H7012A,B
ROOM HUMIDITY SENSOR/
COMBINED ROOM HUMIDITY/TEMPERATURE SENSOR
PRODUCT DATA
FEATURES 
•  Pt 1000, BALCO 500 or 20k ΩΩΩΩ  NTC temperature
sensing element
• Wide sensing range 
• Capacitance type sensing element for relative 
humidity
•  Plug-in design 
GENERAL 
The H7012A Room Humidity Sensor is a capacitance type 
relative humidity sensor for wall mounting.
The H7012B Combined Room Humidity/Temperature Sensor 
incorporates a capacitance type relative humidity sensor with 
a Pt 1000, BALCO 500 or 20kΩ  NTC temperature sensor in 
one housing.
These sensors are used for control, indication and alarm 
monitoring in room air conditioning installations.
Models 
OS-No.  Temperature Sensor Type
SPECIFICATIONS 
General:
Power supply  24Vac, +20...-30%; 50/60Hz,
34Vdc, +20...-30% 
Current consumption 20mA @ 24V 
Ambient  0...50° C (+32...122° F), 5...95%rh
operating limits  non condensing 
Ambient  -25...70° C (-13...158° F), 5...95%rh
storage limits  non condensing 
Dimensions  see Fig. 2 
Weight  130g 
Case  Plastic ( ABS )
flame retardend acc. to UL94-V0 
Mounting  Wall, surface or wall outlet box 
Protection Standard  IP 30 acc. to EN60529
Safety  Class II acc. to EN60730-1
H7012A1009 
H7012B1007  Pt 1000 
H7012B1015  BALCO 500 
H7012B1023
-
20kΩ  NTC
EN0C-0610 0398R3-MA
 
 
Page 2
H7012A,B ROOM HUMIDITY / TEMPERATURE SENSOR
Temperature:
Temperature sensing 
range  0...50° C (32...122° F)
Nominal value 
 Pt 1000  1000Ω  @ 0°C  
 BALCO 500  500Ω  @ 23.3°C  
 NTC  20kΩ  @ 25°C 
Accuracy 
 Pt 1000  ± 0.3K acc. to DIN IEC 751 Class B 
 BALCO 500  ± 0.4K @ 23.3°C  
 NTC  ± 0.2K at 25°C 
Sensitivity 
 Pt 1000  ≈3.85Ω/K  
 BALCO 500  2Ω/K 
Characteristic  see EN0C-0603 
Response time @ air velocity 0.02...0.07m/s
 τ 
0.5 Pt 1000
 τ 
0.5 Balco 500
 τ 
0.5 NTC
 =50s
 =140s
=134s
Overview
Following sensors can be applied for the following control 
systems:
Relative Humidity:
Humidity sensing 
range  5...95%rh 
Output signal  0...1V / 0...10V =  0...100%rh
Output Impedance 
 1V range  183Ω  
 10V range  274Ω 
Outputs short circuit protected 
Sensitivity  10mV / %rh or 100mV / %rh 
Accuracy
  5...10%rh  ±10% 
 10...30%rh  ±  5%
 30...70%rh  ±  3%
 70...90%rh  ±  5%
 90...95%rh  ±10% 
τ
Response time
0.5
=20s
Control systems  Temperature  Humidity
Pt 1000  20kΩ ΩΩΩ NTC  BALCO 500  0...1Vdc  0...10Vdc
Excel Classic  X  X  X  X 
Excel Plus  X  X  X  X 
High Performance Excel Plus  X  X  X  X 
Excel EMC  X  X  X  X 
Excel 500/600 (XF521)  X  X  X 
Excel 500/600 (XF526)  X  X  X  X 
Excel 20 & 50  X  X 
Excel 80B & 100B  X  X  X 
Excel IRC Multicontroller
R7451A1030 
MicroniK 100  X  X 
MicroniK 100 “NEW“
R7420B1036/R7420F1045 
MicroniK 200  X  X  X  X
XX X
XX
EN0C-0604 0796R2-MA  2
 
 
Page 3
DIMENSIONS 
H7012A,B ROOM HUMIDITY / TEMPERATURE SENSOR
80 (3.15)
Honeywell
Honeywell
Honeywell Honeywell
130
(5.12)
Dimensions in mm and (in ch)
20
(0.79)
(1.34)
34
Fig. 1 Dimensions
11
(0.43)
5 mounting holes 4mm (0.16) dia. 
for 3 (2) screws 3.5mm (0 .14) dia. 
mounted in positions 1 (preferred) or 2.
1
2
1,2
2
1
60 (2.36)
30
(1.18)
60
(2.36)
107
(4.21)
INSTALLATION 
230Vac
Transformer f or 
sensors and actuators
24Vac
Sensor
1
27
0...1V/
0...10V
5 / 6
Common
Fig. 2 Installation Example
Controller
rh Input
Common
24Vac  230Vac
Transformer f or 
controller
3  EN0C-0610 0398R3-MA
 
 
Page 4
H7012A,B ROOM HUMIDITY / TEMPERATURE SENSOR
Mounting and Installation Advice:
• = Mount these units at the inside wall of the room to be  
heated or air conditioned, away from doors, windows 
and heat sources.
• = Do not mount in niches, book shelves, behind cabinets  
or curtains or where it could be exposed to solar 
radiation.
• = Seal the conduit opening to avoid false measurement  
due to draught from the conduit.
• = Provide sufficient air circulation. 
Offset due to wire resistance per 10m distance from sensor 
to controller:
Type of wire  Temperature offset
Pt 1000  BALCO 500  NTC
2
0.5mm
(AWG20)
1.0mm
(AWG17)
1.5mm
(AWG15)
0.18° C (0.324° F)  0.3° C (0.54° F)
2
0.09° C (0.162° F) 0.15° C (0.27° F)  negligible
2
0.06° C (0.108° F)  0.1° C (0.1° F)
Wiring connection
NOTE
CAUT I O N 
Use shielded wiring in areas with high EMI. 
Keep 15cm (5.9’’) minimum distance between 
sensor lines and 230Vac power lines.
Use two transformers: one for sensors and 
actuators and one for the controller (see Fig. 3).
Wiring run  Maximum length
Sensor to controller  200m (660ft)
24V
1
24V
2 
3 
4 
5 
6
7
Pt 1000/NTC/ 
BALCO 500
0...1V
0...10V 
COM = 24V
8 
9
10
Home and Building Control Products
Honeywell AG 
Böblinger Straβ e 17 
D-71101 Schönaich 
Phone: (49) 7031 63701 
Fax:   (49) 7031 637493 
http://europe.hbc.honeywell.com
POWER SUPPLY
TEMPERATURE SENSOR
REL. HUMIDITY SENSOR
1 2 3 4 5   6  7   8  9  10
Fig. 3 Installation
Subject to change without notice. Printed in Germany  Manufacturing location certi fied to
EN0C-0610 0398R3-MA