• High Efficiency Particulate Air (HEPA) filter models are
99.97% efficient and the hospital grade particle filter
models are 95% efficient at 0.3 micron particles. Both
models are more efficient on particles smaller and
larger. There is also a 95% ASHRAE model.
• UV-C light kills airborne bacteria.
• UV lamp does not produce ozone.
• Circulates up to 1200 cfm.
• Designed to overcome the increase in air flow
resistance normally caused by filter loading.
• White or black color cover to complement the ceiling.
• Sealed and interlocked design prevents accidental
APPLICATION
The F111U In-Ceiling Media Air Cleaner is a media air cleaner
that uses a three-speed direct drive forward curve blower
motor with ultraviolet lights. The air cleaner removes airborne
particles such as dust, soot, mold spores, pollen and some
cooking smoke, and kills microbial contaminants in the air
circulating through the unit.
exposure to ultraviolet light.
• Innovative design of UV module prevents lamp from
lighting unless the base is correctly mounted.
The Honeywell Trademark is used under license from Honeywell International
Inc. by Air-Pure Systems.
Honeywell International Inc. makes no representations or warranties with
respect to this product.
Contents
68-0275-2
Page 2
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifications. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Models: Refer to Table 1 for model descriptions.
Grill Color: White (standard) or Black .
Blower/Motor: three-speed, direct drive, forward curve.
Installation Weight:
Approximately 115 lb .
Sound Level at 3.3 ft (1m):
Low speed: 53 dBA (3 speed models only).
Medium speed: 57 dBA (3 speed models only)
High speed: 61 dBA.
Temperature Ratings:
Ambient Temperature Range: 30°F to 104°F (-2°C to 40°C).
Relative Humidity:
Up to 95% Reletive Humidity, non-condensing.
Grille Type: Perforated metal.
Mounting: Recesses into opening on the ceiling.
Efficiency:
Total Efficiency: 99.99% combined capture kill/effectiveness.
(Test conducted against serratia marcescens bactera with
a total airflow rate of 900 cfm using new lamps.)
Particle Filtration: 99.97% (Particle collection efficiency of 0.3
micron particle size.)
UV Efficiency: Over 80% (Mathematical simualtion of an
F111U showed a single-pass kill rate of serratia marcelscens bacteria with a total airflow rate of 900cfm using new
lamps.)
Airflow Rate: 900 cubic feet per minute (1530 cubic meters
Replace the ‘W’ with a ‘B’ to any model number in Table 1.
ORDERING INFORMATION
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Commercial Air Products Distributor.
2. Air-Pure Systems
16873 Fish Point Rd. SE
Prior Lake, MN 55372
www.cleanairfacility.com
Phone: (800) 998-1919
Fax: (800) 221-3248
68-0275-22
Page 3
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
TOP VIEW
3/8 X 16
INTERNAL
THREAD (4)
CLEARANCE
FOR LAMP
48 (1219)
46-3/4 (1187)
POWER CONNECTION
POINT
REMOVAL
19 (483)
CEILING
LINE
4
(102)
17-1/4
(438)
4-1/2
(114)
22-1/2
(572)
24 (610)
M20928
Fig. 1. Approximate dimensions of F111U in in. (mm).
PLANNING THE INSTALLATION
The number of F111U air cleaners required is determined by
taking into account the number of occupants and the volume of
the space. Other factors include type of contamination, outdoor
air quality and planned use of the space.
Refer to Table 2 for general guidelines when determining how
many air cleaners are needed.
EXAMPLE: One air cleaner at 900 cfm can provide 10 air
changes per hour in a 12,000 cubic feet (159
cubic meters) area. Table 2 suggests two air
cleaners for a 12,000 cubic feet area. Additional
air cleaners can be required in locations with
increased activity or where contaminant generation rates are unusually high.
If any questions should arise concerning determining the
number of air cleaners needed for an area, consult your local
Honeywell Commercial Air Cleaner Distributor.
Table 2. Determining the Minimum Number of
Air Cleaners Needed for a Space.
Space Volume
(L x W x H) in Cubic
Feet (Cubic Meter)
5000 to 9000
(140 to 255)
9001 to 16000
(255 to 450)
16001 to 21000
(450 to 600)
21001 to 27000
(600 to 765)
27001 to 30000
(765 to 850)
30001 to 36000
(850 to 1020)
Minimum Number of
Air Cleaners
1
2
3
4
5
6
WARNING
TO REDUCE THE RISK OF FIRE,ELECTRICAL
SHOCK, OR INJURY TO PERSONS,OBSERVE THE
FOLLOWING:
1. Installation Work And Electrical Wiring Must Be Done
By Qualified Person(s) In Accordance With All Applicable Codes And Standard, Including Fire Rated Constructions.
2. When Cutting Or Drilling Into The Wall Or Ceiling, Do
Not Damage Electrical Wiring And Other Hidden Utilities.
3. Never Place A Switch Where It Can Be Reached From
A Tub Or Shower.
4. Use This Unit Only In The Manner Intended By The
Manufacturer. If You have Questions, Contact The Manufacturer.
5. Before Servicing Or Cleaning Unit, Switch Power Off At
Service Panel And Lock Service Panel To Prevent
Power From Being Switched on Accidentally.
6. If This Unit Is To Be Installed Over A Tub Or Shower, It
Must Be Marked As appropriate For The Application
and be connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
Choosing a Location
Choosing the correct location for the air cleaner affects the
overall performance of the unit. The bidirectional airflow
pattern must flow into the longest reaches of the zone being
cleaned. See Fig. 2
NOTE: The F111U Has Not Been
Investigated For Use In Fire Resistance
Rated Construction.
CLEANING FOOTPRINT
F111 U
2
CORRECT
1
INCORRECT
Fig. 2. Correct positioning of the air cleaner
for optimum cleaning.
The air cleaner is designed to be suspended centrally in a
space and mounted into or on a ceiling. The cleaning footprint
of the air cleaner is rectangular with air patterns that move
clean air to the corners of the area while drawing contaminated
air up from the center of the area. See Fig. 2.
When multiple air cleaners are installed, position them so the
areas to be cleaned are equal. Consider that the air throw in
one direction is approximately 50 ft (15m). .
CEILING
FLOOR
A12652A
368-0275-2
Page 4
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
IMPORTANT
Never hang the air cleaner higher than 16 ft (5m)
above the floor.
INSTALLATION
WARNING
Explosion Hazard Possible.
Can cause personal injury or equipment damage.
Do not install or use the F111U air cleaner where there
is any danger of gas, vapor or dust explosion.
IMPORTANT
This air cleaner has not been investigated for use in
the ceilings of fire-resistant assemblies.
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Never look at lamps while illuminated.
Only view illumination using light indicator on lamp
knob.
IMPORTANT
Do not attempt to alter physical characteristics of
F1 1 1U. Do not remove any light baffles or attempt to
override lid interlock switch.
Do not attempt to bypass interlock switch in mounting
holes of UV base unit.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Unpack the Air Cleaner
Check that all components are included. The unit consists of:
• cabinet and grille/door assembly.
• High-efficiency media filter.
• Pre-filter.
• Two ultraviolet base modules.
• Latches (2)
• 3-speed switch module
• Literature.
Make Opening (for Mounting in a Drop Ceiling)
1. Size the opening to fit the air cleaner cabinet as closely
as possible.
2. Frame the opening to provide adequate support for the
cabinet.
3. Be sure the cabinet fits snugly in the opening; allow no
more than 1/4 in. (6 mm) from the opening to each side
of the cabinet.
4. Provide access through ceiling adjacent to air cleaner
for UV lamp access.
5. Cover this opening with an easily-removable panel.
6. Cover the framing and any unused portion of the open-
ing with wallboard, plywood, or other material and finish
to match the ceiling.
Electrical Hookup
All wiring must comply with applicable codes and ordinances.
The power source must agree with the model type: 120V,
60 Hz or 230V, 50 Hz.
CAUTION
Electrical Hazard.
Can cause personal injury or equipment damage.
Turn off power before installing or servicing the air
cleaner.
IMPORTANT
The F111U was carefully designed to assure no
unsafe levels of UV light leave the unit. The slight
glow of light at the air vents is not harmful.
IMPORTANT
Stand on a stable platform when working with the air
cleaner.
When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
1. Locate the prepunched hole in the side of the cabinet.
2. Remove the prepunched hole connection box cover
plate.
3. Refer to Fig. 3 for typical electrical diagrams.
WARNING
Risk of Fire or Electric Shock.
Can cause personal injury or equipment damage.
Use only Honeywell 190097C Remote Speed Switch
(3-speed models only) to regulate air cleaner speed.
Using a different speed switch may void the warranty.
IMPORTANT
• Be sure the air cleaner is grounded for correct
operation and safety.
• Canadian installation: NEVER install in ceilings with
thermal insulation value greater than R-40.
68-0275-2 Revised 3-094
Page 5
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
VIO (HIGH)
SWITCH
BLU (MED)
RED (LOW)
BRN
WHT
GRN
WIRE CONNECTOR
BLK
LID INTERLOCK
SWITCH
WIRE CONNECTOR
L
N
G
REMOTE 3-SPEED
EXTERNAL
WIRING BY
INSTALLER
Fig. 3. Typical F111U 120V, 60 Hz or
230, 50 Hz wiring diagram.
Mounting Air Cleaner Cabinet
The air cleaner can be mounted in a drop ceiling system or
hung in an open area. Both mounting methods require the air
cleaner to be level and positioned with the grill facing down for
correct operation.
1. Remove the lid (grill) from the carton and set it aside.
2. Remove all filters.
3. Fit the cabinet into the prepared ceiling opening or
position on the ceiling.
4. Use the four 3/8 x 16T internal nuts (one at each corner)
to fasten the cabinet to a structural support (bar joist,
concrete slab or timber framing). See Fig. 4.
NOTES:
• All external hardware is furnished by the installer.
• When using the suspension system of mounting,
be sure to include a means for leveling adjustment after installation.
• Never rest the air cleaner on the T-bar.
5. Level the air cleaner.
6. Install two ultraviolet base modules on the si des of the
F111U cabinet using the two no.10 x 2 in. phillips head
sheet metal screws provided (predrilled holes for the
mounting screws are provided on the cabinet).
7. Tighten the screws securely (12 to 14in-lb) to seal the
space between the base and the cabinet.
8. Connect the UV base module power cords to the connectors provided in the side of the F111U.
CAPACITOR
BRN
BLK
BLK
WHT
WHT
WHT
WHT
GRN
GRN
TOP OF METAL CABINET
THREADED
ROD
JAM
NUT
CHAIN
EYEBOLT
JAM NUT
3/8 IN. X 16T
OR USING OPTIONAL "Z"
TOP OF METAL CABINET
BOTTOM FLANGE AGAINST
UNDERSIDE OF TEES
FACTORY WIRING
MOTOR
UV MODULES
GRN
A20929A
BRACK
ETS
"Z" BRACKET (4)
NOTE:
FASTEN SECURELY TO STRUCTURAL
SUPPORT SYSTEM, I.E. BAR JOIST,
CONCRETE SLAB OR TIMBER FRAMING.
HEX BOLT
LOCK
WASHER
CEILING
TEE
BOTTOM VIEW OF
UNIT WITHOUT
LID ASSEMBLY
M10892
Fig. 4. Fasten cabinet to a structural support.
568-0275-2
Page 6
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
• Disconnect power to air cleaner at fuse or breaker
CAUTION
Breakable Glass Hazard.
Can cause personal injury.
Be careful when inserting lamps(s) into lamp base.
Wear protective gloves when handling lamp(s).
MERCURY NOTICE
This device contains mercury in the sealed ultraviolet
lamp(s).
Do not place your used lamp(s) in the trash.
Dispose of properly.
CAUTION
Broken Lamp Cleanup Hazard.
Do not use household vacuum cleaner.
Sweep debris into a plastic bag and dispose of
properly.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of old lamp(s).
9. Insert the lamp into the UV base module with the lamp
light indicator at the five o’ clock position. Do not touch
the lamp surface with your hands. Fully insert the ultraviolet lamps into the base modules.
10. Rotate the lamp clockwise until it snaps into place with
the lamp indicator light aligned with the raised button on
the unit grill.
11.Install the high-efficiency main filter. Note airflow direction arrows if present. Install the filter with the direction
arrow pointing towards the motor / blower.
12. Lock and secure the high-efficiency particle filter into
place by closing both latches.
IMPORTANT
Do not touch the pleated filter media. Handle only the filter
frame to prevent damage to the filter media.
13. Install the prefilter in the air cleaner grill. Note the air
flow direction arrows and install the filter with arrows
pointing towards the high-efficiency main filter.
Remote 3 Speed Wall Switch
The 190097C Remote Wall Switch Assembly allows control of
the F111U model air cleaners from a a location separate from
the air cleaner. The assembly includes a remote switch with
an outlet box cover, outlet box, extension ring, and a wire
harness. Wiring to connect the remote switch and air cleaner
must be furnished separately. More detailed instructions
included with 190097C Remote 3 Speed Wall Switch.
CAUTION
• This installation to be performed only by a qualified
installer.
• All wiring to comply with local electrical codes.
A100001
10. Fold wires into box and mount remote switch on outlet
11.On the air cleaner remove two screws on wiring com-
12. Run six conductor, color coded, 18 gauge wires from
13. Connect four wires on air cleaner to remote switch lead
14. Connect one wire on air cleaner to power supply wire
15. Connect the ground wire from the remote switch to a
16. Fold wires into wiring compartment. Replace wiring
17. Turn on power to air cleaner at fuse or breaker.
before beginning work. Failure to do so can result in
shock hazard endangering equipment and personal
safety of installer.
• Only one air cleaner can be connected to a remote
switch
1. Disconnect power to air cleaner.
2. Mount 4” x 4” outlet box at desired remote location.
3. Attach 3/4” extension ring to outlet box.
4. Run six conductor, color-coded, 18-gauge wires from
the remote switch location to the air cleaner.
5. Use four wire nuts to connect four color-coded, lead
wires on the remote switch to four color-coded wires
from the air cleaner. (Red, Blue, Violet, Brown)
6. Use one wire nut to connect white color-coded, lead
wire from the air cleaner to single color-coded wire from
the power supply. (White)
BLACK
Fig. 5. Wiring 3-Speed Remote Switch
7. Connect the ground wire from the power supply to a
ground stud of the outlet box.(Green)
8. Connect the ground wire from the air cleaner to the
ground stud of the outlet box.(Green)
9. Use one wire nut to connect the black color-coded, lead
wire on the remote switch to the black color-coded wire
from the power supply.
box. Leave switch in OFF position.
partment cover and open
the remote switch through the air cleaner access open-
ing into the wiring compartment. Strip ends of remote
switch lead wires
wires with wire nuts following color code used at remote
switch. (Red, Blue, Violet, Brown)
with a wire nut following color code used at remote
switch. (White)
ground stud of the wiring compartment cover.(Green)
compartment cover.
68-0275-2 Revised 3-096
Page 7
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
18. Check operation by turning air cleaner at HIGH,
MEDIUM, and LOW. Note
that only the remote switch
will operate the air cleaner.
Lid Assembly
The F111U lid is held in place by two separable hinges, two
spring loaded plungers, and a safety catch. To install the
spring loaded plungers on the lid follow these steps:
1. Pull the plunger back and twist a quarter turn to reveal
the wrench flat on the body of the spring loaded plunger
(see Fig 6.)
2. Turn the threaded barrel out of the spring plunger.
3. Insert the threaded barrel through the hole in the lid and
turn the spring loaded plunger onto it.
4. Tighten the assembly with wrenches.
5. Repeat steps 1 through 4 for the second plunger.
6. Install the lid to the air cleaner, positioning the lid in the
open position and engaging the hinge pins. Then move
the lid to the side to fully engage the hinge pins.
7. To secure lid to air cleaner, slide safety catch to on
position.
8. Swing the lid to the closed position and pull back on the
spring loaded plungers, then releasing to lock them into
place.
9. Verify that the lid is securely attached at the hinge pins
and at the spring loaded plungers.
WRENCH FLAT
THREADED
BARREL
installed. Do not attempt to override the interlock
switch.
Opening/Closing the Lid
To open the lid, pull the spring loaded plungers back to
disengage the plunger. Carefully swing the lid open on the
hinges while supporting the filter. To close, swing the lid into
the closed position and engage the plungers.
Removing /Replacing the Lid
IMPORTANT
The lid is heavy. Make sure that it is supported
before removing.
To remove the lid, swing it into the open positio n. Slide safety
catch to off position. Move the lid to the side to disengage the
hinge pins. Reverse the procedure to replace the lid. Make
sure safety catch is in safe(on) position.
OPERATION
The F111U In-Ceiling Media Air Cleaner has been engineered
to improve indoor air quality for health care, commercial, and
industrial applications. The filters are the most practical and
effective filtering system for removing atmospheric dust,
pollens, bacteria, viruses, mold spores, smoke, and other
airborne contaminants. Refer to Fig. 7.
WRENCH
FLAT
SPRING
LOADED
PLUNGER
M11994
Fig. 6. Lid assembly.
WARNING
UV Light Hazard.
Accidental exposure to UV light can cause
temporary or permanent loss of vision.
F1 11U lid is designed to operate an interlock switch to
prevent UV light operation if lid is not correctly
CEILING LINE
AIR IN
UV
MODULE
CLEAN AIR
DISCHARGE
A12651A
UV
MODULE
CEILING LINE
CLEAN AIR
DISCHARGE
AIR IN
BLOWER
MOTOR
AIR VENTS
INTAKE
PARTICLE FILTER
PREFILTER
Fig. 7. F111U Series air cleaner operation.
The air cleaner is either operating (high, medium, or low) or
off. Even when the area is unoccupied, the air cleaner can be
operated continuously to prevent buildup of airborne
contaminants.
The minimum recommended air exchange rate is 2.5 times
per hour. In a heavily contaminated area, up to 15 air
exchanges per hour (for example health care applications)
can be necessary. The factors that determine what the rate of
air exchange should be are:
• generation rates of the various pollutants;
• concentration level of the pollutants;
• desired contamination reduction level.
Airborne contaminants will always be present in the air where
contaminant generations take place. Air cleaning systems and
ventilators do not eliminate airborne contaminants, they
768-0275-2
Page 8
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
reduce the excessive accumulation of the contaminants. To
eliminate the contamination, the source of contamination must
be removed.
Local, Federal and professional ventilation engineering
standards and codes prescribe minimum ventilation rates to
dilute air contamination in specific applications. The
ventilation rates usually assume the injection of outdoor air or
conditioned air (HVAC) measured as air exchange rate. The
use of the F111U air cleaner to comply with ventilation
requirements is an acceptable alternative to ventilation with
outdoor air. However, at least 20% of a specified ventilation
rate or code must be derived from outdoor air or conditioned
air. The F111U air cleaner filtered and recirculated air can be
the remaining 80%.
Verify F111U Operation
1. Turn on power to the Air Cleaner and check for proper
operation for 2 to 3 minutes.
2. Listen for a smooth, powerful blower sound and air
discharging from both ends of the air cleaner.
3. The installer should verify that the ultraviolet lamps are
operating by viewing the lamp indicator on the lamp
knob.
IMPORTANT
Do not attempt to look directly into the unit to see the
illuminated ultraviolet lamps.
1. Slowly open the lid, supporting the lid so the filters do
not fall out.
2. Remove the dirty prefilter.
3. Install the new prefilter in the air cleaner lid noting direc-
tion of airflow arrow.
4. Close and latch the lid.
High Efficiency Particle Filter
The high efficiency particle filter collects particulates that pass
through the prefilter. The filter life is typically from 1 to 2 years.
There is decreased air quality and a pulsing sound when the
filter is filled with contaminants. The filter must be replaced
when the pulsing sound is noticed.
NOTE: The filter must be replaced. Washing, vacuuming or
reverse air blasting does not clean it.
1. Slowly open lid, supporting it so the filters do not fall out.
2. Open both filter securing latches with both hands. Slide
the filter toward you.
3. Place spent filter in a plastic trash bag and dispose of
properly.
4. Inspect the motor brackets for loose fasteners and
tighten as necessary.
5. Install the new filter noting the direction of airflow arrow.
IMPORTANT
Do not touch the pleated filter media. Handle only the
filter frame to prevent damage to the filter media.
SERVICE
CAUTION
Electrical Hazard.
Can cause personal injury or equipment damage.
Turn off power before installing or servicing the air
cleaner.
IMPORTANT
Be sure to change filters as recommended to prevent
reduced airflow in the air cleaner. Stand on a stable
platform when working with the air cleaner.
CAUTION
All Filters must be provided from Air-Pure
Systems to maintain U.L. Certification and
Warranty.
The high-efficiency particle filter life ranges from 6 to 24
months with 12 to 24 months as an average. More frequent
replacement may be neccessary in some applications
depending on the load of the filter.
Prefilter
The disposable prefilter collects large dust particulates and
lint- type airborne fibers. Check the filter every two weeks to
determine the replacement frequency. The filters need
replacement when a pulsing sound occurs, .
6. Lock and secure the high efficiency particle filter into
place by closing both latches.
7. Close and latch the lid.
Servicing UV Lamps
CAUTION
Breakable Glass Hazard.
Can cause personal injury.
Be careful when inserting lamps(s) into lamp base.
Wear protective gloves when handling lamp(s).
MERCURY NOTICE
This device contains mercury in the sealed ultraviolet
lamps(s). Do not place your used lamp(s) in the trash.
Dispose of properly.
Broken Lamp Cleanup.
Do not use a household vacuum.
Sweep debris into plastic bag and dispose of properly.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of old lamp(s).
CAUTION
UV Lamp Burn Hazard.
Harmful to bare skin.
Can cause severe burns.
Allow lamps to cool 15 minutes before servicing.
68-0275-2 Revised 3-098
Page 9
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
Replace the lamps every 12 months to maintain peak
performance:
1. Disconnect power to Air Cleaner.
2. Allow lamps to cool for 15 minutes before servicing.
3. Rotate lamp knob counterclockwise and gently pull
knob to remove lamp.
4. Fully insert new lamp into base unit with lamp light
indicator at five o'clock position. Do not touch lamp surface with your hands.
5. Rotate lamp clockwise until it snaps into place with lamp
indicator light aligned with raised button on unit cover.
6. Connect power to Air Cleaner. Ve rify that ultraviolet
lamps are operating by viewing lamp indicator on lamp
knob. Do not attempt to look directly into unit to see
illuminated ultraviolet lamps.
NOTE: The lamps are the only field-serviceable parts in the
UV lights.
NOTES
968-0275-2
Page 10
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
PARTS LIST
Refer to Fig. 8 and Table 3 for replacement part information.
T able 3. Replacement Parts.
Fig.
Reference No.DescriptionPack QtyOrder Number
1Replacement UV Bulb (requires 2)132007346-001
2UV Base Module (includes handle and bulb)132007337-002
3Blower wheel, Se ries 3132002285
4Motor capacitor; 120V, 60 Hz, Series 3132000265-001
Motor capacitor; 230V, 50 Hz, Series 3132000549-001
5Motor; 120 V, 3-Speed, 60 Hz, Series 3132002415-004
Motor; 230V, 3-Speed, 50Hz, Series 3132002415-005
699.97% HEPA media filter, 4.5”, Series 3132000204-002
95% hospital grade filter132000203
95% ASHRAE particle filter150004739-001
7Prefilter (disposable)132002307
8Lid assembly with hinges, latches, and actuator in White Color, 132002308-004
Parts not shown in Fig. 8.
Remote Wall 3-Speed Switch, Series 31190097C
Lid Interlock switch1203324
OPTIONAL Parts not shown in Fig. 8
Motor mount bracket132000260
Motor maintenance grommet set332000261
Z Sidemount Bracket Kit432002353
Spring Loaded Plunger232002278
Shroud Kit (required when F111U in Plenum Air - includes three
shrouds plus hardware).
Lid assembly with hinges and latches in Black Color132002308-005
132007643-001
68-0275-2 Revised 3-0910
Page 11
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
CABINET
ASSEMBLY
UV LAMPS (2 REQUIRED)
1
REPLACEMENT LAMP
UV BASE MODULE (INCLUDES LAMP)
2
BLOWER WHEEL
3
MOTOR CAPACITOR
4
5
MOTOR
6
HIGH EFFICIENCY
MEDIA FILTER
DISPOSABLE PREFILTER
7
LID ASSEMBLY WITH
8
HINGES AND LATCHES
A20931A
Fig. 8. Exploded view of F111U Series 3 In-Ceiling Media Air Cleaner components.
1168-0275-2
Page 12
F111U IN-CEILING MEDIA AIR CLEANER WITH ULTRAVIOLET AIR TREATMENT SYSTEM
LIMITED TWO-YEAR WARRANTY
Air-Pure Systems warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service, for a period
of two (2) years from the date of purchase by the original end-user. If at anytime during the warranty period the product is defective or malfunctions, Air-Pure Systems, through the distributor or dealer, from which the product was purchased, or through an authorized warranty repair
station, shall at Air-Pure Systems option, replace or repair the defective product or component.
This warranty does not cover removal or installation costs. This warranty shall not apply if it is shown that the defect or malfunction was caused
by damage which occurred during handling or shipment, improper electrical connections, improper use of the product or abuse.
Air-Pure Systems sole responsibility shall be to repair or replace the product within the terms stated above. AIR-PURE SYSTEMS SHALL NOT
BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING,
DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. (Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.) THE
WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR-PURE SYSTEMS’ EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES,
WHETHER WRITTEN OR ORAL, IMPLIED OR STATUTORY, INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY, WORKMANSHIP, OR FITNESS FOR A PARTICULAR USE.
This warranty gives you specific legal rights and you may have other rights which vary from state to state.
How to make a warranty claim or have questions answered:
Should you have a warranty claim or questions about the warranty policy, contact the distributor or dealer from which you purchased the product
or the authorized warranty repair stations nearest your location.
NOTE:Do not return any products or parts to the factory without a factory issued “Returned Warranty Goods Label” issued by Air Pure Sys-
In the event you or other persons, have any questions concerning the use and care of this product or this warranty please call or write the factory.
Air-Pure Systems
16873 Fish Point Rd. SE
Prior Lake, MN 55372-1714
Phone: (800) 998-1919
Fax: (800) 221-3248
tems.
Air-Pure Systems
16873 Fish Point Rd. SE
Prior Lake, MN 55372-1714
Phone (800) 998-1919
Fax: (800) 221-3248
68-0275-2 Revised 3-09 www.cleanairfacility.com