Honeywell System 800, Gent System 800 Operator's Manual

by Honeywell
Operator’s Manual & Log book
System 800
Fire Alarm Panel
2 796689 (4188-658) i2_04/07
Table of Contents
Scope 4 General description 5
User responsibility 6
Daily 6 Weekly 6 Quarterly 7 Battery replacement 7
Controls and indicators 8 Navigation 8 Access levels 9
To enter access level 2 9 To return to access level 1 10
Normal Condition 11
To conduct a display test 11
Fire condition 12
To verify fire 13 To cancel buzzer 13 To silence alarms 13 To reset the system 13
Manual control of fire alarms 14
To sound alarms 14 To silence alarms 14
To operate delay mode 15 Fire Test 16
To enter fire test mode 16 To exit Fire test mode 17
Fault condition 18
To Cancel buzzer 18
Disablement condition 20
Typical disablement 20
System information 21
To view active fire events 21 To view active fault events 21 To view active disablement 22 To view historic events 22
796689 (4188-658) i2__04/07 3
System set up 23
Hardware link 23 To enable or disable a zone 24 To edit a zone label 25 To put a zone in and out of test mode 26 To view devices in a zone 27 To enable or disable a device 28 To edit a device label 29 To enable or disable alarm sounders 30 To set up weekly reminder of fire test 31 To set up the Initial and Verify delay 32
Other controls 33
Loop status 33 Local input 33 Loop map 33 Auxiliary relay 34 Fire routing output 34 Fault routing output 34 Maintenance reminder 34
Appendix 35
Glossary of terms 35
Description of Controls and Indicators36
Controls at the system 800 panel 37 Indicators at the system 800 panel 38
Menu 43 Controls and indicators 43
4 796689 (4188-658) i2_04/07
Scope
Safety
Associated documents
This second issue of the Operator’s manual covers the operating instructions for the 24-zone system 800 fire alarm panel. The manual shows how to operate controls and interpret light indications and messages. It includes information on user responsibility and emergency conditions with step by step instructions on how to operate controls. The manual has also a log book with pages to record system events for future reference.
The following information is given in the interest of personal safety and to prevent damage to equipment installed and to ensure the system operates correctly.
The information symbol is accompanied with important text.
This can be either a warning to prevent personal injury or death, or a caution to prevent damage to the system equipment.
Installer’s manual 796688 (4188-657)
All the documents associated with the panel should be kept together near the panel.
Issue Record
Issue Date Comment
1 11/12/00 This is the first issue of the operating manual.
1-1 06/02/01 Minor updates to improve instructions.
2 10/06/03 This is the second update to the installer’s manual include
coincidence detection, sector linking, improvements to the
settings for delay mode and auxiliary relay configuration.
23/04/07 Gent by Honeywell logo added
796689 (4188-658) i2__04/07 5
General description
The system 800 fire alarm panel is designed to meet the requirements of EN54 Parts 2 and 4. It is suitable for installation in small to medium size buildings in accordance with the recommendations of BS5839:Part 1, to provide an automatic fire detection and alarm.
The system 800 panel is installed and configured to monitor devices such as detectors, manual call points and sounder control transponder units connected on a single loop. Each device is capable of being addressed individually and may be assigned to one of 24 zones. The devices and zones in the system can each be given a label for identification. In the event of a fire the panel automatically operates external sounder circuits to raise an alarm in the protected buildings.
The push button controls on the panel are for use by authorised and trained personal.
To comply with the requirements of BS5839:Part 1, there are log sheets provided at the back of this manual for recording system events.
6 796689 (4188-658) i2_04/07
User responsibility
Daily
Weekly
It is recommended that the persons responsible for the fire alarm system should become familiar with:
How to operate the controls
How to interpret visual indications given.
BS 5839:Part 1, states that the system should be inspected daily to ensure that a normal indication is given at the control and indicating equipment and:
any previously indicated fault and
warning condition has received appropriate attention.
all the system events are entered into
the Log Book for future reference.
the use of the area(s) inspected has not
changed since the system was designed.
and no unsafe practices that could lead
to a fire are being undertaken.
At weekly interval:
a different Fire Sensor or Manual Call
Point of the system should be tested to ensure the system is capable of operating under alarm condition.
the operation of the alarm sounders
should be checked to also remind those occupying the premises that there is a fire alarm system with a particular sound.
The test should be performed at a regular time to avoid confusion between a test and a genuine fire alarm.
796689 (4188-658) i2__04/07 7
Quarterly
Battery replacement
At quarterly intervals the fire alarm system should be inspected by the servicing organisation. A trained maintenance engineer from the servicing organisation should carry out any work necessary.
For help with service and maintenance contact your Servicing organisation, see log book.
Every four years the batteries installed in the system 800 panel must be replaced.
CAUTION:
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
8 796689 (4188-658) i2_04/07
Controls and indicators
Audible
indication
While reading the instructions it may help to open out the back page of this manual to view the location of controls and indicators on the panel. For description of controls and indicators see User controls and indicators section.
There is a cancellable buzzer in the panel that operates automatically to announce Fire and Fault events.
Navigation
Previous
Next
Esc
The buttons to navigate the menu and to select a menu option at the panel are the Enter, Previous, Next and Esc buttons.
The Enter button will display the top-level menu or accept a selection.
The menu bar displayed here shows the menu available at access level 1.
The Previous and Next buttons can be used to scroll and select a menu option.
The Esc button performs a quit function.
Pressing the Esc button will close an open menu or sub-menu and return it to the previous display.
796689 (4188-658) i2__04/07 9
Access levels
Access level 1 (A1)
Access level 2
(A2)
To enter access level 2
The instructions in this manual are for access to menu options and push button controls available at access levels 1 and 2.
Access level 1 is for the general public and requires no coded entry, and at this level the light indications of the panel are visible, along with menu options to view logs and gain coded entry to level 2.
Access level 2 is for authorised persons who are responsible for the fire alarm, such as security staff. This level requires a coded entry to the panel’s push button controls and menu options. If controls are not used for 3 minutes duration then access level 2 is automatically exited.
Press the Enter button to display the
menu bar.
Select System menu and option Code,
and then press the Enter button to display the Access code entry form.
Enter the numerical
access code for level 2 controls and menu options. An asterisk will appear on the display for
every number entry.
Press Enter to accept the code.
The factory set codes for:
Access level 1 – None Access level 2 - 2222
An acknowledgement is given of correct code entry.
10 796689 (4188-658) i2_04/07
To return to access level 1
Esc
Alternative method
Previous
Next
To exit access level 2 and return to access level 1.
Press the Esc button to exit to level 1.
Press Enter to accept a return to level 1
and the display will respond with the access level changed message.
Press the Enter button to display the top-
level menu.
Press the Previous or Next button to
‘System’ option and scroll through the menus to highlight Exit to level 1 option.
Press Enter to exit to access level 1.
796689 (4188-658) i2__04/07 11
Normal Condition
Power
The green LED is normally lit giving a steady to indicate that mains and battery supply to the panel are healthy.
To conduct a display test
A2
Esc
Display Test
The panel lights and display can be tested to check that they are working.
The Display Test is factory set to operate at access level 2.
Enter access level 2.
Press the Esc key to exit the menu
screen.
The display test can only operate if the default screen is displayed.
Press the Display Test button.
All the light indicators are lit on the panel and will remain lit for a short duration.
The display pixels are also tested.
12 796689 (4188-658) i2_04/07
Fire condition
Fire
Fire Routing
Activated
Fire Protection
Activated
Fire event(s) from detectors or manual call points in zone(s) are indicated and logged at the panel.
The red Fire light is lit.
The first fire information is given in the top portion of the display, while the latest fire in the lower portion.
The local buzzer sounds to announce each fire event.
If the facilities are available and configured for use, then the Fire Routing and Fire
Protection lights are lit
.
System alarm sounders are active.
Follow site evacuation procedures.
Number of active fires
First fire: Zone number
Device or location label
Latest fire Device of location label
First fire: device number
Number of zones in fire
796689 (4188-658) i2__04/07 13
To verify fire
Delay
A2
Veri fy
Verification
If delay mode is ON, that is if the Delay light is lit, the alarm sounders are inactive for a 30 seconds (factory set) duration. During this time the alarm delay can be extended by a pre-configured time (up to 10 minutes maximum) by operating the Verify button.
Enter access level 2.
Press the Verify button.
The verification light is lit to show the fire alarm delay has been extended.
NOTE: Operating Sound Alarms button or if there is a subsequent fire event the alarms are activated immediately.
To cancel buzzer
Cancel Buzzer
To silence the panel buzzer while the system is in fire condition:
Press the Cancel Buzzer button.
To silence alarms
A2
Silence Alarms
To stop the fire alarm sounders from sounding, for example once the building has been evacuated and the fire fighters are present to attend to the fire.
Enter access level 2.
Press the Silence Alarms button.
To reset the system
A2
Reset
After the emergency is over and the affected devices have been restored for normal operation and alarms have been silenced:
Enter access level 2
Press the Reset button.
14 796689 (4188-658) i2_04/07
Manual control of fire alarms
To sound alarms
A2
Sound Alarms
To manually sound alarms in the system at anytime or resound the alarms after they have been silenced:
Enter access level 2.
Press the Sound Alarms button.
Note the alarms are sounding!
To silence alarms
A2
Silence Alarms
To stop the alarms from sounding:
Enter access level 2.
Press the Silence Alarms button.
Note the alarms are silenced!
Loading...
+ 30 hidden pages