Honeywell H8908C, H8908B User Manual

APPLICATION
Humidity Control
Régulateur d'humidité
-
2
0
°
F
-
1
0
°
F
0
°
F
+
1
0
°
F
+
2
0
°
F
O
v
e
r
2
0
°
F
1
5
%
2
0
%
2
5
%
3
0
%
3
5
%
4
0
%
H
U
M
I
D
I
T
Y
S
E
T
T
IN
G
O
U
T
D
O
O
R
T
E
M
P
E
R
A
T
U
R
E
-
3
0
°
C
-
2
5
°
C
-
2
0
°
C
-
1
0
°
C
-
5
°
C
O
v
e
r
0
°
C
M13371
CASE REMOVAL SLOT
HOLE FOR WIRING THE DUCT MOUNTING INSTALLATIONS
The H8908B Humidistat and H8908C Deh um idi stat (humidity controllers) provide automatic low voltage control of humidifiers and dehumidifiers or venti lator s, respectively, in central heating and air conditioning sys­tems. They have a spst, snap-acting, dust-proof switch and are designed for wall or surface duct mounting.
INSTALLATION
When Installing this Product...
Read these instructions carefully. Failure to follow
1.
them could damage the product or cause a haz­ardous condition. Check the ratings given in the instructions and on
2.
the product to make sure the product is suitable for your application. Installer must be a trained, experienced service
3.
technician. After installation is complete, check out product
4.
operation as provided in these instructions.
CAUTION
Personal Injury Hazard. Power supply can cause electrical shock.
Disconnect power supply before beginning installation.
Location and Mounting
The styling of the H8908 is designed to blend with the latest T8600 family of Honeywell Chronother m ® IV Deluxe Programmabl e Thermostat s . A mounting tem­plate is included for mounting the H8908 next to the T8600. The H8908 can also be mounted at any other convenient location in the living area or equipment room. See Fig 1.
NOTE: The H8908 electrical connections are not
shared with the thermostat.
H8908B Humidistat
H8908C Dehumidistat
INSTALLATION INSTRUCTIONS
Fig. 1. H8908B Humidistat.
Wall Mounting
IMPORTANT
Mount the control in an area with average room temperature and average relative humidity.
The following mounting instructions are for mounting the H8908 on the wall next to the T8600. When install­ing the H8908 at another location, modify the procedure to fit the installation.
Hold the mounting template (included) next to the
1.
T8600. Select the mounting side for the H8908. The template is rever sib le f o r moun ting on either the left or right side of the T8600. See Fig. 2. Mark the holes for the two mounting screws
2.
(included). Then mark the hole for the low voltage wiring on the template that corresponds with the side sel ected in st ep 1. Remove the te mplate and dr ill the holes.
3.
Run low voltage wiring to the location and pull
4.
about 6 in. (152 mm) of wire through the hole. Plug the hole with nonflammable insulation to
5.
prevent drafts from affecting the control opera­tion.
® U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • •All Rights Reserved
69-1341
H8908B HUMIDISTAT H8 908C DEHUMIDISTAT
Remove the H8908 case from the base. See
6.
Fig. 1. Position the base on the wall with the arrow up.
7.
Use the two 1 in. (25 mm) mounting screws to
8.
secure the base to the wall.
THERMOSTAT WALLPLATE
MOUNTING TEMPLATE
RETURN AIR
6 in. (152 mm) MINIMUM
BEST LOCATION
ALTERNATE LOCATION
15 in. (381 mm) MINIMUM
RETURN AIR
MOUNTING
WIRING HOLES FOR MOUNTING ON RIGHT. USE LEFT HOLES FOR MOUNTING ON LEFT.
HOLES (2)
Fig. 2. Positioning mounting template.
IMPORTANT
Use 18- to 22-gauge wire for proper wiring.
Connect the low voltage wires to the leads on the
9.
H8908. Replace the H8908 case.
10.
Duct Mounting
IMPORTANT
When mounting near an elbow area, locate the control 6 in. (152 mm) upstream from the elbow so the element is exposed to the normal airflow (Fig. 3).
4X DRILL 7/64 IN. DIAMETER PERCER 4 X 7/64 PO.
CAUTION
Equipment Damage Hazard. Be careful when selecting control location and cutting hole in ductwork. Do not cut or drill into air conditioning or electrical accessories. Do not install control on supply (hot air) ductwork. To use template:
1. Remove backing and apply template to duct.
2. Cut along template dotted line and drill the
MISE EN GARDE
Risque d'endommager le matériel. Faire attention au moment de choisir l'emplacement du régulateur et de percer les trous dans la gaine. Ne pas couper ou percer les accessoires électriques ou de climatisation. Ne pas installer le régulateur sur la gaine d'alimentation (air chaud). Utilisation du gabarit:
1. Retirer l'endos du gabarit et placer le gabarit
2. Couper le long de la ligne pointillée du gabarit
M13370
1.
2.
3.
4.
5.
6.
7.
8.
9.
IMPORTANT
DUCT TEMPLATE
GABARIT DE GAINE
mounting holes.
sur la gaine. et percer les trous de fixation.
RETURN AIR DUCT
M13369
Fig. 3. Selecting duct location for control.
Locate the control at least 8 in. (203 mm) upstream from the humidifier (or dehumidi fier / ventilator supply) in the return air duct. See Fig. 3. Apply the duct template to the duct location. Use the duct template, Fig. 4, to make the open­ing and mounting holes for the H8908. Remove the H8908 case from the base. See Fig. 1. Position the foam gasket on the H8908 base. Position the base on the duct with the arrow up. Use the four 1 in. (25 mm) mounting screws to secure the base to the duct. Connect the low voltage wires to the leads on the H8908. Replace the H8908 case.
Use 18- to 22-gauge wire for proper wiring.
Fig. 4. Positioning return air duct template.
69-1341 2
M13373
WIRING
M13386
L1 (HOT)
L2
1
2
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
24V WIRING.
HUMIDIFIER
TRANSFORMER
WATER SOLENOID LEAD WIRE
CURRENT SENSING RELAY
C
LO
HI
H8908B
M13385
L1 (HOT)
L2
1
2
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
24V WIRING.
HUMIDIFIER
TRANSFORMER
H8908B
SAIL SWITCH
CAUTION
Personal Injury Hazard. Power supply can cause electrical shock and injury.
Disconnect power supply before installation or servicing.
All wiring must c o mply with applica ble local codes , ordi­nances and regulations. Make wiring connect ion s according to humidifier (or dehumidifier/ventilator) instructions, if available; otherwise, see typical wirin g diagrams in Fig. 5 through 12.
IMPORTANT
Select models of fan centers include humidifer taps so the current sensing relay or sail switch is not needed.
If not using a current sensing relay or sail switch, the humidifier must be energized dur­ing blower motor cycles for proper operation.
On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower. Premature transformer burnout can occur.
On HE360 fan powered humidifier models, only the two yellow wires are connected to the control. The remaining two red wires are only used with electronic humidity controls.
L1
POWER
(HOT) L2
1
2
1
FAN CONTROL
SUPPLY
FURNACE FAN
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
24 VAC WIRING.
MOTOR
Fig. 5. Typical wiring diagram for
system with fan interlock.
H8908B
TRANSFORMER
HUMIDIFIER
2
M13368
H8908B HUMIDISTAT H8908C DEHUMIDISTAT
Fig. 7. Typical wiring diagram of current
sensing relay with humidifier.
Fig. 8. Typical wiring diagram of sail switch with humidifier.
FAN WIRING
H8908B
1
NOTE:
TERMINALS
1
HUMIDISTAT TERMINALS
24V WIRING.
FOLLOW THE INSTALLATION INSTRUCTIONS INCLUDED WITH THE STEAM HUMIDIFIER TO WIRE THE SYSTEM FAN.
1
HUMIDIFIER
TO SYSTEM FAN
M13387
Fig. 9. Typical wiring diagram for steam humidifiers.
H8908C
CHRONOTHERM® IV THERMOSTAT
L1
POWER
(HOT)
SUPPLY
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VAC WIRING.
Fig. 6. Typical wiring diagram for system
DPST SWITCHING RELAY
2-SPEED
HL
FAN MOTOR
C
with 2-speed fan motor.
2
TRANSFORMER
HUMIDIFIER
B
O
HEATING RELAY OR VALVE COIL
COOLING CONTACTOR COIL
WY
FAN RELAY COIL
H8908BFAN CONTROL
1
PROVIDE OVERLOAD PROTECTION AND
M13384
DISCONNECT MEANS AS REQUIRED.
Fig. 10. T ypical par allel wirin g of humidity con troller
with Chronotherm® IV Thermostat for
dehumidification and mildew control.
R
G
1
M13366
3 69-1341
H8908B HUMIDISTAT H8908C DEHUMIDISTAT
CHRONOTHERM® IV THERMOSTAT
BO
1
Fig. 11. Typical series wiring of humidi t y c ont r ol ler
W
Y
HEATING RELAY OR VALVE COIL
COOLING CONTACTOR COIL
PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.
with Chronotherm® IV Therm ost at fo r
dehumidification and m i ldew control.
H8908C
Fig. 12. Typical wiring diagram for HR150,
HR200, ER150 and ER200 Ventilator
or HD220 Dehumidifier appli cat io ns.
FAN RELAY COIL
VENTILATOR/DEHUMIDIFIER
G
DEHUMIDISTAT TERMINALS
R
H8908C
1
M13383
M13367
ADJUSTMENTS
Humidity Control Adjustment
To maintain optimum humidity control without causing condensation on cold surfaces such as windows, the homeowner must adjust the setpoint as the outdoor temperature changes.
To reduce the relative humidity, reduce the setpoint approximately three percent relative humid it y ever y 24 hours. To increase the relative humidity, increase the sepoint approximately three percent re lative humidity every 24 hours.
Setpoint Adjustment
Set the humidity setpoint according to the prevailing outdoor temperature. See Table 1 for recommended settings.
Table 1. Recommended Humidity
Controller Settings.
Outdoor Temperature Recommended
-20 -29 15
-10 -23 20 0-18 25
+10 -12 30 +20 -7 35
>+20 >-7 40
Controller Setting°F °C
Humidity
OPERATION AND CHECKOUT
Place the system in operation and observe through at least one complete cycle to make certain that all com­ponents are functioning properly.
Home and Building Control Home and Building Control
Honeywell Inc. Honeywell Limited-Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P.O. Box 524 North York, Ontario Minneapolis, MN 55408-0524 M2H 3N7
69-1341 G.H. 10-99 Printed in Taiwan R.O.C. www.honeywell.com
Loading...