The high efficiency F50F Electronic Air Cleaner is
mounted in the return air duct of a forced air heating,
cooling, or ventilating system. It captures a significant
amount of airborne particles 0.5 microns and larger from
the air circulated through it. All models have an internal
airflow switch to operate the F50F when the system
blower is on.
PLANNING THE INSTALLATION
Review Installation Requirements
The air cleaner should be installed where all the air
passing through the system circulates through it. The best
location is in the return air duct next to the blower compartment so the air cleaner can help keep the blower motor
and evaporator coils clean.
IMPORTANT
Do not mount in the discharge air duct.
For most efficient air cleaning, airflow must be spread
evenly across the face of the air cleaner. If the duct is a
different size than the air cleaner cabinet, gradual transitions are recommended. If the duct turns sharply just
before the air cleaner, turning vanes are recommended.
Applications with Air Conditioning
The air cleaner should be installed upstream from the
evaporator coil. The air cleaner will help keep the coil
clean, reducing maintenance.
Applications with a Humidifier
An evaporative humidifier can be mounted upstream from
the air cleaner. An atomizing humidifier should be mounted
downstream from the air cleaner, even though hard water
salts will be blown into the living space and deposited as
dust. If an atomizing humidifier must be mounted upstream
from the air cleaner:
1. Mount it as far upstream as possible from the
air cleaner.
2. Install a standard disposable furnace filter between
the humidifier and the air cleaner to trap water
droplets and hard water salts.
3. Frequently clean the air cleaner to prevent a hard
water salt buildup.
NOTE: The volume of water that passes through an
atomizing humidifier can overload the air cleaner,
resulting in hard water salts being deposited as
dust in the living space.
Applications with an Activated Carbon Filter
An activated carbon (charcoal) filter can be used to remove
odors or other gaseous contaminants (not particle-based) that
are not removed by the air cleaner. Locate the carbon filter:
• Downstream from the air cleaner. This means that dust
from the carbon filter will not be collected by the air
cleaner and will be deposited in the living space.
• Outside the air cleaner cabinet. Some carbon filters are
combustible and contact with high voltage could result
in smoke or fire.
• Where carbon granules cannot fall into the electronic
cell. If necessary, use a disposable furnace filter
between the carbon filter and the electronic cell.
• With proper transitions, if the activated carbon filter
requires a differently size duct than the air cleaner.
Allow 20 degrees expansion per side, per fitting.
NOTE: Honeywell does not offer carbon filters. Refer to
an activated carbon filter manufacturer for sizing
and application.
Applications with Outdoor Air Intake
Return air temperature must be at least 40°F (4°C). Lower
temperatures can cause ionizer wire failure. If outdoor air is
used, warm it upstream from the air cleaner by:
• Making sure the outdoor intake is far enough upstream
from the air cleaner so the return and outdoor air is
thoroughly mixed. Stratified air can dump a stream of
very cold air into one section of the air cleaner.
• Adding baffles upstream from the air cleaner to force
thorough air mixing.
• Installing a preheater if large amounts of outdoor air are
used. The preheater, which could be an electric strip
heater or hot water coil, should be controlled by a
thermostat. Hot water or steam coils should be
protected by a freeze-up control.
Optional W8600F
The F50F terminal board is recessed slightly so it or the wires
will not interfere with installation. The entire power supply box
can be unplugged and removed to provide access to the
terminals. The W8600F air cleaner monitor can be mounted in
the living area or in the furnace room. It should be located in a
convenient location to observe the display.
Choose a location that is readily accessible for regular
inspection and cleaning. Allow at least 13 in. [330 mm] in
front of the access door for removing the prefilter and
electronic cell. Allow enough room above the power supply
so it can be serviced without removing pipes, ducts, or
other heating system components.
The air cleaner
will not exceed 40°F to 125°F (4°C to 52°C).
must
be installed where the temperature
Choose Mounting Position
WARNING
Heavy Equipment.
Can cause injury or equipment damage.
Do not mount the air cleaner with the access door
facing down. If the access door faces down, the
latch may not hold, and the cell and prefilter can
fall unexpectedly. Also, nothing holds the cell and
prefilter in place when the access door is opened.
The air cleaner can be mounted in any position except with
the access door facing down. Following is a list of air cleaner
mounting positions for a variety of furnace installations.
A
B
NOTE: At least 13 in. [330 mm] clearance is required
between the access door and any obstructions
for cell and prefilter maintenance.
—
Upflow “Highboy” furnace:
cleaner is mounted vertically where return enters side
inlet of furnace. See Fig. 1A.
—
Downflow “Highboy” furnace
furnace (air cleaner cabinet can easily support weight
of furnace and air conditioner coil). Air cleaner is
mounted horizontally where return enters from below.
See Fig. 1B.
—
Upflow “Highboy” furnace:
cleaner is mounted vertically on furnace between
furnace and louvered return air opening in closet door.
See Fig. 1C.
—
“Lowboy” furnace:
in return plenum just above furnace, opposite supply
plenum. See Fig. 1D.
—
Downflow “Counterflow” furnace:
mounted horizontally in return duct or plenum just
above furnace. See Fig. 1E.
—
High capacity system:
be used together. See Fig. 1F.
—
Electric furnace or heat pump:
is mounted with access door on top. See Fig. 1G.
—
Horizontal furnace:
where return enters. See Fig. 1H.
C
Side installation; air
: Installation beneath
Closet installation. Air
Air cleaner is mounted horizontally
Air cleaner is
Two or more air cleaners can
Single cell air cleaner
Air cleaner is mounted vertically
D
69-0754B—1
E
G
F
Fig. 1. Mounting positions with a variety of furnace installations.
2
H
M11973
F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
Determine Duct Design Requirements
The air cleaner is adaptable to all new or existing forced air
heating, cooling and ventilating systems used in residential
applications. Transitions, turning vanes, or offsets may be
needed in some applications for effective operation.
Transitions
Transitions are needed when the duct is a different size
than the air cleaner cabinet. Gradual transitions reduce air
turbulence and increase efficiency. Limit expansion to no
more than 20 degrees (about 4 in. per running foot
[100 mm per 300 linear mm]) on each side of a transition
fitting. See Fig. 2.
CHANGE DUCT SIZE GRADUALLY TO MINIMIZE TURBULENCE.
20 DEGREE EXPANSION PER SIDE PER
FITTING (4 in. PER LINEAR FOOT
[100 mm PER 300 LINEAR mm]).
RETURN
AIR DUCT
TRANSITION FITTING
ELECTRONIC AIR CLEANER CABINET
Fig. 2. Change duct size gradually to
minimize turbulence.
Turning Vanes
If the air cleaner is installed close to an elbow or angle
fitting, install turning vanes inside the angle to distribute
airflow more evenly across the face of the cell. See Fig. 3
Offsets
If the duct connection to the furnace in a side installation
allows less than 7 in. (178 mm) for mounting the air
cleaner cabinet, add an offset to the elbow. See Fig. 3.
TYPICAL USE OF DUCT OFFSET TO ALLOW
SPACE FOR ELECTRONIC AIR CLEANER.
M5626A
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Electric Shock Hazard.
Can cause electrical shock or
equipment damage.
Do
not
connect to power before installation
is complete.
Unpack Electronic Air Cleaner
J Check that all components are included. The electronic
air cleaner is shipped assembled. The unit consists of a
galvanized steel cabinet, power supply with on-off
switch and neon light, one or two electronic cells and
prefilters, access door with test button, and homeowner
literature package.
J W8600F (optional), mounting hardware and installation
literature must be ordered separately.
Clean Blower Compartment
J Remove and discard the existing furnace filter.
J Thoroughly clean the blower compartment.
J If possible, power vacuum the ductwork to remove
accumulated dust in an existing home, or construction
dirt in a new home. The electronic air cleaner cannot
remove dust that has settled in the blower compartment
and distribution ducts.
J Check the edges of the furnace fan blades for dirt
buildup and clean as necessary. The fan will not deliver
the rated cfm if the blades are dirty.
LESS
THAN
7 in.
[178 mm]
E
L
E
C
T
R
O
N
I
C
A
I
R
C
L
E
A
N
E
R
1 TURNING VANES HELP DISTRIBUTE AIRFLOW EVENLY.
Fig. 3. Typical use of duct offset to allow space for
electronic air cleaner.
OFFSET
AT LEAST
7 in.
1
[178 mm]
M5627A
Fasten Cabinet To Furnace
NOTE: This procedure shows a side installation on a
typical highboy furnace. You may need to alter
the procedure to fit your application.
J Remove and set aside the access door, electronic
cell(s) and prefilter(s).
J Align the cabinet with the return air opening.
J Create opening in furnace to match air cleaner
cabinet opening.
J Install a transition if the furnace and air cleaner
openings are different sizes. See Fig. 2.
J Place blocks under the cabinet so the unit is firmly
supported and level. The 5/8 in. (16 mm) mounting foot
on the cabinet hinge plate provides the minimum
clearance required for the access door hinge.
J If a W8600F is used, first attach the wires to the
W8600F and then attach the wires to the air cleaner
power box terminal board. See Fig. 4 and the W8600F
installation literature, form 69-1200.
3
69-0754B—1
F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
W8600F
1
1
ELECTRONIC AIR CLEANER
TERMINAL STRIP
ON POWER BOX
4
2
3
R
B
1 CONNECT TO W8600F TERMINALS BEFORE CONNECTING TO
POWER BOX.
GREEN
1
G
Y
RED
BLUE
4
3
THREE-WIRE
THERMOSTAT CABLE
M11974
Fig. 4. Schematic for wiring W8600F to F50F.
J Attach the cabinet securely to the furnace. The unit can
be attached directly, as shown, or a starting collar can
first be fitted in the furnace opening. Either drill holes
and fasten with sheet metal screws or rivets, or use slip
joints. If drilling holes, use locking pliers to help hold the
unit in place during drilling. See Fig. 5.
Fasten Cabinet To Ductwork
J Install a transition if the opening in the air cleaner
cabinet and the duct are different sizes. See Fig. 2.
J Fasten the other side of the cabinet to the elbow using
sheet metal screws, rivets, or slip joints as appropriate.
See Fig. 6.
Install Optional W8600F Air Cleaner Monitor
Choose a location for the W8600F if it is part of the
installation. The W8600F is designed to mount next to your
thermostat, or in any convenient visible area (such as
utility room) where it can be seen as it monitors the air
cleaner performance. It shares no electrical connections
with the thermostat. To install the W8600F, see Fig. 4 and
refer to the Installations Instructions, form 69-1200,
included with the air cleaner monitor.
Seal Joints
J Seal all joints in the return air system between the air
cleaner and the furnace to prevent dust from entering
the clean airstream.
Disable Unused Prefilter Guide
J Crimp the end of the downstream (closest to the
furnace) prefilter guide to prevent incorrect prefilter
installation following cleaning. See Fig. 6.
ELECTRONIC AIR CLEANER
M3678
Fig. 5. Fasten cabinet to furnace.
Install Turning Vanes
J Mount turning vanes inside the elbow or angle fitting
that is directly against the air cleaner cabinet.
69-0754B—1
M5640A
Fig. 6. Crimping the prefilter guide.
Position Cell Key
The electronic cell must always be installed so the ionizer
section is on the upstream side. A factory-installed cell key
on the bottom of the cabinet allows the cell to be inserted
in only one direction. As long as the arrow molded into the
plastic key points in the same direction as the airflow, the
ionizer will always be on the upstream side.
If the position of the key must be reversed, proceed as
follows:
1. Re
move electronic cell.
2. Remove the screw holding the cell key in place.
See Fig. 7.
4
DOWNSTREAM
AIRFLOW
CELL
PREFILTER GUIDES
M5639
Fig. 7. Position of cell key determines orientation of
cell (arrow on key must point downstream).
3. Turn the key around and place it over the opposite
holes. The tab on the bottom fits into the larger hole,
and the screw into the smaller hole. Make sure the
arrow on the key points in the direction of the air flow
(downstream).
4. Tighten the screw into the new hole.
5. Insert the electronic cell. The ionizer section will now
be on the air-entering (upstream) side of the cabinet.
Attach Cell Handle(s)
The cell handles are packed int the installers bag
assembly. They must be installed on the end of the cell
closest to the access door. To install:
1. Orient the cell as it will be when installed. The gray
contact board must be up and the airflow arrow
stamped into the cell must point downstream.
2. Hold the handle sideways and insert the solid tab on
the back of the handle into the slot in the cell. Turn
the handle 90 degrees clockwise to align the divided
tab with the square hole. See Fig. 8.
CELL KEY
INSTALL HANDLE ON END OF CELL
CLOSEST TO ACCESS DOOR.
Fig. 8. Install handle on end of cell
closest to access door.
KEY
CELL KEY
SCREW
ALTERNATE
HOLES FOR
KEY
ROTATE 90
DEGREES
FOLD TAB
TO LOCK
HANDLE
IN PLACE
M6047A
F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
3. Insert the divided tab into the square hole.
4. Fold up the wedge and insert it into the divided tab
to lock the handle in place. If necessary, press with
a blunt instrument like the end of a pliers.
Reassemble Air Cleaner
J Insert the electronic cell with the gray contact board up
and the airflow arrow pointing downstream. If the cell
does not slide easily in to the cabinet, check the
orientation of the cell key.
J Insert the prefilter on the upstream side of the cabinet
in the guide provided.
J Replace the access door. Insert the tab on the bottom
of the door into the slot in the cabinet, then swing it
closed and press into place. The door must be firmly in
place or the air cleaner will not operate.
Complete Wiring
WARNING
Electric shock hazard.
Can cause personal injury.
Do
not
use an extension cord.
• All wiring must comply with local codes and ordinances.
•The line voltage power source must match the voltage and
frequency printed on the label inside the access door.
J
Plug the F50F directly into the correct voltage and
frequency outlet. See Fig. 9 through 12 for internal
schematic. The F50F will operate properly at any fan
speed on a multispeed or modulated speed system
wired with conduit or plugged in.
NOTE: To reduce the risk of electric shock, this product
has a grounding type plug that has a third
(grounding) pin. This plug will only fit into a
grounding type power outlet. If the plug does not
fit into the outlet, contact a qualified electrician to
install the proper outlet. Do
in any way.
not
change the plug
5
69-0754B—1
F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
BLACK
5
BLACK
4
4
BLUE
B4
R3
Y2
G1
1 INTERLOCK SWITCH.
2 SHORTING BAR.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 OPTIONAL W8600F AIR CLEANER MONITOR. DRIVER
BOARD AND CABLE PROVIDED WITH W8600F.
5 NEON LIGHT.
RED
GREEN
6
5
J2
2
Fig. 9. Internal schematic for F50F with W8600F.
BLACK
7
BLACK
P3
P4
J4
J5
2
J3
J1
J1
ORANGE
GRAY
VIOLET
BLACK
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
P3
P4
J4
BLACK COLLECTOR
RED IONIZER
POWER
SUPPLY
BROWN
P2
P1
BLACK
3
BLACK COLLECTOR
1
BLACK
RED IONIZER
RED
BLACK
RED
TEST
BUTTON
BLACK
BLACK
BLACK
TEST
BUTTON
CONTACT
BOARD
WHITE
M11975
GREEN
CONTACT
BOARD
J5
2
J3
4
B4
R3
Y2
G1
1 INTERLOCK SWITCH.
2 SHORTING BAR.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 OPTIONAL W8600F AIR CLEANER MONITOR. DRIVER BOARD AND
CABLE PROVIDED WITH W8600F.
5 TOP TERMINAL ON TRANSFORMER
6 INPUT POWER. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
7 NEON LIGHT.
RED
GREEN
6
5
2
4
BLUE
J1
J2
J1
ORANGE
GRAY
VIOLET
BLACK
AIRFLOW SWITCH BOARD
Fig. 10. Internal schematic for 220/240V F50F models.
69-0754B—1
6
5
W4 W2 W1 W3
3
BROWN
BLACK
BLACK
1
BLACK
GREEN
WHITE
BLACK
6
L1 L2
220/240V
50/60 Hz
M11976
F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
BLACK COLLECTOR
RED IONIZER
BLACK
5
BLACK
4
B4
R3
Y2
G1
1 INTERLOCK SWITCH.
2 SHORTING BAR.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 OPTIONAL W8600F AIR CLEANER MONITOR. DRIVER
BOARD AND CABLE PROVIDED WITH W8600F.
5 NEON LIGHT.
6 TRANSFORMER.
7 INPUT POWER. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
RED
GREEN
6
5
2
4
BLUE
J1
J2
Fig. 11. Internal schematic for CE compliant 230V, 2 cell F50F models.
BLACK
7
BLACK
P3
P4
J4
2
J3
J1
POWER
SUPPLY
J5
E1/B2
ORANGE
GRAY
VIOLET
BLACK
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
P3
P4
J4
BLACK
E2/B4
BLACK
3
BLACK COLLECTOR
RED IONIZER
6
RED
BLACK
TEST
BUTTON
TEST
BUTTON
CONTACT
BOARD
1
BLACK
BROWN
CONTACT
BOARD
230V ac
50 Hz
GROUND
M11977
L
7
N
J5
2
J3
4
B4
R3
Y2
G1
1 INTERLOCK SWITCH.
2 SHORTING BAR.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 OPTIONAL W8600F AIR CLEANER MONITOR. DRIVER
BOARD AND CABLE PROVIDED WITH W8600F.
5 BROWN WIRE TO TOP TERMINAL.
6 INPUT POWER. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
7 NEON LIGHT.
6
RED
5
2
GREEN
Fig. 12. Internal schematic for CE compliant 230V, 1 cell F50F models.
4
BLUE
J1
J2
J1
ORANGE
GRAY
VIOLET
BLACK
5
BROWN
BLACK
W4 W2 W1 W3
3
AIRFLOW SWITCH BOARD
7
1
BLACK
BROWN
230V ac
50 Hz
GROUND
M11978
L
6
N
69-0754B—1
F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
J Alternatively, the F50F can be wired with conduit.
1. Open access door.
2. Remove and retain the (2) screws from the front of
the power box and the (2) screws from the sides of
the power box. See Fig. 13.
3. In the power box, remove and retain (2) wire nuts that
connect the line cord leads to the power box wiring.
4. Remove the green lead from the green grounding
screw on the wiring compartment barrier.
5. Remove the power cord and the strain relief.
6. Install plug (provided in bag assembly) in the hole
left by the power cord.
7. Attach conduit through a power box side knockout.
8. Wire the air cleaner directly to line voltage using wire
nuts. See Fig. 14. Secure ground connection to the
green ground screw on the wiring compartment
barrier.
9. Replace power supply cover and access door.
REMOVING COVER FROM POWER BOX.
2
1
OPERATION
Large particles (lint, hair) are caught by the prefilter. As the
dirty air passes through the intense high voltage electric
field surrounding the ionizer wires, all particles are given
an electrical charge. The air then moves through the
collector part of the cell where alternate parallel plates are
charged positively and negatively, creating a uniform
electrostatic field. The charged particles are attracted to
and collect on the plates having the opposite electrical
charge. The air leaving the air cleaner has fewer particles.
Each time the air circulates through the F50F, more
particles are removed.
CHECKOUT
Inspect The Installation
Make sure:
• Turning vanes and transitions, as needed, are
properly installed.
• Sheet metal joints between air cleaner and furnace
are sealed.
• All sheet metal connections are complete.
• Original furnace filter has been removed and the blower
compartment cleaned.
• If an atomizing humidifier is installed upstream from the
air cleaner, a disposable furnace filter is installed
between the humidifier and the air cleaner.
• Outside air, if used, is mixed with return air or heated,
as necessary, before it can reach the air cleaner.
• The airflow arrows on the electronic cell point
downstream.
• The prefilter is on the upstream side of the cell.
• The cell handle faces outward.
• The electronic cell and prefilter are clean and dry.
• That W8600F (if included) wiring connections are
properly made.
Fig. 13. Removing cover from power box.
WIRING
ELECTRONIC
AIR CLEANER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
2
THE AIR CLEANER CAN BE COMPLETELY ISOLATED FROM
THE ELECTRICAL CIRCUIT OF THE HVAC SYSTEM UNLESS
REQUIRED BY LOCAL CODE TO USE SAME CIRCUIT. ANY
CONVENIENT HOUSE CIRCUIT CAN POWER AIR CLEANER,
REGARDLESS OF ELECTRICAL RATING OF HVAC SYSTEM.
COMPARTMENT
BLACK
BROWN
Fig. 14. Conduit connection for F50F.
69-0754B—1
3
M5676A
2
L1 (HOT)
1
L2
M5707
Check Air Cleaner Operation
With all components in place, turn on the air cleaner switch
and energize the system blower. Check the following
points of operation:
1. The neon light next to the on-off switch is on. If a
W8600F is part of the installation, also check the
wall panel and make sure ON is indicated. The
W8600F FAULT indicator will come on if there is a
problem with the high voltage power supply.
2. Turn off the system blower. The neon light should go
off after a few seconds. The neon light shows that
the air cleaner is energized and the high voltage
power supply is working properly.
3. Turn on the system blower. With the air cleaner
energized, push the test button. A snapping sound
indicates that the collector voltage is present on the
cell. On air cleaner with a W8600F, the FAULT
indicator will come on when the test button is held
down.
4. With a multispeed blower, repeat steps 1-3 for each
fan speed.
5. If operation is not as described, refer to the Trouble-
shooting and Service section.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.