Honeywell F58F, F50F User Manual

208414, 208415 Replacement
Power Supply Kit for Electronic Air Cleaner
INSTALLATION INSTRUCTIONS
APPLICA TION
These kits replace the power supplies with W8600E solid­state performance indicators (SSPI) used in the F50F and F58F Electronic Air Cleaners. See Table 1.
NOTE: The W8600E Remote Performance Indicator
driver circuit board has been calibrated with the power supply in this kit. False wash indications will occur if used with a different power supply.
Table 1. Power Supply Replacement Guide.
EAC Electrical
Model Rating
F50F 120 Vac, 60 Hz 16 x 20 406 x 508 1.33 N/A 208414G
220/240 Vac, 50/60 Hz
F58F 120 Vac, 60 Hz 20 x 25 508 x 635 2.10 3 208414H
Nominal Size Ionizer Current
(in.) (mm) (mA) J6 Position
16 x 25 406 x 635 1.65 2 208414H 20 x 20 508 x 508 1.65 2 208414H 20 x 25 508 x 635 2.10 3 208414H 20 x 12-1/2 508 x 318 1.05 N/A 208414C 20 x 12-1/2 508 x 318 1.05 N/A 208415C
NOTE: Use the 120 Vac replacement power supply in
Table 1 when servicing the F50F or F58F Electronic Air Cleaners that were modified with the 203365A Transformer Kit to operate at 220/ 240 Vac.
The power supply board in the 208414H Kit has been calibrated to provide a selectable ionizer current output. Select the correct ionizer current by moving the J6 shorting bar to the correct position. See Tables 1 and 2. See Fig. 8 for location of J6. All other kits have single-current output.
Replacement Power Supply
(OS No.)
INST ALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition such as electrical shock.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
®U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • All Rights Reserved
W ARNING
ELECTRICAL HAZARD. Can Cause Electrical Shock or Equipment Damage.
Disconnect power before removing old power supply board and installing replacement power supply board.
T o Remove Old Power Supply Board
NOTE: Observe the location of leadwires to be replaced
on the power supply. Label the leadwires to identify them for reconnecting later.
Open access door. See Fig. 1.
Open power box.
X-XX UL
69-1136-2
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Table 2. Ionizer Current Output Guide
J6 Shorting Bar
Position Ionizer Current Output (mA)
32.10
21.65
11.05
REMOVING COVER FROM POWER BOX.
2
1
3
M5676A
Fig. 1. Remove cover from power box.
Disconnect the leads from 1, 2, 3, 4, P1, P2, P3, P4,
P5, P12, P14, P17, P18 and P21 on the old power supply. See Fig. 2 through 5.
POWER SUPPLY
M5764
Fig. 2. Power supply location on F50F and F58F.
Remove and discard W8600E terminal block and
wiring. Set aside screws for later use.
Remove and set aside the sheetmetal screws holding
the board in place.
Discard the old power supply.
Install New Power Supply
When replacing the power supply, reuse the remain-
ing leadwires in the air cleaner when removing the old power supply.
Install W8600E terminal block and wiring supplied
with this kit using screws previously removed.
Align the mounting holes and mount the new power
supply in the air cleaner, using the sheetmetal screws removed earlier. Orient the power supply so P1 and P2 are toward the front (closest to the switch and neon light).
Route the remaining leads so the P3 and P4 leads
are separate from the low voltage leads. Route all high voltage leads around, rather than over, the power supply board. Low voltage leads can go over the power supply board.
Connect leads to the terminals on the new power supply.
IMPORTANT
Do not splice ionizer and collector leads. These leads must be unbroken to avoid electrical shock through the connector or tape covering the splice.
Plug the electronic air cleaner directly into the correct
voltage and frequency outlet or reconnect power for directly wired devices. See Fig. 3 or 4 for internal schematic. The air cleaner operates correctly at any fan speed on a multispeed or modulated speed system wired with conduit or plugged in.
NOTE: To reduce the risk of electric shock, this product
has a grounding type plug with a third (ground­ing) pin. This plug fits only into a grounding type power outlet. If the plug does not fit into the outlet, contact a qualified electrician to install the proper outlet. Do
not
change the plug in any way.
CHECKOUT
IMPORTANT
The following instructions are for use only by qualified personnel.
With all components in place, turn on the air cleaner switch and energize the system blower. Check the following points of operation:
1. The neon light next to the on-off switch is on. If a W8600E is part of the installation, check the wall panel and make sure the ON LED is lighted. The W8600E CHECK LED comes on if there is a problem with the high voltage power supply.
2. Turn off the system blower. The neon light should go off after a few seconds. The neon light shows that the air cleaner is energized and the high voltage power supply is working properly.
3. Turn on the system blower. With the air cleaner energized, push the test button. A snapping sound indicates that the collector voltage is present on the cell. The W8600E CHECK LED comes on when the test button is held down.
4. With a multispeed blower, repeat steps 1 through 3 for each fan speed.
5. If operation is not as described, refer to the Trouble­shooting and Service section.
69-1136—2
2
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
INTERNAL SCHEMATIC FOR ELECTRONIC AIR CLEANER WITH W8600E.
BLACK
BLACK
TERMINAL STRIP
FRONT BACK
1
1
TO W8600E WALL PANEL
1 INTERLOCK SWITCH. 2 OUTPUT REDUCTION JUMPER. 3 AIRFLOW SWITCH DISABLE JUMPER. 4 RESISTOR FOR W8600 WASH INDICATION THRESHOLD. PRESENT ON POWER
SUPPLIES MANUFACTURED WITH DATE CODE 9430 AND EARLIER. 5 ONE-CELL UNIT SIMILAR, BUT WITH JUST ONE CELL. 6 P1, P2 TERMINALS ON 120V MODELS ONLY. POWER CONNECTIONS ON 240V MODELS ARE TO QUICK-CONNECTS ON POWER
SUPPLY TRANSFORMER. BROWN LEAD GOES TO TOP TERMINAL AND BLACK LEAD TO BOTTOM TERMINAL.
2
2
3
3
4
4
P3
P4
P21
P17
BLACK
1
BLACK
P5 P12 2
P18
BLACK COLLECTOR
POWER SUPPLY
J2
2
J7
4
P14
3
1
4
R43
BLACK
6
P2
P1
RED IONIZER
5
GREEN
BROWN
BLACK
WHITE
RED
VIOLET BLACK
TEST BUTTON
BLACK
ORANGE
GRAY
GREEN
AIRFLOW SWITCH BOARD
W4 W2 W1 W3
Fig. 3. Internal schematic for F50F and F58F Electronic Air Cleaner with W8600E.
CONTACT BOARD
3
M15096
BLACK COLLECTOR
BLACK
5
BLACK
2
4
BLUE
B4
RED
YELLOW
GREEN
5 3 2 1
R3 Y2 G1
1 INTERLOCK SWITCH. 2 SHORTING BAR. 3 AIRFLOW SWITCH DISABLE JUMPER. 4 W8600E REMOTE PERFORMANCE INDICIATOR DRIVER. 5 NEON LIGHT.
J1
J2
P3
P4
E5
E4 E3
J1
E6
J5
BLACK
E2
GRAY
VIOLET
E1
ORANGE
AIRFLOW SWITCH BOARD
POWER SUPPLY
P2
P1 BLACK
W4 W2 W1 W3
3
RED IONIZER
BROWN
BLACK
RED
BLACK
1
BLACK
Fig. 4. Retrofitted schematic for F50F and F58F Electronic Air Cleaner with W8600E.
3
TEST BUTTON
BLACK
CONTACT BOARD
WHITE
GREEN
M15097
69-1136—2
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
BLACK
7
BLACK
4
BLUE
B4
RED
YELLOW
GREEN
5 3 2 1
R3 Y2 G1
1 INTERLOCK SWITCH. 2 SHORTING BAR. 3 AIRFLOW SWITCH DISABLE JUMPER. 4 W8600E REMOTE PERFORMANCE INDICIATOR DRIVER. 5 TOP TERMINAL ON TRANSFORMER 6 INPUT POWER. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 7 NEON LIGHT.
J1
J2
P3
P4
E5
2
J1
Fig. 5. Retrofitted schematic for 220/240 Vac F50F Electronic Air Cleaner with W8600E.
TROUBLESHOOTING AND SERVICE
W ARNING
ELECTRIC SHOCK HAZARD. Can Cause Personal Injury or Equipment Damage. Instructions are Only for Use by Qualified Personnel.
The following procedures expose hazardous live parts. Disconnect from power between checks and proceed carefully.
Tools and Equipment
Troubleshooting the electronic air cleaner requires:
Needle-nose pliers for stringing ionizer wires and inserting edge connectors.
Test meter.
Although a meter is needed for some steps, the primary diagnostic tools are the See Fig. 6.
neon light
and the
test button
.
BLACK COLLECTOR
RED IONIZER
E6
J5
E4 E3
BLACK
E2
VIOLET
5
BROWN
E1
ORANGE
GRAY
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
Test Button
When pushed, the to ground. The resulting arcing sound indicates that high voltage is being supplied to the collector. The solid state power supply controls current flow to the collector. On air cleaners with a W8600E, the CHECK LED comes on when the
BLACK
1
BLACK
3
test button
test button
TEST BUTTON
RED
BLACK
BLACK
BLACK
L1 L2
shorts from collector voltage
is held down.
COLLECTOR TERMINAL
IONIZER TERMINAL
COLLECTOR TERMINAL
CONTACT BOARD
6
220/240V 50/60 Hz
WHITE
GREEN
M15098
Neon Light (On Power Box)
The neon light is powered through the power supply and is on when the power supply output voltage is normal.
69-1136—2
M6155
Fig. 6. Use an ohmmeter to check
the electronic cells for short circuits.
4
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Check Led (Air Cleaners With W8600E)
The CHECK LED on the W8600E lights to indicate the following problems: excessive dirt loading (beyond that required to activate the WASH LED), partial shorting of the collector, continuous ionizer or collector arcing, power supply failure, excessive ionizer current, or any condition causing a major reduction in high voltage.
Power Supply
W ARNING
ELECTRIC SHOCK HAZARD. Can Cause Personal Injury.
Always turn off power and remove access door before removing the power box or its cover.
The solid state power supply assembly has no field serviceable components. If troubleshooting indicates a power supply or solid state performance indicator problem, replace the entire power supply assembly.
Troubleshooting Procedure
The electronic air cleaner Troubleshooting chart shows how to quickly isolate an air cleaner problem. The primary diagnostic tools are the Some steps require a meter. See Fig. 7.
TROUBLESHOOTING AIR CLEANERS WITH SOLID STATE PERFORMANCE INDICATOR.
START
MAKE SURE ELECTRONIC CELL(S) ARE CLEAN, DRY AND PROPERLY INSTALLED. MAKE SURE PREFILTER(S) ARE IN CABINET SLOT FARTHEST FROM FURNACE.
TURN ON ELECTRONIC AIR CLEANER AND SYSTEM FAN.
CHECK NEON LIGHT.
CORRECT WIRING.
WIRING
CHECK WIRING BETWEEN W8600E AND AIR CLEANER. USE MAX NO. 18 4-WIRE THERMOSTAT CABLE CONNECTED 1(G) TO 1(G), 2(Y) TO 2(Y), 3(R) TO 3(R), AND 4(B) TO 4(B).
1 2
3
NOT OK
WIRING OK
REPLACE
3
W8600E.
FOR POWER SUPPLY REPLACEMENT, SEE FORM 69-0776. W8600E HAS THREE LIGHT-EMITTING DIODES (LEDS):
ON, WASH, AND CHECK. W8600E OPERATION CAN BE CHECKED SEPARATELY.
SEE W8600E INSTRUCTIONS.
PUSH TEST BUTTON AND LISTEN FOR SNAPPING SOUND.
OFF
CHECK ON LED IN W8600E
OFF
DEPRESS AND HOLD DOWN TEST BUTTON. CHECK LED IN W8600E SHOULD COME ON
TURN OFF AIR CLEANER AND REMOVE CELL(S) ONLY (NOT PREFILTERS). CLOSE ACCESS DOOR AND TURN ON AIR CLEANER.
WASH LED IN W8600E SHOULD COME ON.
OFF
ELECTRONIC AIR CLEANER AND W8600E ARE OK.
ON
ON
ON
YES
2
ON
2
2
TO USE THIS CHART:
1.
FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND.
2.
EACH TIME YOU ISOLATE AND FIX A PROBLEM, GO BACK TO START.
3.
REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK.
THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALIFIED PERSONNEL ONLY. TO REDUCE RISK OF ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING OTHER THAN CONTAINED IN THE OPERATING INSTRUCTIONS UNLESS YOU ARE QUALIFIED TO DO SO.
PUSH TEST BUTTON
OFF
AND LISTEN FOR SNAPPING SOUND.
NO
NO
TURN OFF AIR CLEANER AND REMOVE CELL(S) ONLY (NOT PREFILTERS). CLOSE ACCESS DOOR AND TURN ON AIR CLEANER.
CHECK NEON LIGHT.
INSPECT CELL(S) FOR:
BENT COLLECTOR
PLATES BROKEN IONIZER
WIRES DIRT ON INSULATORS
DAMAGED IONIZER
OR COLLECTOR CONTACT TABS
YES
REPAIR OR REPLACE CELL(S).
WITH OHMMETER, CHECK FOR SHORT BETWEEN:
••CELL FRAME AND
IONIZER SECTION CELL FRAME AND COLLECTOR SECTION
CELL SHORTED
REPLACE CELL.
Fig. 7. Troubleshooting air cleaners with solid-state performance indicator.
ON
CELL OK.
WARNING
RISK OF ELECTRIC SHOCK
YES
OFF
CHECK FOR CORRECT INPUT VOLTAGE ACROSS P1 AND P2 TERMINALS ON POWER SUPPLY.
TURN OFF AIR CLEANER, REPLACE CELLS(S) AND DISCONNECT FOUR W8600E LEADS AT AIR CLEANER. REPLACE ACCESS DOOR.
NO
TURN ON AIR CLEANER. PUSH TEST BUTTON AND LISTEN FOR SNAPPING SOUND.
REPLACE POWER BOX OR POWER SUPPLY.
INFINITE RESISTANCE
AIR CLEANER OK. TURN OFF AIR CLEANER AND RECONNECT W8600E LEADS 1(G) TO 1(G), 2(Y) TO 2(Y), 3(R) TO 3(R), AND 4(B) TO 4(B).
neon light
REPLACE LIGHT ASSEMBLY.
FIX WIRING.
and the
WARNING
THIS STEP EXPOSES DANGEROUSLY HIGH VOLTAGE. ONLY A QUALIFIED SERVICE TECHNICIAN SHOULD ATTEMPT THIS STEP.
NO
YES
NO
YES
1
test button
M5609E
.
5
69-1136—2
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Modification To Reduce Ozone Odor
W ARNING
ELECTRIC SHOCK HAZARD. Can Cause Personal Injury
Always disconnect power before opening power supply cover.
The electronic air cleaner generates a small amount of ozone in normal operation. During the first or second week of operation, the amount may be higher because of sharp edges on some of the new high voltage metal parts. Normal use quickly dulls these edges.
The average person can detect the odor of ozone in concentrations as low as 0.003 to 0.010 parts per million (ppm). The electronic air cleaner contributes 0.005 to
0.010 ppm of ozone to the indoor air. The U.S. Food and Drug Administration and Health and Welfare Canada recommend that indoor ozone concentration does not exceed 0.050 ppm. As a comparison, the level in major cities is sometimes as high as 0.100 ppm.
However, if desired, the ozone generated by the air cleaner can be reduced in one of two ways:
1. Install an activated carbon filter downstream from the air cleaner. Make sure particles from the air filter cannot fall into the air cleaner.
W ARNING
ELECTRIC SHOCK HAZARD. Can Cause Personal Injury.
Only a trained service technician should perform the following procedure.
outdoor
ozone
2. To reduce ozone production about 20 to 25 percent and reduce efficiency about seven to ten percent, depending on actual airflow delivered by the furnace blower:
a. Unplug or disconnect power supply to the air
cleaner. b. Open the access door. c. Remove the power box cover. See Fig. 1. d. Locate J5 shorting bar on the power supply.
See Fig. 8. Remove the shorting bar and
reinstall on only one pin.
NOTE: The ozone will be reduced, and the
shorting bar is available for reinstallation, if needed.
e. Replace the power supply cover and access
door. Turn on the power. f. Repeat the checkout procedure before leaving
the job.
J4 SHUNT IN POSITION TO DISABLE NEON LIGHT OUTPUT
J4
P3
J4 SHUNT IN POSITION TO ENABLE NEON LIGHT OUTPUT
J5 SHUNT IN NORMAL POSITION
J5 SHUNT IN OZONE REDUCED POSITION
P4
J4
E5
E6
J4
3 2 1
J6
J5
J5
E4 E3
J5
Fig. 8. Move J5 shorting bar to reduce ozone
production about 20 to 25 percent.
E2
E1
J3
J1
P1
P2
M14200
69-1136—2
6
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
LIMITED TWO-YEAR WARRANTY
Honeywell warrants this product to be free from defects in the workmanship or materials, under normal use and service, for a period of two (2) years from the date of purchase by the consumer. If, at any time during the warranty period, the product is defective or malfunctions, Honeywell shall repair or replace it (at Honeywells option) within a reasonable period of time.
If the product(s) is defective, please contact:
a) the dealer from whom you purchased it, or b) the local Honeywell Authorized Repair Station, or c) the local Honeywell Home and Building Control Office, or d) the Honeywell Customer Assistance Center toll free at 1-800-468-1502, or e) package the defective cell, power supply or other component with care, along with a bill of sale, receipt, or other
dated proof of purchase, and a short description of the malfunction, and ship it, prepaid, to the following address:
Honeywell, Inc. Return Goods Department 1050 Berkshire Lane Plymouth, MN 55441-4437
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Honeywell that the defect or malfunction was caused by damage that occurred while the product was in the possession of a consumer.
Honeywell sole responsibility shall be to repair or replace the product within the terms stated above. HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.
THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE, AND HONEYWELL EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, IMPLIED OR STATUTORY, INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY, WORKMANSHIP, OR FITNESS FOR A PARTICULAR PURPOSE.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. If you have any questions concerning this warranty, please write our Customer Assistance Center, Honeywell Inc.,
P.O. Box 524, MN27-2164, Minneapolis, Minnesota 55440-0524 or call toll-free at 1-800-468-1502, Monday-Friday, 7:00 a.m.-5:30 p.m. Central time. In Canada, Honeywell Limited/Honeywell Limitee, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
7
69-1136—2
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
69-11362
69-11362 G.H. Rev. 12-99 Printed in Mexico
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
8
Loading...