Honeywell H8908D, H8908C, H8908B, H8908A User Manual

Place Bar Code Here
H8908A/B Humidistat;
CAUTION
H8908C/D Dehumidistat
INSTALLATION INSTRUCTIONS
APPLICATION
The H8908 family of low-voltage humidistats/ dehumidistats provide accurate control of whole house humidifiers, dehumidifiers, and ventilators. They have a snap-acting, dust-proof SPST switch and can be mounted to a duct or wall.
Before Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
Fig. 1. H8908A,D control.
M24726
Personal Injury Hazard. Power supply can cause electrical shock.
Disconnect power supply before beginning installation.
NOTE: The H8908 electrical connections are not
shared with the thermostat.
OUTDOOR
TEMPERATURE
-20 F
-30 C
-10 F
Humidity Control Régulateur d'humidité
HOLE FOR WIRING THE DUCT MOUNTING INSTALLATIONS
0 F +10 F +20 F
Over 20 F
Over 0 C
CASE REMOVAL SLOT
-25 C
-20 C
-10 C
-5 C
Fig. 2. H8908B,C control.
HUMIDITY SETTING
15%
20% 25% 30%
35% 40%
M13371
69-1341EF-07
H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT
DUCT INSTALLATION
1. Choose a location on the duct.
ALTERNATE LOCATION
RETURN AIR
6 in. (152 mm) MINIMUM
BEST LOCATION
RETURN AIR DUCT
15 in. (381 mm) MINIMUM
Fig. 3. Duct installation locations.
2. Apply sticker template to duct and drill holes for
mounting screws. Cut along the dotted line of the template with metal shears or tin snips.
Fig. 4. Drill and cut holes in duct.
3. Run two-fan, low-voltage wire to the mounting loca-
tion on the duct. See Fig. 5.
IMPORTANT
Use rated 18-22 gauge wire. Leave approximately 6 in. of wire to properly connect the humidistat.
RETURN AIR
M13369
M24800
REMOTE MOUNT INSTALLATION
1. Choose a location in the living area.
NOTE: Select a location clear of drafts or excessive
humidity. Avoid mounting near doors or win­dows, or in bathrooms or kitchens. See Fig. 6.
Fig. 6. Choose a location in the living area.
2. Cut 1 in. diameter wire hole in wall.
3. Run two-fan, low-voltage wire to the mounting loca-
tion in the living area.
IMPORTANT
Use rated 18-22 gauge wire. Leave approxi­mately 6 in. of wire to properly connect the humi­distat.
M24718
RETURN
SUPPLY
TWO-FAN 18-22 GAUGE WIRE
M24720
Fig. 5. Run wire to the mounting location.
69-1341EF—07 2
M24721
Fig. 7. Run wire to the mounting location.
H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT
M24722
4. Remove the base bracket from the humidistat. For
duct mount, slide the black gasket onto the base bracket. See Fig. 8.
NOTE: Use gasket only when mounting the control to
ductwork. Leave off when mounting to a wall.
M24733
Fig. 8. Seal base bracket.
5. Secure the base bracket to the duct or remote loca-
tion. Secure to the duct with four 1-in. (25 mm) screws (provided) or to the wall with two 1-in. (25 mm) screws (provided).
Fig. 9. Mount base bracket to duct or remote location.
3 69-1341EF—07
H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT
CAUTION
WIRING
Personal Injury Hazard. Can cause electrical shock and injury.
Disconnect power before installation or servicing.
All wiring must comply with applicable local codes, ordinances and regulations. Make wiring connections according to humidifier (or dehumidifier/ventilator) instructions, if available; otherwise, see typical wiring diagrams in Fig. 12–19.
IMPORTANT
Select models of fan centers include humidifier taps so the current sensing relay, sail switch or air pressure switch is not needed. If not using a current sensing relay, sail switch, or air pressure switch, the humidifier must be energized during blower motor cycles for proper operation.
On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower. Premature transformer burnout can occur. On HE365 fan powered humidifier mod­els, only the two yellow wires are connected to the control. The remaining two red wires are only used with electronic humidity controls.
6. Using wire nuts, connect the low-voltage wire to the
leads on the H8908 humidistat. See Fig. 6–19 for different wiring configurations.
H8908
30 40
TRANSFORMER
20
10
OFF ON
HUMIDIFIER
L1
POWER
(HOT)
L2
1
12PROVIDE DISCONNECT MEANS AND
FAN CONTROL
SUPPLY
FURNACE FAN MOTOR
OVERLOAD PROTECTION AS REQUIRED.
24 VAC WIRING.
Fig. 12. Wiring H8908 with fan interlock.
L1
POWER
(HOT)
SUPPLY
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VAC WIRING.
FAN CONTROL
HL
C
DPST SWITCHING RELAY
2-SPEED FAN MOTOR
2
TRANSFORMER
Fig. 13. Wiring H8908 with 2-speed fan motor.
50
60
H8908
30 40
20
10
OFF ON
HUMIDIFIER
M24728
2
M24727
50
60
M24734
Fig. 10. Wire the humidistat.
7. Mount the humidistat by hooking the two hinges at
the top of the back cover to the raised edge at the top of the base bracket. Press the bottom of the humidistat in to engage the base hinge. You will hear a “click” when the humidistat is secured.
M24801
Fig. 11. Attach the humidistat to the base.
69-1341EF—07 4
H8908
30 40
50
20
10
OFF ON
TRANSFORMER
CURRENT SENSING RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
24V WIRING.
Fig. 14. Typical wiring diagram of current
sensing relay with humidifier.
2
60
L1
L2
(HOT)
LO
C
HI
1
HUMIDIFIER
WATER SOLENOID LEAD WIRE
M24729
H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT
H8908
AIR
PRESSURE SWITCH/
SAIL SWITCH
2
40
30
50
20
10
60
OFF ON
TRANSFORMER
1
L1
L2
(HOT)
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
24V WIRING.
Fig. 15. Wiring H8908 in line with
air pressure switch/sail switch and humidifier.
TH9421 VISION PRO
THERMOSTAT
H8908B
30 40
20
10
OFF ON
50
60
24 VOLT
TRANSFORMER
HUMIDIFIER
1 2 3
SYSTEM
TRANSFORMER
L2
C
L1
R
M24730B
L2
L1
C
R
COM N.O. N.C.
S688 AIR
PRESSURE
SWITCH/
SAIL SWITCH
HE225/HE265
HUMIDIFIER
Fig. 17. Wiring H8908 with VisionPRO® IAQ on typical 2-stage furnace.
VISIONPRO® THERMOSTAT
Y2 L A W2 S1 S2
RC
R
W
Y
G
C
H8908D
H8908
FAN WIRING
30 40
TERMINALS
50
20
10
60
1
OFF ON
HUMIDISTAT TERMINALS
24V WIRING.
1
FOLLOW THE INSTALLATION INSTRUCTIONS
NOTE:
INCLUDED WITH THE STEAM HUMIDIFIER TO WIRE THE SYSTEM FAN.
HUMIDIFIER
Fig. 16. Wiring H8908 with steam humidifiers.
EQUIPMENT INTERFACE MODULE
1 2 3 C
24 VAC
R RC RH
H1 U M2
D1 H
OR
M2 V1
N T2
H8908D
20
10
30 40
OFF ON
50
60
CONV. HP
W1 W2 W3 Y Y2 G
L NOT USED OUT1 OUT2 IN1 IN2
DATS1
DATS2
STAGE 1
O/B AUX AUX2 Y Y2 G
HEAT
STAGE 2 HEAT
COMPRESSOR
FAN RELAY
C7089U1006
VENTILATOR/DEHUMIDIFIER
TERMINALS
1
TO SYSTEM FAN
M24731
M24724B
HEATING RELAY OR VALVE COIL
COOLING CONTACTOR COIL
FAN RELAY COIL
1
PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
Fig. 18. Wiring H8908 with VisionPRO®
Thermostat for dehumidification.
20
10
30 40
OFF ON
M24725
Fresh Air Ventilation System Système de ventilation à air frais
50
60
Fig. 19. Typical wiring diagram for HR150,
HR200, ER150 and ER200 Ventilator
or DH90 Dehumidifier applications.
M24732
5 69-1341EF—07
Loading...
+ 11 hidden pages