus
Timeout
Keep Alive
Time
Displaying the current firmware version in hex, e.g. H’0100 indicates the firmware
version V1.00.
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for “month”; 100s
digit and 10s digit are for “day”.
For 1 digit: 0 = morning; 1 = afternoon.
Preset: 500 (ms)
Preset: 30 (s)
63-4528—0474
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
LED Indicators & Troubleshooting
LED Indicators
LEDStatusIndicationAction
POWERGreen
OnPower supply in normal statusNo action required
OffNo power supplyCheck if the power supply is plugged.
OnNetwork connection in normal statusNo action required
LINKGreen
FlashesNetwork in operationNo action required
OffNetwork not connectedCheck if the network cable is connected
Troubleshooting
AbnormalityCauseAction
POWER LED offVFD not powered
MODBUS TCP/IP
COMMUNICATION CARD not
connected to VFD
MODBUS TCP/IP
LINK LED off
COMMUNICATION CARD not
connected to network
Poor contact to RJ-45 connector
MODBUS TCP/IP
No module found
COMMUNICATION CARD not
connected to network
Check if VFD is powered, and if the power supply is
normal.
Make sure MODBUS TCP/IP COMMUNICATION CARD
is connected to VFD.
Make sure the network cable is correctly connected to
network.
Make sure RJ-45 connector is connected to Ethernet
port.
Make sure MODBUS TCP/IP COMMUNICATION CARD
is connected to network.
PC and MODBUS TCP/IP
COMMUNICATION CARD in
different networks and blocked by
Search by IP or set up relevant settings by VFD keypad.
network firewall.
Fail to open MODBUS
TCP/IP COMMUNICATION
CARD setup page
MODBUS TCP/IP
COMMUNICATION CARD not
connected to network
Incorrect communication setting in
DCISoft
Make sure MODBUS TCP/IP COMMUNICATION CARD
is connected to the network.
Make sure the communication setting in DCISoft is set to
Ethernet.
PC and MODBUS TCP/IP
COMMUNICATION CARD in
different networks and blocked by
Conduct the setup by VFD keypad.
network firewall.
Able to open MODBUS
TCP/IP COMMUNICATION
CARD setup page but fail
to utilize webpage
monitoring
Fail to send e-mail
Incorrect network setting in
MODBUS TCP/IP
COMMUNICATION CARD
Incorrect network setting in
MODBUS TCP/IP
COMMUNICATION CARD
Check if the network setting for MODBUS TCP/IP
COMMUNICATION CARD is correct. For the Intranet
setting in your company, please consult your IT staff. For
the Internet setting in your home, please refer to the
network setting instruction provided by your ISP.
Check if the network setting for MODBUS TCP/IP
COMMUNICATION CARD is correct.
Incorrect mail server settingPlease confirm the IP address for SMTP-Server.
7563-4528—04
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
M33578
32164
5
7
PROFIBUS DP COMMUNICATION CARD
Features
1. Supports PZD control data exchange.
2. Supports PKW polling VFD parameters.
3. Supports user diagnosis function.
4. Auto-detects baud rates; supports maximum 12Mbps.
Product Introduction
1. NET indicator
2. POWER indicator
3. Positioning hole
4. VFD connection port
5. PROFIBUS DP connection port
6. Screw fixing hole
Specifications
PROFIBUS DP Communication Connector
InterfaceDB9 Connector connectorDB9
Transmission methodHigh-speed RS-485RS-485
Transmission cableShielded twisted pair cable
Electrical isolation500VDC500VDC
Communication
Message typeData exchange periodically
Module namePROFIBUS DP COMMUNICATION CARD
GSD document08DB.GSD
Company ID08DB(HEX)
Serial transmission speed
supported (auto-detection)
Support 9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;
PROFIBUS DP Communication Connector: Definition of pins
PinName Definition
1-Not defined
2-Not defined
3Rxd/Txd-PSending/receiving data P(B)
4-Not defined
5DGNDData reference ground
6VPPower voltage – positive
7-Not defined
8Rxd/Txd-NSending/receiving data N(A)
9-Not defined
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
LED Indicator and Troubleshooting
There are 2 LED indicators on PROFIBUS DP COMMUNICATION CARD. POWER LED displays the status of the working power.
NET LED displays the connection status of the communication.
POWER LED
LED statusIndicationAction
Green light onPower supply in normal status.No action required
OffNo power
Check if PROFIBUS DP COMMUNICATION CARD and VFD
are properly connected.
7763-4528—04
DEVICENET COMMUNICATION CARD
M33580
432168
5
7
NET LED
LED statusIndicationAction
Green light onNormal statusNo action required
Red light on
Red light flashes
Orange light flashes
PROFIBUS DP COMMUNICATION CARD
is not connected to PROFIBUS DP bus.
Invalid PROFIBUS communication
address
PROFIBUS DP COMMUNICATION CARD
fails to communication with VFD.
Connect PROFIBUS DP COMMUNICATION CARD to
PROFIBUS DP bus.
Set the PROFIBUS address of PROFIBUS DP
COMMUNICATION CARD between 1 ~ 125 (decimal)
Switch off the power and check whether PROFIBUS DP
COMMUNICATION CARD is correctly and normally
connected to VFD.
DEVICENET COMMUNICATION CARD
Features
1. Based on the high-speed communication interface of Honeywell HSSP protocol, able to conduct immediate control to the
VFD.
2. Supports Group 2 only connection and polling I/O data exchange.
3. For I/O mapping, supports Max. 32 words of input and 32 words of output.
4. Supports EDS file configuration in DeviceNet configuration software.
5. Supports all baud rates on DeviceNet bus: 125kbps, 250kbps, 500kbps and extendable serial transmission speed mode.
6. Node address and serial transmission speed can be set up on VFD.
7. Power supplied from the VFD.
Product introduction
1. NS indicator
2. MS indicator
3. POWER indicator
4. Positioning hole
5. DeviceNet connection port
6. Screw fixing hole
7. Fool-proof groove
8. VFD connection port
63-4528—0478
DEVICENET COMMUNICATION CARD
Specifications
DeviceNet Connector
Interface5-PIN open removable connector. Of 5.08mm PIN interval
Transmission methodCAN
Transmission cableShielded twisted pair cable (with 2 power cables)
Transmission speed125kbps, 250kbps, 500kbps and extendable serial transmission speed mode
There are 3 LED indicators on DEVICENET COMMUNICATION CARD. POWER LED displays the status of power supply. MS
LED and NS LED are dual-color LED, displaying the connection status of the communication and error messages.
POWER LED
LED statusIndicationAction
OnPower supply in abnormal status.
Check the power supply of DEVICENET
COMMUNICATION CARD.
OffPower supply in normal statusNo action required
NS LED
LED statusIndicationAction
1. Check the power of DEVICENET COMMUNICATION
CARD and see if the connection is normal.
2. Make sure at least one or more nodes are on the bus.
3. Check if the serial transmission speed of DEVICENET
COMMUNICATION CARD is the same as that of other
Off
No power supply or DEVICENET
COMMUNICATION CARD has not
completed MAC ID test yet.
nodes.
Green light
flashes
DEVICENET COMMUNICATION CARD is
on-line but has not established connection
to the master.
1. Configure DEVICENET COMMUNICATION CARD to the
scan list of the master.
2. Re-download the configured data to the master.
DEVICENET COMMUNICATION CARD is
Green light on
on-line and is normally connected to the
No action required
master
Red light
flashes
Red light on
DEVICENET COMMUNICATION CARD
is on-line, but I/O connection is timedout.
1. The communication is down.
2. MAC ID test failure.
3. No network power supply.
4. DEVICENET COMMUNICATION
CARD is off-line.
1. Check if the network connection is normal.
2. Check if the master operates normally.
1. Make sure all the MAC IDs on the network are not
repeated.
2. Check if the network installation is normal.
3. Check if the baud rate of DEVICENET COMMUNICATION
CARD is consistent with that of other nodes.
4. Check if the node address of DEVICENET COMMUNICATION CARD is illegal.
5. Check if the network power supply is normal.
MS LED
LED statusIndicationHow to correct
OffNo power supply or being off-line
Green light
flashes
Waiting for I/O dataSwitch the master PLC to RUN status
Check the power supply of DEVICENET COMMUNICATION
CARD and see of the connection is normal.
Green light onI/O data are normal--
Red light
flashes
Mapping error
Red light onHardware error
Orange light
flashes
63-4528—0480
DEVICENET COMMUNICATION CARD is
establishing connection with VFD.
1. Reconfigure DEVICENET COMMUNICATION CARD
2. Re-power VFD
1. See the error code displayed on VFD.
2. Send back to the factory for repair if necessary.
If the flashing lasts for a long time, check if DEVICENET
COMMUNICATION CARD and VFD are correctly installed and
normally connected to each other.
Connecting ETHERNET/IP COMMUNICATION CARD to a Network
1. Turn off the power of VFD.
RJ45
2. Open the cover of VFD.
3. Connect CAT-5e network cable to RJ-45 port on ETHERNET/IP
COMMUNICATION CARD.
M33582
[Figure 2]
RJ-45 connector: Definition of Pins
PINSignalDefinitionPINSignalDefinition
1Tx+
2Tx-
3Rx+
Positive pole for data
transmission
Negative pole for data
transmission
Positive pole for data
receiving
5--N/C
6Rx-
Negative pole for data
receiving
7--N/C
8 1
M33584
4--N/C8 --N/C
Connecting ETHERNET/IP COMMUNICATION CARD to VFD-CORE
1. Switch off the power of VFD.
2. Open the front cover of VFD.
3. Place the insulation spacer into the positioning pin at Slot 1 (shown in Figure 3), and aim the two holes on the PCB at the
positioning pin. Press the pin to clip the holes with the PCB (see Figure 4).
4. Screw up at torque 6 ~ 8 kg-cm (5.21 ~ 6.94 in-lbs) after the PCB is clipped with the holes (see Figure 5).
63-4528—0482
M33585
ETHERNET/IP COMMUNICATION CARD
[Figure 3]
[Figure 4]
M33575
[Figure 5]
Communication parameter for VFD-CORE to connect to an Ethernet
Before VFD-CORE is linked to an Ethernet, set up the communication parameters shown in the table below. Then Ethernet
master will be able to read/write the frequency characters and control characters from/into VFD-CORE after communication
parameters are set.
Remove ETHERNET/IP COMMUNICATION CARD from VFD-CORE
1. Switch off the power supply of VFD-CORE.
2. Remove the two screws (see Figure 6).
3. Twist opens the card clip and inserts the slot type screwdriver to the hollow to prize the PCB off the card clip (see Figure 7).
4. Twist opens the other card clip to remove the PCB (see Figure 8).
8363-4528—04
ETHERNET/IP COMMUNICATION CARD
M33575
M33576
M33577
[Figure 6][Figure 7]
[Figure 8]
63-4528—0484
ETHERNET/IP COMMUNICATION CARD
LED Indicators & Troubleshooting
There are 2 LED indicators on ETHERNET/IP COMMUNICATION CARD. The POWER LED displays the status of power supply,
and the LINK LED displays the connection status of the communication.
LED Indicators
LEDStatusIndicationAction
POWERGreen
OnPower supply in normal statusNo action required.
OffNo power supplyCheck the power supply.
OnNetwork connection in normal statusNo action required.
LINKGreen
FlashesNetwork in operationNo action required.
OffNetwork not connectedCheck if the network cable is connected.
Troubleshooting
AbnormalityCauseAction
Check if VFD is powered, and if the power supply is
normal.
Make sure ETHERNET/IP COMMUNICATION CARD is
connected to VFD.
Make sure the network cable is correctly connected to
network.
POWER LED off
LINK LED off
VFD not powered
ETHERNET/IP COMMUNICATION
CARD not connected to VFD
ETHERNET/IP COMMUNICATION
CARD not connected to network
Poor contact to RJ-45 connectorMake sure RJ-45 connector is connected to Ethernet port.
No communication
card found
ETHERNET/IP COMMUNICATION
CARD not connected to network
PC and ETHERNET/IP
COMMUNICATION CARD in different
networks and blocked by network
Make sure ETHERNET/IP COMMUNICATION CARD is
connected to network.
Search by IP or set up relevant settings by VFD keypad.
firewall.
Fail to open
ETHERNET/IP
COMMUNICATION
CARD setup page
ETHERNET/IP COMMUNICATION
CARD not connected to network
Incorrect communication setting in
DCISoft
PC and ETHERNET/IP
COMMUNICATION CARD in different
networks and blocked by network
Make sure ETHERNET/IP COMMUNICATION CARD is
connected to the network.
Make sure the communication setting in DCISoft is set to
Ethernet.
Conduct the setup by VFD keypad.
firewall.
Able to open
ETHERNET/IP
COMMUNICATION
CARD setup page but
fail to utilize webpage
monitoring
Fail to send e-mail
Incorrect network setting in
ETHERNET/IP COMMUNICATION
CARD
Incorrect network setting in
ETHERNET/IP COMMUNICATION
CARD
Check if the network setting for ETHERNET/IP
COMMUNICATION CARD is correct. For the Intranet
setting in your company, please consult your IT staff. For
the Internet setting in your home, please refer to the
network setting instruction provided by your ISP.
Check if the network setting for ETHERNET/IP
COMMUNICATION CARD is correct.
Incorrect mail server settingPlease confirm the IP address for SMTP-Server.
Air PressureOperation/ Storage: 86 to 106 kPaTransportation: 70 to 106 kPa
Environment
Pollution Level
IEC721-3-3
Operation: Class 3C2; Class 3S2Storage: Class 2C2; Class 2S2Transportation: Class 1C2; Class 1S2
No concentrate
AltitudeOperation
If VFD is installed at altitude 0~1000m, follow normal operation restriction. If it is installed at
altitude 1000~3000m, decrease 2% of rated current or lower 0.5
o
C of temperature for every
100m increase in altitude. Maximum altitude for Corner Grounded is 2000m.
Package
Drop
Vibration
Storage
ISTA procedure 1A(according to weight) IEC60068-2-31
Transportation
1.0mm, peak to peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from 13.2Hz to 55Hz; 1.0G range from 55Hz to 512 Hz.
Comply with IEC 60068-2-6
Impact
IEC/EN 60068-2-27
Operation
Position
Plenum
Rating
Max. allowed offset angle ±10o (under normal installation
position)
Compliance with UL 508C, the Standard for Power Conversion Equipments, 3rd Edition, and the Canadian Standard for Industrial
Control Equipment, C22.2-No. 14.
ModelFrameTop coverConduit BoxProtection Level
HCRDAxxxxx1000T
HCRDCxxxxx1000T
Table 5. Specification for Operation Temperature and Protection Level
Frame A-C
230V: 0.75-3kW
Remove top
coverStandard
IP20/UL Open Type
conduit plate
Standard with
IP20/UL Type1/NEMA1
top cover
Frame D-E
230V: Above 37kW
N/ANo conduit box IP00
IP20/UL Open Type
Only the circled area is IP00;
other parts are IP20.
Frame A-C
460V: 0.75~37kW
Remove top
coverStandard
IP20/UL Open Type
conduit plate
Standard with
IP20/UL Type1/NEMA1
top cover
Frame D-E
460V: Above 45kW
N/AStandard
conduit box
IP20/UL Type1/NEMA1
Operation
Temperature
-10-50o C
(14-120o F)
o
-10-40
C
(14-104o F)
o
-10-50
C
(14-122o F)
o
-10-50
C
(14-122o F)
o
-10-40
C
(14-104o F)
o
-10-40
C
(14-104o F)
63-4528—0490
CHAPTER 10: DIGITAL KEYPAD
M31501
CORE
F1
F2
F3
F4
ESC
MENU
AUTO
HAND
STOP
RESET
FWD
REV
FWD
ENTER
ERR
COMM
RUN
RUN
Communication Interface
RJ-45 (socket)、RS-485 interface;
Installation Method
Embedded type and can be put flat on the surface of the control box. The
front cover is water proof.
Charge the digital keypad for 6 minutes before you use it to program the VFD.
RUN
STOP
RESET
REV
FWD
ENTER
ESC
MENU
HCRDKEYPAD
Table 1. Descriptions of Keypad Functions
KeyDescriptions
This is the RUN/START command to the VFD when in Hand/Keypad control only.
It can operate the AC motor drive by the function setting and the RUN LED will be ON.
Stop Command Key. This key has the highest processing priority in any situation. Drive will always STOP
when this button is pressed.
The RESET key can be used to reset the drive after the fault occurs. For those faults that can’t be reset by
the RESET key, see the fault records after pressing MENU key for details.
This key controls the operational direction of the motor. NOT activated out of the box.
Press ENTER and go to the next submenu. If at the parameter level, press enter to modify and press
enter to save changes
ESC key function is to leave current menu and return to the last menu. It is also functioned as a return key
in the sub-menu.
Press menu to return to main menu. See main menu descriptions on following pages.
9163-4528—04
CHAPTER 10: DIGITAL KEYPAD
F1
F2
F3
F4
HAND
AUTO
RUN
STOP
RESET
REV
FWD
HAND
AUTO
RIGHT and LEFT arrows to move the cursor with a numeric parameter, or to enter into and out of menus.
UP and DOWN arrows used to change numeric parameter values, or cycle through menu options.
Function Keys - will have different functions at different times as displayed on the screen. Used during
Wizard Mode.
Pressing the HAND key will take the VFD into Hand control, where the user can control the motor
Frequency and START and STOP.
Pressing this key will revert the VFD to remote/Automatic control from a remote speed and start
command source.
Table 1. Descriptions of Keypad Functions
Table 2. Descriptions of LED Functions
LEDDescriptions
Steady ON: operation indicator for the VFD, including DC brake, zero speed, standby, restart after fault
and speed search.
Blinking: VFD is decelerating to stop.
Steady OFF: VFD is not running.
Steady ON: VFD is stopped.
Blinking: VFD is in the standby status.
Steady OFF: VFD running.
Operation Direction LED (green: forward running, red: reverse running).
Blinking: drive is changing the operation direction.
HAND LED: HAND LED is on (HAND mode); HAND LED is off (AUTO mode).
AUTO LED: AUTO LED is on (AUTO mode); AUTO LED is off (HAND mode).
Startup in Digital Keypad
1. The default Start-up page is Honeywell Logo, displayed for 3 seconds
2. Selection Screen. Choose how to interact with the VFD.
— Press F4: Initials the Startup Wizard
— Press Menu: Redirect to the main menu
— Press Esc: Redirect to the monitor screen
63-4528—0492
Startup Wizard Guide
Follow the steps in the table below to complete the Startup Wizard.
Table 3. Honeywell Commissioning Start-Up Wizard
CHAPTER 10: DIGITAL KEYPAD
Screen #Screen
Verbiage
1Boot Screen Honeywell displayed for 3 secondsN/A
2Selection
Screen
3Select
Language
4Clock Time
and DATE
5Motor
Voltage
6Motor
Current
7Motor FREQ Motor's rated frequency based upon Motor Name
8Motor RPMMotor's rated RPM based upon Motor Name
9ACCEL
TIME
10DECEL
TIME
11, 12, 13PRESET
SPEED
1,2,3
14Analog Input Select the speed reference signal type. 0. 0-10V - Use AVI (Analog Voltage Input terminal)
15MIN
Frequency
16MAX
Frequency
17PRESS F4
to SAVE
ALL
Choose how to interact with the VFD:
Recommendation: Press function key F4 to start
the wizard
Choose the keypad programming language
Use UP and DOWN arrows to change from
default. Press ENTER to accept change.
F1 BACK up one menu (SAME function
throughout WIZARD)
F4 Next Parameter (SAME function throughout
WIZARD)
Select the time (Military) HH:MM:SS and date
YY/MM/DD
Motor's rated voltage based upon Motor Name
Plate data
Full Load AMPs (FLA)Do not use the motor
service factor amperage for this value.
Plate data
Plate data
The time required to accelerate from the motor’s
current speed reference to a new speed
reference
The time required to decelerate from the motor’s
current speed reference to a new speed
reference
Present Speed options. On digital input closure
the VFD will ignore the speed reference from the
analog input and will run at the programmed
speed.
The minimum frequency at which the motor will
operate
The maximum frequency at which the motor will
operate
Saves all parameter updates - VFD is ready to
operate
Screen DescriptionScreen options
F4: Initials the START UP WIZARD
Menu: redirects to MAIN MENU
ESC: redirects to MONITOR Screen
1. English (Default)
2. Spanish
3. Chinese
4. Portuguese
5. French
Use arrow keys to adjust. Press ENTER to save changes,
F4 to advance without changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
The default motor voltage is based on the VFD voltage that
you have selected
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Acceleration time is factory set for typical Fan and Pump
needs. Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
Decceleration time is factory set for typical Fan and Pump
needs. Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
With the use of MFI (Multifunction inputs) 1, 2, or 3 the drive
can be sent to the programmed speed on digital input
closure (Usage not required in the field). Adjust as needed
or press F4 to accept factory defaults.
1. 4-20mA - Use ACI (Analog current input terminals)
2. 2-10V - Use AVI
3. 0-20mA - Use ACI
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
F1 will escape the user back to the Selection Screen again
F4 will save parameters and take the user to the display
screen
9363-4528—04
CHAPTER 10: DIGITAL KEYPAD
Copy/Save
1.
2.
3.
Copy/Save
1.2009/05/04
2.
3.
File 1
1.Keypad->VFD
2.VFD->Keypad
3.
ENTER
Enter time setup; “9” will continue to blink
Move to left / right
Increase / decrease the value
When done, press
to confirm.
Quick Setup
1: V/F Mode
2: SVC Mode
3: My Mode
Keypad Lock
Press ENTER to
Lock Key
Displ Setup
1:Contrast
2:Back-Light
3:Text Color
Menu Structure
NOTE: This menu is accessed when the MENU button is pressed.
Start WizardRestart the Start-up Wizard: See Wizard instructions
Copy/Save1. Copy Parameters (4 parameter copies can be stored per keypad)
2. Press Enter on row 1-4, then select save to save parameters or load to upload
parameters to the VFD from the saved parameter list.
Fault Record1. Records the last 6 fault records
2. The first fault is the current or most recent fault
3. Select the fault code for time, date, frequency output, current, voltage, and DC Bus
Voltage at time of fault
4. Press ENTER to view a particular fault and scroll UP and DOWN to see data
Time Setup
Table 4. Main Menu Structure.
Quick SetupQuick Settings Menu contains a list of optional parameter lists for different applications.
Keypad LockThe keypad is locked when ENTER is pressed. When any key is pressed the following
LanguageUse the arrow key to move up and down to change the language selection
Display SetupDisplay Setup Menu allows the user to adjust the backlight time and contract. UP and
Advanced ParametersFull Parameter list setup. Refer to the full parameters in Chapter 12 or at
Splash ScreenRefer to the full parameters in Chapter 12
63-4528—0494
MY MODE, where frequency used parameters can be saved is located here.
STARTUP WIZARD parameters are also listed in this menu.
screen will appear.
Keypad Lock
Press ESC 3sec
to UnLock Key
To unlock, hold the ESC key down for 3 seconds. Press ENTER when done.
DOWN arrows are used to adjust settings. ENTER must be pressed for changes to be
saved.
http://www.customer.honeywell.com
CHAPTER 10: DIGITAL KEYPAD
ocA
Oc at accel
Fault
CE01
Comm. Error 1
Warning
NOTE: This menu is accessed when the MENU button is pressed.
Main PageRefer to the full parameters in Chapter 12
PLC EnabledRefer to the full parameters in Chapter 12
Copy PLCRefer to the full parameters in Chapter 12
PC LinkRefer to the full parameters in Chapter 12
Table 4. Main Menu Structure.
Other display
When a fault occurs, the menu will display:
1. Press ENTER and start RESET. If still no response, please contact Honeywell Technical Support or return to the factory. To
view the fault DC BUS voltage, output current and output voltage, press “MENU”à“Fault Record”.
2. Press ENTER again, if the screen returns to main page, the fault is clear.
3. When fault or warning message appears, backlight LED will blinks until the fault or the warning is cleared.
Optional accessory for digital keypad: RJ45 Extension Lead
CableDescription
Cable 7 RJ45 Extension Lead 7 feet
Cable 15 RJ45 Extension Lead 15 feet
NOTES:
1. Keypad supports up to 4 main pages. If you download over 4 main pages, it will only support the first 4 downloaded main
pages.
2. By pressing keypads, you can only switch pages from pates. It doesn’t support entering words or images.
0: No function
1: Read only
6: Reset PLC (including CANopen Master Index)
00-02Parameter Reset
7: Reset CANopen Index (Slave)
9: All parameters are reset to factory settings(base
frequency is 50Hz)
10: All parameters are reset to factory settings (base
frequency is 60Hz)
0: F (frequency command)
a
00-03Start-up Display Selection
1: H (output frequency)
2: U (multi-function display, see Pr.00-04)
3: A (output current)
0: Display output current (A)
1: Display counter value (c)
2: Display actual output frequency (H.)
3: Display DC-BUS voltage (v)
4: Display output voltage (E)
5: Display output power angle (n)
6: Display output power in kW (P)
8: Display estimate output torque % (t)
10: Display PID feedback in % (b)
11: Display AVI1 in % (1.)
12: Display ACI in % (2.)
a
00-04
Content of Multi-function
Display (User Defined)
13: Display AVI2 in % (3.)
14: Display the temperature of IGBT in °C (i.)
15: Display the temperature of heat sink in °C (c.)
16: The status of digital input (ON/OFF) (i)
17: The status of digital output (ON/OFF) (o)
18: Multi-step speed (S)
19: The corresponding CPU pin status of digital input (d.)
20: The corresponding CPU pin status of digital output (0.)
25: Overload counting (0.00~100.00%) (h.)
26: Ground Fault GFF (Unit :%)( G.)
27: DC Bus voltage ripple (Unit: Vdc) (r.)
28: Display PLC data D1043 (C)
30: Display output of user defined (U)
31: H page x Pr.00-05 Display user Gain(K)
00-05
00-06Software version
a
00-07
Coefficient Gain in Actual
Output Frequency
Parameter Protection
Password Input
0~160.000
0.00~655.35
0~65535
0~4 : Recording # of times of password attemps
0~65535
a
00-08
Parameter Protection
Password Setting
0 : No password protection / password is entered correctly
(Pr00-07)
1 : Parameter is locked
Bit 0: Group 0
Bit 1: Group 1
Bit 2: Group 2
Bit 3: Group 3
a
00-09Display advanced parameters
Bit 4: Group 4
Bit 5: Group 5
Bit 6: Group 6
Bit 7: Group 7
Bit 8: Group 8
Bit 9: Group 9
00-10Velocity Control Mode
a
00-11Loading mode selection
0 : VF (V/F control)
2 : SVC (Sensor-Less Vector Control)
0 : Normal duty
1 : Heavy duty
Factory
Setting
0
0
0
0
0
0
0
0
0
63-4528—0498
CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
ParameterFunctionSetting
2~15kHz
00-12Carrier Frequency (KHz)
2~10kHz
2~9kHz
00-13
PLC command mask (SOOC,
SOOF)
0~65535
0: Digital keypad
1: RS-485 serial communication
a
00-14
Source of the MASTER
Frequency Command (AUTO)
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
0: Digital keypad
a
00-15
Source of the Opertaion
Command (AUTO)
1: External analog input (Pr.03-00)
2: RS-485 serial communication
3: External UP/DOWN terminal
5: Communication card ( not included CANopen card)
a
00-16Stop method
a
a
00-17
00-18
Motor Operating Direction
Control
Memory of Communication
Frequency Command
0: Ramp to stop
1: Coast to stop
0: Enable forward/reverse
1: Reverse disable
2: Forward disable
Read Only
Bit 0~3: user defined on decimal places
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
00-19User Defined Property
0011b: three decimal place
Bit 4~15: user define on unit
000xh: Hz
001xh: rpm
002xh: %
003xh:kg
0: Disable
0000b: 0~65535 (No decimal place in Pr.00-19 setting)
0001b: 0.0~6553.5 (One decimal place in Pr.00-19
00-20Max. User Defined Value
setting)
0010b: 0.0~655.35(Two decimal place in Pr.00-19 setting)
0011b: 0.0~65.536 (Three decimal place in Pr.00-19
setting)
230V
460V
230V
460V
230V
460V
Normal duty:
1~20hp
Heavy duty:
0.5~15HP
Normal duty:
1~25hp
Heavy duty:
0.5~20HP
Normal duty:
25~60hp
Heavy duty:
20~50hp
Normal duty:
30~100hp
Heavy duty:
25~75hp
Normal duty:
75~125hp
Heavy duty:
60~100hp
Normal duty:
125~536hp
Heavy duty:
100~475hp
Factory
Setting
8
6
4
0
Read
Only
2
1
1
1
Read
Only
0
0
9963-4528—04
CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
ParameterFunctionSetting
00-21User Defined ValueRead Only
0: Standard HOA
1: LOC/REM not maintain
00-22Local / Remote Selection
2: REM maintain
3: LOC maintain
4: LOC/REM maintain
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
a
00-23
Source of the Master
Frequency Command
(HAND)
8: Communication card (no CANopen card)
0: Digital keypad
a
00-24
Source of the Operation
Command (HAND)
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication card
5: Communication card (not include CANopen card)
00-25
Digital Keypad STOP
Function
0: STOP key disable
1: STOP key enable
00-26Display Filter Time (Current)0.001~65.5350.100
00-27Display Filter Time (Keypad)0.001~65.5350.100
00-28Software Version (Date Code)0~65535
Factory
Setting
Read
Only
0
0
0
0
Read
Only
63-4528—04100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.