This thermostat provides electronic control of 24 VAC single-stage and multi-stage
heating and cooling systems, or 750 mV heating systems.
System Types
(up to 2 heat/2 cool)
•Gas, oil, or electric heat with air
conditioning
•Warm air, hot water, high-efficiency
furnaces, heat pumps, steam, gravity
•Heat only — two-wire systems,
power to open and close zone
valves (Series 20), and normallyopen zone valves
•Heat only with fan
•Cool only
•750 mV heating systems
Power Options
•Battery power only
•Common wire only
•Common wire with battery backup
Changeover Options
•Selectable manual or
auto-changeover modes
System Settings
•Heat, Off, Cool,Auto, Em Heat
Fan Settings
•Auto, On
Must be installed by a trained, experienced technician
•Read these instructions carefully. Failure to follow these instructions can
damage the product or cause a hazardous condition.
•Check the ratings in this booklet to verify that this product is suitable for your
application (see page 17).
•Always test for proper operation after installation (see page 13).
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
Install the thermostat about 5 feet (1.5m) above the floor in an area
with good air circulation at average temperature.
NO
Do not install in locations where the thermostat can be affected by:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Sunlight or radiant heat from appliances
• Concealed pipes or chimneys
• Unheated/uncooled areas such as an outside wall behind the thermostat
NO
1
Installation Guide
Pre-installation checklist
Package contents
Check to make sure your package includes the following items:
Quick
FocusPRO™TH6220D
programmable thermostat
(wallplate attached to back)
reference
card
Operating manual
Wall anchors and
mounting screws
(2 each)
AA alkaline
batteries (2)
Required tools & supplies
•No. 2 Phillips screwdriver
•Small pocket screwdriver
•Drill
•Drill bit (3/16” for drywall, 7/32” for plaster)
•Hammer
•Pencil
•Electrical tape
•Level (optional)
2
FocusPRO™TH6220D Programmable Thermostat
Wallplate installation
Insert finger into wire hole and pull to
remove wallplate from thermostat.
Insert quick reference card
Remove the wallplate from the thermostat as shown at left, then follow
directions below for mounting.
1Insert quick reference card in slot
in back of thermostat.
2Pull wires through wire hole.
3Position wallplate on wall, level and
mark hole positions with pencil.
4Drill holes at marked positions as
shown below, then tap in supplied
wall anchors.
5Place wallplate over anchors, insert
and tighten mounting screws.
Drill 3/16” holes for drywall.
Drill 7/32” holes for plaster.
Wall anchors
Mounting screwsWire hole
3
Installation Guide
Wiring
CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
Keep wires in this
shaded area
Heat Pump
Conventional
NOTES
R & Rc terminals
In single-transformer system, leave metal
jumper in place between R & Rc. Remove
metal jumper if two-transformer system.
C terminal
The C (common wire) terminal is optional
when thermostat is powered by batteries.
W (O/B) terminal
If thermostat is configured for a heat pump
in the Installer Setup, configure changeover
valve for cool (“O” factory setting) or heat
(“B”).
L terminal (Output)
Heat pump reset. L terminal powered continuously when thermostat is set to Em Heat.
Configure thermostat for 2 heat / 1 cool heat
pump in the Installer Setup.
Wire specifications
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
Wiring
1Loosen screw terminals, insert
wires into terminal block, then
re-tighten screws.
2Push excess wire back into the
wall opening. Keep wires in shaded
area as shown at left.
3Plug the wall opening with non-
flammable insulation to prevent
drafts from affecting thermostat
operation.
Terminal Designations
Conventional Terminal Letters:
Y22nd stage compressor contactor
W2 2nd stage heat relay
GFan relay
W1st stage heat relay
CCommon wire from secondary side of
cooling system transformer
Y1st stage compressor contactor
RHeating power. Connect to secondary
side of heating system transformer.
RcCooling power. Connect to secondary
side of cooling system transformer.
Heat Pump Terminal Letters:
LHeat pump reset. L terminal powered
continuously when System is set to Em
Heat.
EEmergency heat relay
Aux Auxiliary heat relay
GFan relay
O/B Changeover valve for heat pumps
CCommon wire from secondary side of
cooling system transformer.
YCompressor contactor
RHeating power. Connect to secondary
side of heating system transformer.
RcCooling power. Connect to secondary
side of cooling system transformer.
4
FocusPRO™TH6220D Programmable Thermostat
Wiring diagrams
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
In Installer Setup, set system type to 1Heat/1Cool Heat Pump
In Installer Setup, set system type to 2Heat/1Cool Heat Pump
L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
In Installer Setup, set system type to 1Heat/1Cool Heat Pump
In Installer Setup, set system type to 2Heat/1Cool Heat Pump
L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool
Typical 1H/1C heat pump systemTypical heat-only system
.
& changeover valve to 0 or B.
.
conventional.
6
FocusPRO™TH6220D Programmable Thermostat
Wiring diagrams
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
In Installer Setup, set system type to 1Heat/1Cool Heat Pump
In Installer Setup, set system type to 2Heat/1Cool Heat Pump
L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool
Typical heat-only system with fanHeat-only system (Series 20)
.
& changeover valve to 0 or B.
.
conventional.
7
Installation Guide
Wiring diagrams
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
In Installer Setup, set system type to 1Heat/1Cool Heat Pump
In Installer Setup, set system type to 2Heat/1Cool Heat Pump
L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool
Typical cool-only systemHeat-only system (normally open zone valve)
.
& changeover valve to 0 or B.
.
conventional.
8
FocusPRO™TH6220D Programmable Thermostat
Wiring diagrams
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
In Installer Setup, set system type to 1Heat/1Cool Heat Pump
In Installer Setup, set system type to 2Heat/1Cool Heat Pump
L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool
Typical 2H/2C system (1 transformer)Typical 2H/1C heat pump system
.
& changeover valve to 0 or B.
.
conventional.
9
Installation Guide
Power options & mounting
AC Power
The thermostat can be powered by 24
VAC power, or by batteries.
Connect common
side of transformer
to “C” terminal
Jumper
To wire the thermostat for AC power,
connect the common side of the cooling transformer to the “C” terminal as
shown at left.
I
Immppoorrttaanntt::
Remove R/Rc jumper for
2-transformer systems only. (See wiring
diagram on page 5.)
Battery Power
The thermostat can be powered by
batteries alone or, if used with AC
power, can provide backup power.
During power interruptions the
batteries will save time/day settings
and power the display.
Install batteries in back of thermostat
(optional if AC powered).
After installation, batteries can be
changed without removing the thermostat from the wall (see page 15).
To Mount Thermostat
Align the 4 tabs on the wallplate with
corresponding slots on the back of the
thermostat, then push gently until the
thermostat snaps in place.
10
FocusPRO™TH6220D Programmable Thermostat
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
FAANN
To begin, pr
buttons until the display changes
ess and hold the and
F
Setup FunctionSettings & Options
1
System type
0 Gas, oil or electric heat with air conditioning
11 heat/1 cool heat pump
2Heat only (2-wire systems/power to open & close zone valves/
normally open zone valves)
3Heat only with fan
4Cool only
52 heat/1 cool heat pump
62 heat/2 cool conventional
72 heat/1 cool conventional
81 heat/2 cool conventional
Function
number
1
Press or to change settings
Press
Press
NNEEXXTT
to advance to next function
DOONNEE
D
to exit and save settings
Setting
0
NextDone
2
Changeover valve
(O/B terminal)
3
Fan control
(heating)
5
Heat cycle rate
(CPH: cycles/hour)
6
Second stage heat
cycle rate/
Auxiliary heat
(CPH)
0 Changeover valve (O/B terminal energized in cooling)
1Changeover valve (O/B terminal energized in heating)
0 Gas or oil furnace — equipment controls fan in heating
1Electric furnace — thermostat controls fan in heating
5 For gas or oil furnaces of less than 90% efficiency
1For steam or gravity systems
3For hot water systems & furnaces of over 90% efficiency
9For electric furnaces
1Auto changeover (Heat/Cool/Auto/Off)
2Auto changeover only (Auto) **See page 14
™
1On**See page 14
0Off
0 Fahrenheit
1Celsius
5 Five-minute compressor off time **See page 14
[Other options: 0, 1, 2, 3 or 4-minute off time]
0 5/2 (programmable weekdays and weekends)
15/1/1 (weekdays, Saturday & Sunday programmable)
90Highest heating temperature setting
40-89 Heating temperature range (increments of 1°F, or 0.5°C)
**See page 14
28
Cool temperature
range stops
50Lowest cooling temperature setting
51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
12
FocusPRO™TH6220D Programmable Thermostat
Installer system test
Follow the procedure below to test the heating, cooling and fan.
To begin, press and hold theand
buttons until the display changes
System TestSystem Status
10
Heating system
0Heat and fan turn off
1Heat turns on. Fan also turns on immediately if Function 1 is set
to “1” or “5,” or if Function 3 is set to “1”
2Second stage heat turns on
System test
number
System
status
10
Press to turn on system
Press to turn off system
NEEXXTT
Press
Press
N
to advance to next test
D
DOONNEE
to terminate system test
**See page 11
0
NextDone
20
Emergency
heating system
30
Cooling system
40
Fan system
70
Thermostat
information
(for reference only)
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
0Heat and fan turn off
1Heat and fan turn on
2Second stage heat turns on (Aux)
0Compressor and fan turn off
1Compressor and fan turn on
2Second stage compressor turns on
0Fan turns off
1Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
13
Installation Guide
Auto Changeover (Setup Function 12)
Auto Changeover is a feature used in
climates where both air conditioning and
Set Clock/Day/
Schedule
Fan
Auto
System
Auto
heating are used on the same day.When the
system is set to Auto, the thermostat
automatically selects heating or cooling
depending on the indoor temperature.
Heat and cool settings must be at least 3
degrees apart.The thermostat will automatically
adjust settings to maintain this 3-degree
separation (called “deadband”).
The 3-degree separation between heating
and cooling set temperatures is fixed, and
cannot be changed.
Adaptive Intelligent Recovery™(Setup Function 13)
Adaptive Intelligent Recovery eliminates guesswork when setting your schedule. It
allows the thermostat to “learn” how long your furnace and air conditioner take to
reach the temperature you want.
Just set your program schedule to the time you want the house to reach your
desired temperature.The thermostat then turns on the heating or cooling at just the
right time to reach your scheduled temperature at your scheduled time.
For example:Set the Wake time to 6 am, and the temperature to 70°.The heat will
come on bef
ore 6 am, so the temperature is 70° by the time you wake at 6.
Built-in compressor protection (Setup Function 15)
Inside
°
75
Set Clock/Day/
Schedule
Message flashes until safe
restart time has elapsed
6:30
Fan
Auto
AM
System
Cool
Setting
75
Cool On
Cool
This feature helps prevent damage to the
°
compressor in your air conditioning or heat
pump system.
Damage can occur if the compressor is restarted too soon after shutdown.This feature
forces the compressor to wait for a few
minutes before restarting.
During the wait time, the message Cool On
or Heat On (heat pumps only) will flash on
the display.When the safe wait time has
elapsed, the message stops flashing and the
compressor turns on.
14
FocusPRO™TH6220D Programmable Thermostat
Quick reference to controls
Digital display screenBattery holder (see page 10)
Temperature buttons
Press to adjust temperature
settings
Hold button
Press to override programmed
temperature control
Function buttons
Press to select the function displayed just above each button.
(Functions change depending on the task.)
Quick reference to display screen
Current inside temperature Low battery warning Current time/day
In Recovery
Adaptive Intelligent
Recovery
Current program period
Wake/Leave/Return/Sleep
Set Clock/Day/Schedule
Press to set time, day or
program schedules.
Function buttons
Press the button beneath each function to view or change
settings (functions change depending on the task)
Inside
75
WakeWed
Set Clock/Day/
Replace Battery
°
Schedule
In Recovery
6:30
Fan
Auto
AM
System
Heat
Heat
Setting
°
75
Auxiliary
Heat On
Temperature setting
Auxiliary heat
(Only for heat pumps
with auxiliary heat)
System status
Heat On/Cool On
(If flashing, see page 14)
System setting
Heat/Cool/Auto/Off/
Em Heat
Fan setting
Auto/On
Battery replacement
Press and pull to removeInsert fresh AA
alkaline batteries,
then reinstall
battery holder
15
Installation Guide
In case of difficulty
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank•Check circuit breaker and reset if necessary.
•Make sure power switch at heating & cooling system is on.
•Make sure furnace door is closed securely.
•If thermostat is battery powered, make sure fresh AA alkaline batteries
are correctly installed (see page 10).
Temperature
settings do not
change
Heating system
does not respond
(“Heat On”
appears on
screen)
Cooling system
does not respond
(“Cool On”
appears on
screen)
Make sure heating and cooling temperatures are set to acceptable ranges:
•Heat: 40° to 90°F (4.5° to 32°C).
•Cool: 50° to 99°F (10° to 37°C).
Check temperature range stop settings (Function 27 & 28 on page 12).
•Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
•Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
•Check for loose or broken wires between the thermostat and the heating
equipment.
•Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
•Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
Fan does not
turn on in a call
for heat
Heat pump
issues cool air
in heat mode,
or warm air in
cool mode
Heat/cool both
on at same time,
or heat does
not turn off
•Check for loose or broken wires between the thermostat and the cooling
equipment.
•Check Installer Setup, Function 3 (Fan Control), to make sure the fan
control is properly set to match the type of system (see page 11).
•Check Installer Setup, Function 2 (Changeover Valve), to make sure it is
properly configured for your system (see page 11).
•Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating/cooling equipment (see page 11).
•Check to make sure heating and cooling wires are not shorted together.
16
FocusPRO™TH6220D Programmable Thermostat
In case of difficulty
Heating equipment is running
in cool mode
Cannot change
system setting
to “Heat”
Cannot change
system setting
to “Cool”
“Heat On” is
not displayed
“Cool On” is not
displayed
“Cool On” or
“Heat On”
is flashing
•Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating/cooling equipment (see page 11).
•Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating equipment (see page 11).
•Change Installer Setup, Function 12 (System Setting) to Manual
Changeover (see page 12).
•Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed cooling equipment (see page 11).
•Change Installer Setup, Function 12 (System Setting) to Manual
Changeover (see page 12).
•Change the System Setting to Heat
the current room temperature.
•Change the System Setting to Cool
the current room temperature.
•Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
, and set the temperature level above
, and set the temperature level below
or Auto
or Auto
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Battery holder ......................................................Part Number 50007072-001
Cover plate assembly ........................................Part Number 50002883-001
(Use to cover marks left by old thermostats.)
Specifications
Temperature Ranges
•Heat: 40° to 90°F (4.5° to 32°C)
•Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
•32° to 120°F (0° to 48.9°C)
Shipping Temperature
•-20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
•5% to 90% (non-condensing)
Electrical Ratings
TerminalVoltage (50/60Hz)Running Current
W (O/B) Heating20-30 Vac0.02-1.0 A
(Powerpile)750 mV DC100 mA DC
W2 (Aux) Heating20-30 Vac0.02-0.5 A
Y Cooling20-30 Vac0.02-1.0 A
Y2 Cooling20-30 Vac0.02-1.0 A
G Fan20-30 Vac0.02-0.5 A
Physical Dimensions
•3-9/16” H x 5-13/16” W x 1-1/2” D
•91 mm H x 147 mm W x 38 mm D
E Emergency heat20-30 Vac0.02-1.0 A
L Heat pump reset20-30 Vac0.02-0.5 A
17
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422