Honeywell DT7500SN Users Manual

Lowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet Immunity
Lowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet Immunity
Lowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet Immunity
Lowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet Immunity
Lowest Sensitivity: 3 - 5 Steps; Up to 45 kg (100 lb) Pet Immunity
DT7500SN V-PlexTM DUAL TEC
Cover Tamper Switch
Contact AP du capot
Interruttore tamper sul
coperchio
Tamper de la cubierta
Cover Tamper Switch

Motion Sensor - Installation Instructions
5
4
1
OFF
OFF
BOARD
PLACA DE CIRCUITO IMPRESO / REPLACE CIRCUIT
RIPOSIZIONARE IL CIRCUITO / VOLVER A COLOCAR LA
WIRE / CABLAGE / COLLEGAMENTO / CABLEADO / WIRE
ON
REPLACE CIRCUIT BOARD / REMISE EN PLACE DU PCB /
Wide Angle Lens (installed)
Wide Angle Lens (installed)
Wide Angle Lens (installed)
Wide Angle Lens (installed)
Wide Angle Lens (installed)
LOCATION / EMPLACEMENT / POSIZIONAMENTO / LOCALIZACIÓN / LOCATION
W
2
1
With SMB10T
With SMB10T
With SMB10T
With SMB10T
With SMB10T
With SMB10T
10mA
24 VDC,
TAMPER
SMB-10T
Polling Loop
9 - 13VDC
Low Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet Immunity
Low Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet Immunity
Low Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet Immunity
Low Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet Immunity
Low Sensitivity: 2 - 4 Steps; Up to 23 kg (50 lb) Pet Immunity
ON
2
1
W
W
T T
V­V+
Pet Immune Lens (included)
Pet Immune Lens (included)
Pet Immune Lens (included)
Pet Immune Lens (included)
Pet Immune Lens (included)
6
a
APPROPRIATE SETTINGS
E SELEZIONARE LE IMPOSTAZIONI APPROPRIATE / IDENTIFICAR LOS COMPONENTES Y SELECCIONAR LA CONFIGURACIÓN ADECUADA / IDENTIFY COMPONENTS AND SELECT
IDENTIFY COMPONENTS AND SELECT APPROPRIATE SETTINGS / IDENTIFICATION DES COMPOSANTS ET SÉLECTION DES PARAMÈTRES APPROPRIÉS / IDENTIFICARE I COMPONENTI
OFF
T T
-
+
Medium Sensitivity: 1 - 3 Steps; No Pet Immunity
Medium Sensitivity: 1 - 3 Steps; No Pet Immunity
Medium Sensitivity: 1 - 3 Steps; No Pet Immunity
Medium Sensitivity: 1 - 3 Steps; No Pet Immunity
Medium Sensitivity: 1 - 3 Steps; No Pet Immunity
ON
Look-Down Mask (install as shown when using Pet Immune Lens)
Look-Down Mask (install as shown when using Pet Immune Lens)
Look-Down Mask (install as shown when using Pet Immune Lens)
Look-Down Mask (install as shown when using Pet Immune Lens)
2
1
High Sensitivity: 1 - 2 Steps; No Pet Immunity
High Sensitivity: 1 - 2 Steps; No Pet Immunity
High Sensitivity: 1 - 2 Steps; No Pet Immunity
High Sensitivity: 1 - 2 Steps; No Pet Immunity
High Sensitivity: 1 - 2 Steps; No Pet Immunity
Look-Down Mask (install as shown when using Pet Immune Lens)
The sensor will respond to all communications with the
host panel armed or disarmed.
The sensor will not transmit or indicate intrusion alarms
when the panel is disarmed; in the armed state, the sensor
will respond to all communications to or with the host panel.
If installed with a Standard V-Plex
TM
Panel:
If installed with a Smart V-Plex
TM
Panel:
LED
ON
234
1
OFF
High Sensitivity
Pulse Count 1
ON
1
OFF
Pulse Count 2
Low Sensitivity
5
Microwave Walk Test ON
Anti-Mask ON
LED Enabled
234
5
LED Disabled
Microwave Walk Test OFF
Anti-Mask OFF
25%
100%
Regolazione della portata
Ajuste del rango de detección
Range Adjustment
50%
75%
Range Adjustment
Réglage de la portée hyper
2.1 - 2.4 m
(7 - 8 ft)
2
OPEN / OUVERTURE / APERTURA / APERTURA / OPEN
1
OFF
ON
2
1
3
High Sensitivity
Pulse Count 1
LED Enabled
Microwave Walk Test ON
Anti-Mask ON
Pulse Count 1
Microwave Walk Test ON
High Sensitivity
LED Enabled
Anti-Mask ON
High Sensitivity
Pulse Count 1
LED Enabled
Microwave Walk Test ON
Anti-Mask ON
Pulse Count 1
Microwave Walk Test ON
High Sensitivity
LED Enabled
Anti-Mask ON
2
ON
234
1
OFF
Pulse Count 2
Low Sensitivity
LED Disabled
Microwave Walk Test OFF
respond to all communications with the host panel, armed or
disarmed.
in the armed state, the sensor will respond to all communications
to or with the host panel.
If installed with a Standard V-Plex
5
Anti-Mask OFF
transmit or indicate intrusion alarms when the panel is disarmed;
<PT> If installed with a Smart V-Plex
ON
234
1
OFF
Pulse Count 2
Low Sensitivity
LED Disabled
Microwave Walk Test OFF
respond to all communications with the host panel, armed or
disarmed.
in the armed state, the sensor will respond to all communications
to or with the host panel.
If installed with a Standard V-Plex
5
Anti-Mask OFF
transmit or indicate intrusion alarms when the panel is disarmed;
<ES> If installed with a Smart V-Plex
ON
234
1
OFF
Pulse Count 2
Low Sensitivity
LED Disabled
Microwave Walk Test OFF
respond to all communications with the host panel, armed or
disarmed.
in the armed state, the sensor will respond to all communications
to or with the host panel.
If installed with a Standard V-Plex
<IT> If installed with a Smart V-Plex
transmit or indicate intrusion alarms when the panel is disarmed;
ON
5
OFF
Anti-Mask OFF
disarmed.
234
1
Pulse Count 2
Low Sensitivity
If installed with a Standard V-Plex
respond to all communications with the host panel, armed or
5
LED Disabled
Microwave Walk Test OFF
Anti-Mask OFF
transmit or indicate intrusion alarms when the panel is disarmed;
in the armed state, the sensor will respond to all communications
to or with the host panel.
<FR> If installed with a Smart V-Plex
(22-16 AWG)
0.3-1.3mm
2
Rear T amper Breakaway Tab
3
Rear T amper Breakaway Tab
Rear T amper Breakaway Tab
Rear T amper Breakaway Tab
Rear T amper Breakaway Tab
MOUNT / INSTALLATION / MONTAGGIO / MONTAJE / MOUNT
TM
Panel: The sensor will
TM
Panel: The sensor will not
TM
Panel: The sensor will
TM
Panel: The sensor will not
TM
Panel: The sensor will
TM
Panel: The sensor will not
TM
Panel: The sensor will
TM
Panel: The sensor will not
Use these holes when
mounting to a standard
U.S. electrical junction box
/
!
!b FOR PET IMMUNITY
!!
Mount the center of the sensor at 2.3 m (7.5 feet) high.
Set the sensor to the Lowest or Low sensitivity (see step 6a).
Install Pet Immune lens (5-532-489-01 - see Lens Change
Instructions on page 3).
Install the look-down mask (see Step 6a).
Install the sensor where pets cannot come within 1.8 m (6 ft) of the
sensor by climbing on furniture or other objects.
Aim the sensor away from stairways, furniture or other objects that can be climbed on by pets.
TEST the installation site to determine the exact level of attainable animal immunity.
Note: Pet immunity characteristics for this sensor have not been verified by Underwriter’s Laboratories, Inc.
"
" PROGRAM SENSOR SERIAL NUMBER ID
""
Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure. The unique serial number can be found on a bar code label on the sensor PCB. The serial number can be entered into the control panel in one of the following methods:
A. Download it through software (Zone definition screen of Compass
software). This is recommended for large installations and installations where foot traffic cannot be controlled.
B. Enter the number through the keypad at the “INPUT S/N” prompt
during manual zone programming. E n sure n o ot her pol li n g de vi ces are activated when manually entering the sensor serial number.
C. Activate the sensor twice while at the “INPUT S/N” prompt during
manual zone programm i ng.
To enter the sensor’s serial number for option B or C:
Refer to the control panel’s manual for programming instructions. For all V-Plex
06” for SL (Serial Polling Device) at the “INPUT TYPE” prompt. For Smart V-Plex
At the “INPUT S/N” prompt, eith er ent er the serial num b er (an d “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), the n w a it 3-6 seco nds an d faul t th e sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enrolled. If a “1” does not appear under the “L” on the zone summary screen, press [*] and enter the loop number manually at the next screen.
#
# NORMAL WALK TEST – 10 MINUTES
##
Normal walk test mode activates after power up mode and remains active for 10 minutes. For an additional 10 minutes of walk test time, remove and replace the front cover. In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting. [Note: if the panel is not a Smart V-Plex enabling the LED (DIP switch 3 = ON.]
Walk through the detection area and observe the LED. If necessary, adjust the microwave range, pulse count or sensitivity
setting. (For LED activation meaning, refer to the LED Indicator table below.)
TM
panels, enter INT FOLLOWER 04 for the Zone Type and
TM
panels press “1” (Yes) for SMART CONTACT.
TM
panel, walk test can also be done by
DT7500SN V-PlexTM DUAL TEC

Motion Sensor - Installation Instructions
!
!b FOR PET IMMUNITY <FRENCH>
!!
Mount the center of the sensor at 2.3 m (7.5 feet) high.
Set the sensor to the Lowest or Low sensitivity (see step 6a).
Install Pet Immune lens (5-532-489-01 - see Lens Change
Instructions on page 3).
Install the look-down mask (see Step 6a).
Install the sensor where pets cannot come within 1.8 m (6 ft) of the
sensor by climbing on furniture or other objects.
Aim the sensor away from stairways, furniture or other objects that
can be climbed on by pets.
TEST the installation site to determine the exact level of attainable
animal immunity.
Note: Pet immunity characteristics for this sensor have not been verified by Underwriters Laboratories, Inc.
"
" PROGRAM SENSOR SERIAL NUMBER ID
""
Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure. The unique serial number can be found on a bar code label on the sensor PCB. The serial number can be entered into the control panel in one of the following methods:
A. Download it through software (Zone definition screen of Compass
software). This is recommended for large installations and installations where foot traffic cannot be controlled.
B. Enter the number through the keypad at the INPUT S/N prompt
during manual zone programming. En sur e n o other polling devices are activated when manually entering the sensor serial number.
C. Activate the sensor twice while at the INPUT S/N prompt during
manual zone programm i ng.
To enter the sensor’s serial number for option B or C:
Refer to the control panels manual for programming instructions. For all V-Plex
06 for SL (Serial Polling Device) at the INPUT TYPE prompt. For Smart V-Plex
At the INPUT S/N prompt, either enter the seri al num b er (an d “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), the n w a it 3-6 seco nds an d faul t th e sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enroll ed. If a “1” does not appear under the L on the zone summary screen, press [*] and enter the loop number manually at the next screen.
#
# NORMAL WALK TEST 10 MINUTES
##
Normal walk test mode activates after power up mode and remains active for 10 minutes. For an additional 10 minutes of walk test time, remove and replace the front cover. In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting. [Note: if the panel is not a Smart V-Plex enabling the LED (DIP switch 3 = ON.]
Walk through the detection area and observe the LED. If necessary, adjust the microwave range, pulse count or sensitivity
setting. (For LED activation meaning, refer to the LED Indicator table below.)
TM
panels, enter INT FOLLOWE R 04 fo r the Zo ne T ype and
TM
panels press 1 (Yes) for SMART CONTACT.
TM
panel, walk test can also be done by
!
!b FOR PET IMMUNITY <ITALIAN>
!!
Mount the center of the sensor at 2.3 m (7.5 feet) high.
Set the sensor to the Lowest or Low sensitivity (see step 6a).
Install Pet Immune lens (5-532-489-01 - see Lens Change
Instructions on page 3).
Install the look-down mask (see Step 6a).
Install the sensor where pets cannot come within 1.8 m (6 ft) of the
sensor by climbing on furniture or other objects.
Aim the sensor away from stairways, furniture or other objects that
can be climbed on by pets.
TEST the installation site to determine the exact level of attainable
animal immunity.
Note: Pet immunity characteristics for this sensor have not been verified by Underwriters Laboratories, Inc.
"
" PROGRAM SENSOR SERIAL NUMBER ID
""
Each sensor has a factory-assigned serial number which must be entered into the control panel during the zone programming procedure. The unique serial number can be found on a bar code label on the sensor PCB. The serial number can be entered into the control panel in one of the following methods:
A. Download it through software (Zone definition screen of Compass
software). This is recommended for large installations and installations where foot traffic cannot be controlled.
B. Enter the number through the keypad at the INPUT S/N prompt
during manual zone programming. En sur e n o ot her polling devices are activated when manually entering the sensor serial number.
C. Activate the sensor twice while at the INPUT S/N prompt during
manual zone programm i ng.
To enter the sensor’s serial number for option B or C:
Refer to the control panels manual for programming instructions. For all V-Plex
06 for SL (Serial Polling Device) at the INPUT TYPE prompt. For Smart V-Plex
At the INPUT S/N prompt, either enter the seri al num b er (an d “1” for the loop number), or fault the sensor (wave your hand in front of the sensor or activate the tamper), the n w a it 3-6 seco nds an d faul t th e sensor again. The keypad will beep after each fault to confirm the signal. The sensor should now be enroll ed. If a “1” does not appear under the L on the zone summary screen, press [*] and enter the loop number manually at the next screen.
#
# NORMAL WALK TEST 10 MINUTES
##
Normal walk test mode activates after power up mode and remains active for 10 minutes. For an additional 10 minutes of walk test time, remove and replace the front cover. In walk test mode, the LED is always enabled, regardless of the LED DIP switch setting. [Note: if the panel is not a Smart V-Plex enabling the LED (DIP switch 3 = ON.]
Walk through the detection area and observe the LED. If necessary, adjust the microwave range, pulse count or sensitivity
setting. (For LED activation meaning, refer to the LED Indicator table below.)
TM
panels, enter INT FOLLOWER 04 for the Zone Type and
TM
panels press 1 (Yes) for SMART CONTACT.
TM
panel, walk test can also be done by
$
$ MICROWAVE WALK TEST – 10 MINUTES
$$
1. Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF.
2. Set Range Adjustment potentiometer to 25% and replace the cover.
3. Walk through the detection area and observe the LED.
4. If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activati o n mea nin g, refer to t he LED Indic at or table below.)
Indicator LEDs
Condition Indicator LED
Power Up
Normal Walk Test Red ON for 3 seconds if Alarm
Microwave Walk Test Red ON if Microwave is set too high
Trouble or Anti-Mask Fast Blinking Red (LED Enabled
Slow Blinking Red (will finish within 60 seconds)
Yellow ON for 2 seconds if Microwave event detected Green ON for 2 seconds if PIR event detected
Green ON if Microwave is set correctly OFF if Microwave is set too low
or Disabled)
%%%% ANTI-MASK
When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) wh en a variet y of mate rials an d reflective objects are placed in front of it. Follow the mounting guidelines in step 1 to avoid false mask alarms.
To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensors view. The sensor will clear an anti-mask condition when three valid alarms are detected. After a mask condition is cleared, fully walk test the required detection area.
TROUBLESHOOTING
RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition. If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present.
Solution: Momentarily power down the sensor. If the trouble does not clear, replace the sensor. (Please ch e ck the powe r, all wiri ng an d that the sensor is not masked before replacing the sensor.)
$
$ MICROWAVE WALK TEST 10 MINUTES
$$
1. Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF.
2. Set Range Adjustment potentiometer to 25% and replace the cover.
3. Walk through the detection area and observe the LED.
4. If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activati o n mea nin g, refer to t he LED Indic at or table below.)
Indicator LEDs
Condition Indicator LED
Power Up
Normal Walk Test Red ON for 3 seconds if Alarm
Microwave Walk Test Red ON if Microwave is set too high
Trouble or Anti-Mask Fast Blinking Red (LED Enabled
Slow Blinking Red (will finish within 60 seconds)
Yellow ON for 2 seconds if Microwave event detected Green ON for 2 seconds if PIR event detected
Green ON if Microwave is set correctly OFF if Microwave is set too low
or Disabled)
%%%% ANTI-MASK
When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it. Follow the mounting guidelines in step 1 to avoid false mask alarms.
To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensors view. The sensor will clear an anti-mask condition when three valid alarms are detected. After a mask condition is cleared, fully walk test the required detection area.
TROUBLESHOOTING
RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition. If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present.
Solution: Momentarily power down the sensor. If the trouble does not clear, replace the sensor. (Please ch e ck the powe r, all wiri ng an d that the sensor is not masked before replacing the sensor.)
DETECTION PATTERNS / COUVERTURE DE DETECTION / DIAGRAMMA DI COPERTURA / PATRON DE DETECCIÓN / DETECTION PATTERNS
50 / 15m Wide Angle Lens (P/N 5-532-439-01 Installed) Top View / VUE DE DESSUS / Vista in pianta / VISTA DESDE ARRIBA / Top View
$
$ MICROWAVE WALK TEST 10 MINUTES
$$
1. Set the Microwave Walk Test DIP switch to ON, or toggle it ON and OFF.
2. Set Range Adjustment potentiometer to 25% and replace the cover.
3. Walk through the detection area and observe the LED.
4. If necessary, adjust the potentiometer until desired detection range is obtained. (For LED activati o n mea nin g, refer to t he LED Indic at or table below.)
Indicator LEDs
Condition Indicator LED
Power Up
Normal Walk Test Red ON for 3 seconds if Alarm
Microwave Walk Test Red ON if Microwave is set too high
Trouble or Anti-Mask Fast Blinking Red (LED Enabled
Slow Blinking Red (will finish within 60 seconds)
Yellow ON for 2 seconds if Microwave event detected Green ON for 2 seconds if PIR event detected
Green ON if Microwave is set correctly OFF if Microwave is set too low
or Disabled)
%%%% ANTI-MASK
When DIP switch 5 is set to ON, the sensor indicates a mask condition (see LED Indicator table above) when a variety of materials and reflective objects are placed in front of it. Follow the mounting guidelines in step 1 to avoid false mask alarms.
To clear a mask condition, visually inspect the sensor and remove any materials blocking the sensors view. The sensor will clear an anti-mask condition when three valid alarms are detected. After a mask condition is cleared, fully walk test the required detection area.
TROUBLESHOOTING
RED LED flashing rapidly during normal operation indicates a trouble or an anti-mask condition. If the sensor is not masked (see step 10), either a microwave, PIR, or temperature compensation fault is present.
Solution: Momentarily power down the sensor. If the trouble does not clear, replace the sensor. (Please ch e ck the powe r, all wiri ng an d that the sensor is not masked before replacing the sensor.)
LENS MASKING / LENS MASKING / LENS MASKING / LENS
MASKING / LENS MASKING
TOP
25 / 35FT
5-532-489-01
Side View
VUE DE COTE / Vista in sezione / VISTA
LATERAL / Side View
- Page 2 -
Loading...
+ 2 hidden pages